Home / Charts / Goodman / Amana furnace codes

Goodman / Amana GRVS80 / GRVS96 Ultra-Low NOx Furnace Codes

Applies to: Goodman / Amana GRVS80 / GRVS96 Ultra-Low NOx (R-32 era single-stage, variable-speed communicating; also ARVS80, ARVS96, CDVS96, DR80SC, DR96SC, DD96SC). Three-character seven-segment display on the integrated control.

Covers the Goodman GRVS80 and GRVS96 and Amana ARVS80 and ARVS96 Ultra-Low NOx variable-speed furnaces (RS6621303 Rev. 2, pp. 31-35, and RS6612303 Rev. 1, pp. 34-38, which also covers CDVS96*U). Daikin's DR80SC*U (RSD6621303 Rev. 2, pp. 32-36) and DR96SC*U/DD96SC*U (RSD6612303 Rev. 1, pp. 33-38) service instructions list the same codes and fault descriptions. The older R-410A GMVS96 U and GMVS80 U have their own charts.

CodeMeaningWhat to check
IdLIdle: normal operation.
nonENo display: no 120 VAC to the furnace or no 24 V to the integrated control.Breaker, manual disconnect and door switch; 120 VAC on the transformer primary and 24 V on the secondary; 24 V wires to the 12-pin harness. Replace the control only after the wiring checks out.
Eb0Circulator blower motor not running when it should be.Loose motor power leads; open circuit or loose wiring at the inductor (3/4 and 1 HP models); failed motor.
Eb1The control has lost communication with the circulator blower motor.Loose wiring at the motor leads; check the motor and the control and replace whichever has failed.
Eb2Blower motor horsepower in the shared data set doesn't match the motor.Make sure the motor horsepower is the one specified for the model; make sure the shared data set is correct and re-populate it with the CoolCloud HVAC app. The code clears once they match.
Eb3Blower motor running in a power, temperature or speed limiting condition; the furnace runs at reduced performance with less airflow.Blocked filters, restrictive or undersized ductwork (all registers open), high ambient temperature.
Eb4Blower motor senses a loss of rotor control or high current.Abnormal motor loading or a sudden blockage: check filters, filter grilles, registers, the duct system and the furnace air inlet and outlet.
Eb5Blower motor failed to start 10 consecutive times.Obstruction in the blower housing, seized bearings or a failed motor; repair or replace the wheel or motor.
Eb6Blower motor shut down on over or under voltage, or on over-temperature of its power module.Line voltage must be within the range on the rating plate; high ambient temperature.
Eb7Blower motor doesn't have enough information to operate, or failed to start 40 consecutive times.Make sure the control has the correct shared data set; check for a locked rotor.
Eb9Airflow lower than demanded; reduced performance or low stage when high stage is expected.Blocked filters, restrictive or undersized ductwork (all registers open), high ambient temperature.
Ed0Data not yet on network.Populate the shared data set with the CoolCloud HVAC app; the code clears once the data is downloaded.
Ed1Invalid shared data; operation different than expected, or none.Make sure the shared data set is right for the model and re-populate it with the CoolCloud HVAC app.
EE0Lockout after too many ignition retries (3 total): failure to establish flame, or loss of flame after it was established.Gas supply and pressure; front cover pressure switch and drainage; igniter and its alignment; restricted orifices; flame sensor (clean with steel wool); flue blockage, length and elbows; combustion air; inducer performance. How to fix →
EE1Pressure switch circuit closed at the start of the heating cycle.Sticking switch contacts or a short in the switch wiring. How to fix →
EE2Pressure switch circuit open; the inducer runs with no further operation.Pressure switch hose blocked, pinched or misconnected; blocked flue or inlet pipe; blocked drain system; weak inducer; wrong switch set point or bad contacts; loose wiring. How to fix →
EE3Primary limit circuit open; the circulator blower runs with no furnace operation.Blocked filters or restrictive ductwork; blower speed and motor; loose wiring in the limit circuit. Check the temperature rise against the specification sheet. How to fix →
EE4Flame sensed with no call for heat; inducer and circulator run continuously.Short to ground in the flame sense circuit, a lingering burner flame, or a slow-closing gas valve. How to fix →
EE5Open fuse.Replace the fuse (3-amp automotive type) and find the short in the low-voltage wiring, or the back of the control touching the mounting panel because standoffs are missing. How to fix →
EE6Low flame sense microamp signal (furnace still runs).Clean a coated or oxidized flame sensor with steel wool; check its position in the flame; check the inlet air piping for blockage, length, elbows and termination; compare gas pressure with the rating plate. How to fix →
EE7Problem with the igniter circuit.Wiring from the control to the igniter; a shorted igniter; the furnace ground; the igniter output from the control (igniter relay fault). How to fix →
E10Grounding fault.Poor neutral connection: verify the neutral wire to the furnace and continuity to the ground source.
E11Open burner box limit switch circuit.Gas pressure too high, misaligned burners, or a restricted heat exchanger or vent. How to fix →
