Goodman / Amana GMVS96 / AMVS96 U-revision Furnace Codes

Applies to: Goodman / Amana GMVS96 / AMVS96 U-revision (96% variable-speed with analog pressure sensor, model numbers GMVS96*U and AMVS96*U). Seven-segment display on the integrated control module.

Covers the U-revision GMVS96 and Amana AMVS96 only. Earlier GMVS96 furnaces use pressure switches and a different chart; check the model number on the rating plate.

CodeMeaningWhat to check
d0Equipment lacks shared data.Populate the shared data set using the memory card.
Eb0Circulator blower motor is not running when it should be running.Wiring connections, continuity through the inductor, the motor.
Eb1Integrated control module has lost communications with the circulator blower motor.Wiring connections, motor, then the control.
Eb2Circulator blower motor horsepower in the shared data set does not match the motor.Motor horsepower against the nameplate; reload shared data with the correct memory card.
Eb3Circulator blower motor is operating in a power, temperature, or speed limiting condition.Filters, blocked ductwork, closed registers, duct sizing. How to fix →
Eb4Circulator blower motor senses a loss of rotor control or high current.Filters, grilles, registers and ducts for blockage. How to fix →
Eb5Circulator blower motor fails to start 10 consecutive times.Obstruction in the blower, wheel and shaft rotation, motor.
Eb6Circulator blower motor shuts down for over or under voltage, or for over temperature on the power module.Voltage to the furnace against the nameplate range.
Eb7Circulator blower motor lacks information to operate properly, or fails to start 40 consecutive times.Locked rotor; confirm the control has the correct shared data.
Eb9Airflow is lower than demanded.Filters, blocked ductwork, closed registers, duct sizing. How to fix →
E1bAnalog pressure sensor reference error: APS reference out of range (5.0 +/- 0.2 V) for 5 seconds.Electrical connections to the pressure sensor. How to fix →
E1cAnalog pressure sensor null error: inconsistent pressure reading with the inducer off.Electrical connections to the pressure sensor. How to fix →
E1dAnalog pressure sensor span error: inconsistent pressure reading with the inducer on.Electrical connections to the pressure sensor. How to fix →
E1EAnalog pressure error (blocked vent error).Blocked vent, or the pressure sensor or its connection. The pressure could not reach its target with the inducer at maximum or minimum RPM. How to fix →
E1FAnalog pressure sensor input error: sensor input voltage out of range for 5 seconds.The pressure sensor and its connection.
E10Grounding fault or poor neutral connection.Neutral connection to the furnace and continuity to ground.
E11Open rollout switch.Gas pressure, burner alignment, burner restriction. How to fix →
Ed0Data not yet on network.Populate the shared data set using the memory card.
Ed1Invalid memory card data.Confirm the shared data set is right for the model; reload with the correct memory card.
EE0Lockout after too many ignition retries (3 total): failure to establish flame or loss of flame after it was established.Gas supply, front cover pressure switch and drainage, igniter, flame sensor, flue piping, inducer. How to fix →
EE1Low stage pressure switch circuit is closed at the start of the heating cycle.Sticking switch contacts or a short in the switch wiring. How to fix →
EE2Low stage pressure switch circuit is not closed. Inducer runs continuously with no furnace operation.Switch hose, blocked flue or inlet pipe, blocked drain, weak inducer, wrong switch, loose wiring. How to fix →
EE3Primary limit circuit is open. Circulator blower runs continuously.Filters, restrictive ductwork, blower speed or failed blower motor, limit wiring. How to fix →
EE4Flame sensed with no call for heat. Inducer and blower run continuously.Short to ground in the flame sense circuit; lingering flame from a slow-closing gas valve.
EE5Open fuse.Short in the low voltage wiring. Fix it, then replace the fuse. How to fix →
EE6Flame sense microamp signal is low (furnace still operates).Coated or mispositioned flame sensor; lazy flame from gas pressure or combustion air. How to fix →
EE7Problem with the igniter circuit.Igniter wiring, shorted igniter, unit ground, igniter relay on the control. How to fix →
EE8High stage pressure switch circuit is closed at the start of the heating cycle. Furnace runs on low stage only.Sticking switch contacts or a short in the switch wiring. How to fix →
EE9High stage pressure switch circuit is not closed. Furnace runs on low stage only.Switch hose, flue and inlet piping, drain, inducer, wiring. How to fix →
EEAPolarity of 115 volt AC is reversed, or poor unit ground.Correct polarity and ground.
EEbGas valve is not energized when it should be (external gas valve error).Gas valve circuit wiring; control board.
EECGas valve is energized when it should not be (internal gas valve error).Gas valve circuit wiring; control board.
EEdAux limit switch open (blower compartment).Filters, ductwork, blower speed and motor, wiring. How to fix →
EEFAux switch (condensate switch) open.Evaporator drain pan, trap and piping. How to fix →

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Goodman Service Instructions, GMVS96*U and AMVS96*U gas furnaces, Troubleshooting chart, pp. 34-39. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.