ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N8MSN / N8MSL Furnace Codes
International Comfort Products builds furnaces sold under several brand names, including Heil, Tempstar, Comfortmaker and Arcoaire. This chart is from the N8MSN/N8MSL manual; the 90% N9MSE has its own chart. Go by the service label on the blower door of the furnace you're working on.
| Code | Meaning | What to check |
|---|---|---|
| 2 | Pressure switch did not open. | Check for obstructed pressure tubing and a pressure switch stuck closed. How to fix → |
| 3 | Pressure switch did not close or reopened. | If open longer than five minutes, the inducer shuts off for 15 minutes before retrying. Check: excessive wind, vent sizing, inducer motor and its voltage (115 VAC), pressure switch, combustion air supply, disconnected or obstructed pressure tubing, low inlet gas pressure (if an LGPS is used), restricted vent. If it opens during the blower on-delay, the blower comes on for the selected off-delay. How to fix → |
| 4 | Limit circuit fault. | A limit, draft safeguard, flame rollout or blocked vent switch (if used) is open. The blower runs for 4 minutes or until the switch closes, whichever is longer. Open longer than 3 minutes changes to lockout code 7. The flame rollout switch and BVSS need a manual reset. Check: restricted vent, vent sizing, loose blower wheel, excessive wind, dirty filter or restricted ducts, blower motor or capacitor, switch or connections, combustion air supply (rollout open). How to fix → |
| 5 | Abnormal flame-proving signal. | Flame is proved while the gas valve is de-energized. The inducer runs until the fault clears. Check for a leaky or stuck-open gas valve. |
| 6 | Ignition proving failure. | The control tries three more times before lockout 6+1. Check: flame sensor grounded or oxidized (clean with fine steel wool); flame current (0.5 microamps DC minimum, 4.0-6.0 nominal); gas valve off or defective; manual shut-off; low inlet gas pressure; hot surface igniter; control ground continuity; flame carryover or rough ignition. The green/yellow wire must be connected to the furnace sheet metal. How to fix → |
| 7 | Limit circuit lockout. | The limit, draft safeguard, flame rollout or blocked vent switch (if used) was open longer than 3 minutes. The control auto-resets after three hours. See code 4. How to fix → |
| 8 | Gas heating lockout. | The control will NOT auto-reset. Check for a miswired gas valve or a defective control (valve relay). |
| 10 | Polarity. | Line voltage (115 VAC) polarity reversed. If the furnace is twinned, see the twinning kit instructions. |
| 1+2 | Blower on after power up. | The blower runs for 90 seconds if power comes on during a call for heat (R-W closed), or if R-W opens during the blower on-delay. |
| 6+1 | Ignition lockout. | The control auto-resets after three hours. See code 6. How to fix → |
| OFF | LED off: secondary voltage fuse open. | Check the door switch, 115 VAC at L1 and neutral, 24 VAC between 24VAC (red) and COM (blue), the 3 A 24 V fuse, and for a short in the 24 V wiring. How to fix → |
| ON / SOLID | LED on solid: control circuitry lockout. | Auto-resets after one hour. Caused by a stuck-open gas valve relay, a flame sense circuit failure or a software check error. Reset power to clear it; replace the control if the code repeats. |
How to read the codes
- Each code is one or two digits. The first number is the count of short flashes; the number after the plus sign is the count of long flashes. For example, 6+1 is six short flashes then one long.
- Heartbeat (bright-dim): the control has 24 VAC. That's normal.
- To recall the last stored code, the control must be idle (no call for heat, cool or fan, blower off) and showing the heartbeat. Then either jumper TEST/TWIN to the thermostat C terminal for 2-3 seconds, or briefly remove and reconnect one limit wire (main, rollout or draft safeguard switch).
- If the jumper stays on more than 4-5 seconds, code 10 flashes but the stored code is kept. If the limit wire stays off more than 4-5 seconds, code 4 flashes and the stored code is lost.
- After the stored code flashes 4 times, the component test starts: the inducer runs throughout, and the hot surface igniter, fan (if equipped), heat speed and cool speed each come on for 10-15 seconds. The gas valve and humidifier are not turned on.
- Stored codes erase automatically after 72 hours.
Source: ICP N8MSN/N8MSL Installation Instructions, 441 01 1402 03 (March 2013), Figure 44 Service Label, p. 38. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.