E12Redundant relay open alarm.Replace the integrated control; don't replace other parts based on this code.
E13Redundant relay stuck closed alarm.Replace the integrated control. If E13 stays after the new control, replace the system wire harness.
E14External flash fault: data error in the storage function (fault history, system status).Replace the integrated control if the code doesn't reset.
E15External return air temperature sensor circuit open (no return reading in the CoolCloud app).Allow up to 90 seconds for the control to detect sensors. Make sure the probe is plugged in all the way and its connector is crimped properly; the probe should read 10 kΩ at 77°F (lower when warmer, higher when colder); otherwise replace the control board.
E16External return air temperature sensor circuit shorted.Check the probe terminals and conductors for a short; if the error shows with the probe unplugged, check the board connector for a short; replace the control board.
E17External supply air temperature sensor circuit open (no supply reading in the CoolCloud app).Allow up to 90 seconds for detection. Probe plugged in all the way, connector crimped properly, 10 kΩ at 77°F; otherwise replace the control board.
E18External supply air temperature sensor circuit shorted.Check the probe terminals and conductors for a short; if the error shows with the probe unplugged, check the board connector; replace the control board.
E19Onboard return air temperature sensor unplugged.Power cycle (allow up to 90 seconds for detection); look for damage to the onboard sensor (R311); replace the control board.
E1AOnboard return air temperature sensor shorted.Power cycle (allow up to 90 seconds); make sure nothing on the board is shorting the onboard sensor (R311); replace the control board.
EbFInducer communication alarm.Loose wiring between the control and the inducer: check the red, black and white harness and its connections at both ends.
E1bAnalog pressure sensor reference error: the 5 VDC reference is out of range (5.0 ±0.2 VDC for 5 seconds).Red, black and white harness and connections to the inducer and control; replace the pressure sensor. How to fix →
E1CAnalog pressure sensor null error: sensor voltage out of range with the inducer off.Red, black and white harness and connections; pressure hoses to the pressure sensor and pressure switch. How to fix →
E1dAnalog pressure sensor span error: sensor out of range when the pressure switch is closed, or the switch opens and closes outside the expected sensor range.Harness and connections; pressure hoses to the sensor and switch; replace the pressure switch if the error continues. How to fix →
E1EAnalog pressure sensor pressure error: inducer RPM has reached its limit, or a blocked flue pipe.Harness and connections; flue piping for blockage, length, elbows and termination; replace the pressure sensor if necessary. How to fix →
E1FAnalog pressure sensor input error: wrong pressure sensor installed.Harness and connections; replace the pressure sensor with the correct part. How to fix →
EEA120 VAC polarity reversed.Correct the polarity per the wiring diagram and verify the furnace ground.
EEbThe control is not energizing the gas valve when it should.Check the gas valve circuit wiring; if it is good, replace the integrated control. Goodman says not to replace the gas valve for this code.
EECGas valve energized when it should be off.Cycle 120 VAC. If EEC stays, it is a wiring problem outside the control: inspect the system wiring and replace the system harness; if EEC still stays, replace the control.
EEdAuxiliary limit switch open (blower compartment).120 V power shut off during a heat cycle; not enough air over the heat exchanger (blocked filters, restrictive ducts, blower speed or failed blower motor); loose wiring in the limit circuit. How to fix →
EEEThe control has detected an internal fault.Power off for at least 3 minutes and back on; inspect the 120 V and 24 V wiring and the ground. Replace the control; don't replace other parts based on this code.
EEFAUX switch (condensate switch) open.High water in the evaporator coil drain pan or auxiliary drain pan: check the pan, the drain piping and the auxiliary pan.
EAFLost communication with the R-32 sensor; the furnace is in mitigation mode (fan only).The furnace may not be paired with an R-32 cooling unit: see the manual's R-32 information section. Otherwise check the sensor wire and connection, and replace the sensor if needed.
EA0The R-32 sensor has detected a refrigerant leak; mitigation mode (fan only).Look for a leak at the indoor coil. Heating resumes once no leak is detected and the 5-minute delay is over.
EA1The R-32 sensor has detected a fault; mitigation mode (fan only).Check the R-32 sensor and replace it if necessary.
EA2The control has detected a problem with its internal A2L relay and is running mitigation mode.Disconnect any wire on the control's ALARM terminal and cycle power. If the code clears, repair the ALARM wiring; if not, replace the control.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Goodman Service and Troubleshooting, *RVS96*U & CDVS96*U Single Stage Variable Speed Ultra-Low NOx Gas Furnaces, RS6612303 Rev. 1, Status Codes p. 34 and Troubleshooting pp. 35-38 (read from page images). The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.