ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N8MSN / N8MSL Furnace Codes

Applies to: ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N8MSN / N8MSL (80% single-stage, PSC blower). STATUS LED on the furnace control, seen through the sight glass in the blower access door.

International Comfort Products builds furnaces sold under several brand names, including Heil, Tempstar, Comfortmaker and Arcoaire. This chart is from the N8MSN/N8MSL manual; the 90% N9MSE has its own chart. Go by the service label on the blower door of the furnace you're working on.

CodeMeaningWhat to check
2Pressure switch did not open.Check for obstructed pressure tubing and a pressure switch stuck closed. How to fix →
3Pressure switch did not close or reopened.If open longer than five minutes, the inducer shuts off for 15 minutes before retrying. Check: excessive wind, vent sizing, inducer motor and its voltage (115 VAC), pressure switch, combustion air supply, disconnected or obstructed pressure tubing, low inlet gas pressure (if an LGPS is used), restricted vent. If it opens during the blower on-delay, the blower comes on for the selected off-delay. How to fix →
4Limit circuit fault.A limit, draft safeguard, flame rollout or blocked vent switch (if used) is open. The blower runs for 4 minutes or until the switch closes, whichever is longer. Open longer than 3 minutes changes to lockout code 7. The flame rollout switch and BVSS need a manual reset. Check: restricted vent, vent sizing, loose blower wheel, excessive wind, dirty filter or restricted ducts, blower motor or capacitor, switch or connections, combustion air supply (rollout open). How to fix →
5Abnormal flame-proving signal.Flame is proved while the gas valve is de-energized. The inducer runs until the fault clears. Check for a leaky or stuck-open gas valve.
6Ignition proving failure.The control tries three more times before lockout 6+1. Check: flame sensor grounded or oxidized (clean with fine steel wool); flame current (0.5 microamps DC minimum, 4.0-6.0 nominal); gas valve off or defective; manual shut-off; low inlet gas pressure; hot surface igniter; control ground continuity; flame carryover or rough ignition. The green/yellow wire must be connected to the furnace sheet metal. How to fix →
7Limit circuit lockout.The limit, draft safeguard, flame rollout or blocked vent switch (if used) was open longer than 3 minutes. The control auto-resets after three hours. See code 4. How to fix →
8Gas heating lockout.The control will NOT auto-reset. Check for a miswired gas valve or a defective control (valve relay).
10Polarity.Line voltage (115 VAC) polarity reversed. If the furnace is twinned, see the twinning kit instructions.
1+2Blower on after power up.The blower runs for 90 seconds if power comes on during a call for heat (R-W closed), or if R-W opens during the blower on-delay.
6+1Ignition lockout.The control auto-resets after three hours. See code 6. How to fix →
OFFLED off: secondary voltage fuse open.Check the door switch, 115 VAC at L1 and neutral, 24 VAC between 24VAC (red) and COM (blue), the 3 A 24 V fuse, and for a short in the 24 V wiring. How to fix →
ON / SOLIDLED on solid: control circuitry lockout.Auto-resets after one hour. Caused by a stuck-open gas valve relay, a flame sense circuit failure or a software check error. Reset power to clear it; replace the control if the code repeats.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: ICP N8MSN/N8MSL Installation Instructions, 441 01 1402 03 (March 2013), Figure 44 Service Label, p. 38. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.