Related
- How to read furnace LED flash codes
- Furnace pressure switch troubleshooting
- Flame sensor microamps and cleaning
Other brands
- Lennox Merit ML180UH (80% single-stage)
- Carrier 58CVA / 58CVX (80% variable-speed two-stage)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N9MSE (90% single-stage condensing, PSC blower)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N80ESU / R80ESU (80% single-stage, ECM blower, Ultra Low NOx, minor series 2 and 3)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N80MSU (80% single-stage, ECM blower, Ultra Low NOx, 3-digit display, minor series 3)
- Rheem / Ruud R96V / 96MDV (96% two-stage communicating)
- Rheem / Ruud R97V (97% modulating communicating, downflow/horizontal)
- Rheem / Ruud R98V (98% modulating communicating, upflow)
- Goodman / Amana GR9S80 / GD9S80 (80% single-stage)
- Trane / American Standard S9X1 / S9X2 / S9B1 (96% condensing)
- Lennox SL280UHV (80% two-stage variable speed)
- Goodman / Amana / Daikin GM9S96 / GC9S96 / GM9S92 (96% and 92% condensing, single-stage)
- Carrier 59TP6C two-stage condensing with InteliSense (Performance series)
- Lennox G60DF / G60DFV (older two-stage SureLight boards 18M3401, 46M9901, 18M9901, 49M5901)
- Lennox G60UH / G60UHV (SureLight boards 100869 and 100870)
- Rheem / Ruud R801T Ultra Low NOx (14 ng/J) single-stage upflow/horizontal, constant-torque blower
- Rheem / Ruud 802V / 80MDV (80% two-stage communicating, ECM blower; model numbers (-)802V and (-)(-)80MDV)
- Trane / American Standard S8B1 / S8X1 / S8X2 (80% single-stage and two-stage)
- Trane / American Standard A801X060AM3S (80% single-stage, 2024 installation manual)
- Trane / American Standard A801X (80% single-stage: A801X040AM3SD, A801X040BM2SD, A801X060BM4SD, A801X080BM4SD, A801X080CM5SD, A801X100CM5SD, A801X120DM5SD)
- Goodman / Amana GMVC96 / GCVC96 (96% two-stage variable-speed, *MVC96*BA and *CVC96*BA)
- Goodman / Amana GMVS96 / AMVS96 U-revision (96% variable-speed with analog pressure sensor, model numbers GMVS96*U and AMVS96*U)
- Goodman / Amana GMVM96 / GCVM96 / AMVM96 / ACVM96 (96% modulating, model numbers *MVM96 and *CVM96)
- Rheem / Ruud R801T / 80MSX (80% single-stage, constant-torque blower; model numbers (-)801T and (-)(-)80MSX)
- Rheem / Ruud 802P / 80MDP (80% two-stage, model numbers (-)802P and (-)(-)80MDP)
- Rheem / Ruud 802T / 80MDT (80% two-stage with constant-torque blower, model numbers (-)802T and (-)(-)80MDT)
- Rheem / Ruud 801S / 801P / 80MSS / 80MSP (80% single-stage, model numbers (-)801S, (-)801P, (-)(-)80MSS and (-)(-)80MSP)
- Rheem / Ruud W801T (Rheem Select 80% downflow single-stage)
- Rheem / Ruud R951T (95% single-stage condensing, constant-torque blower; model numbers (-)951T)
- Rheem / Ruud 801V Ultra Low NOx (80% communicating, constant CFM blower, upflow/horizontal)
- Carrier 58STA / 58STX (80% single-stage, 4-way multipoise)
- Carrier 58CTA / 58CTX (80% two-stage, 4-way multipoise, Series 140/E)
- York TG9S (95.5% AFUE single-stage PSC, multi-position)
- York TM9V (96% AFUE two-stage variable-speed ECM, multi-position)
- York UTEC Board (single- and two-stage furnaces from August 2009; SAP 539617, 542760, 542767, 542766; Source 1 S1-33102956000, S1-03102951001, S1-33102954000, S1-33102955000)
- York White-Rodgers Board (the generation before the 2009 UTEC boards; 265901, S1-33109167000 / 265902, S1-33109168000 / 265903, S1-33109169000 / 265904)
- York TI Board (older furnaces; 031-01972-000 TI 6DT-1, 031-01973-000 TI 6DT-2, 031-09117-000 TI 6MD-1, 031-09118-000 TI 6MI-1)
- Carrier 58SB0A / 58SB1A (single-stage, non-condensing)