Rheem / Ruud R96P / 96MDP Furnace Codes

Applies to: Rheem / Ruud R96P / 96MDP (96% two-stage condensing, PSC blower; model numbers (-)96P and (-)(-)96MDP, e.g. R96PA0702317MSA). Seven-segment display on the integrated furnace control (IFC).

The (-) in the model number stands for the brand prefix (R Rheem, U Ruud). The two-stage communicating R96V has a longer list; see its chart.

CodeMeaningWhat to check
0Standby: no fault, no thermostat call.
10One-hour lockout.Shown alternately with the code that caused it: 11 (four failed ignitions in a row), 59 (water sensed several times), 61 (dead blower), 93 (internal fault), 13 (flame lost five times) or 14 (unexpected flame). Gas heat stops; other modes such as cooling still work. See that code.
11Failed ignition.After each failed try the inducer runs a 20-second post-purge and tries again; after four failures it goes to a one-hour lockout (10). Causes: flame sense rod can't sense flame (clean or replace, check its wiring and the furnace ground); gas valve off; igniter not working or misplaced; faulty control; flame not carrying from burner to burner (check manifold pressure during ignition: natural gas about 3.5 in. w.c., LP about 10 in. w.c.). How to fix →
12Low flame sense.Flame current is weak or marginal; the furnace keeps running but may soon move to 13 or 11. Clean or replace the flame sense rod and check its wiring; reinstall or replace a badly mounted or poorly grounded sensor and make sure the furnace is grounded. How to fix →
13Flame lost after it was established.The blower runs at the correct speed and finishes a 90-second off-delay; the inducer runs a 20-second post-purge, then ignition is retried. Clean or replace the flame sense rod, reinstall or replace a poorly grounded sensor, and check that all burner assembly parts, seals between the burner and blower compartments, the combustion door gasket and the door are in place. How to fix →
14Flame present with the gas valve off.Blower runs at maximum heat speed and inducer at high speed until the fault clears, then a one-hour lockout. Causes: miswired 24 VAC to the gas valve main solenoid, gas valve stuck open, or a faulty control. Rewire, replace the gas valve or replace the control. How to fix →
20Twinning fault.Neither furnace runs. Power off at one furnace, transformers out of phase (flame LED dim), controls that don't match, or broken or missing board contacts. Check wiring and that both blower doors are on, phase the transformers, use the same IFC part number on both, or replace the control. How to fix →
22Main limit open.Blower runs at maximum heat speed, gas valve off, inducer on high until the limit closes. If open over 150 seconds the control declares a dead blower and alternates 10 and 61. Causes: no or too little airflow, faulty limit, loose wiring, dead blower, input too high. Check the blower, ducts, filters and static pressure, temperature rise on high and low heat against the nameplate, the limit, wiring, and burner orifices and high-fire manifold pressure. How to fix →
26Line and neutral reversed, or poor ground.No heating or cooling. Check voltage with a meter and reverse line and neutral at the furnace or the disconnect if needed; check the ground wire inside the furnace is attached to the cabinet and the ground at the breaker box.
33Manual reset limit (rollout) open.Gas valve off, blower on at maximum heat speed and inducer on high. Causes: not enough venting through the inlet or exhaust, loose wiring, unstable flame. Check the pressure switches aren't welded or bypassed, inducer speed, vent length and obstructions, and the inducer-to-panel and heat exchanger gaskets; check burner assembly seals, the door seal, and the heat exchanger for damage (crushed tubes, breached collector box). Push the rollout switch back to reset it once fixed. How to fix →
44Low pressure switch closed with the inducer off.Faulty switch; switch physically bypassed in the field; loose or faulty wiring; or abnormally high negative pressure on the vent system with the inducer off. Fix: replace the switch, remove any bypass and find out why it was done (for example vent length too long), fix wiring, and check venting and terminations against the installation instructions. (Rheem's solution column for 44 says to replace the high pressure control; the fault is the low pressure switch.) How to fix →
45Low pressure switch open with the inducer on high speed.Before heat: the inducer stays on high; if the switch hasn't closed in 60 seconds, a 5-minute soft lockout. After heat is established: gas valve off, blower finishes its off-delay, inducer post-purges, then retries. Causes and fixes: vent blocked or badly terminated, too much vent length or too many elbows, faulty or disconnected inducer, faulty control (inducer relay), loose wiring, damaged hoses, wind gusts (check termination and whether a high altitude kit is needed), faulty pressure switch. How to fix →
46Low pressure switch open with the inducer on low speed.Shown only after heat is established and switched to low fire. Gas valve off, blower finishes its low-speed off-delay, inducer post-purges on low, then retries. (1) Blocked or improperly terminated inlet or exhaust vent; (2) vent length or number of elbows over the maximum; (3) faulty or disconnected inducer; (4) faulty control board (inducer relay); (5) high altitude kit not installed at high elevation; (6) loose or faulty wiring; (7) disconnected, blocked, split or cut pressure switch hoses; (8) wind gusts (sporadic); (9) faulty pressure switch. Fix: check the vent for blockage and termination, remove excess venting per the spec sheet, repair or replace the inducer or its wiring, replace the control board, check whether a high altitude kit is needed, fix wiring, replace hoses, and replace the pressure switch. How to fix →
55High pressure switch closed with the inducer off.Faulty switch; switch physically bypassed in the field; loose or faulty wiring; or abnormally high negative pressure on the vent system with the inducer off. Fix: replace the switch, remove any bypass and find out why it was done (for example vent length too long), fix wiring, and check venting and terminations against the installation instructions. How to fix →
57High pressure switch open with the inducer on high speed.Shown during the heat call, except during low heat and before the pre-purge and blower delays finish. If it happens during high heat and the low switch stays closed, the furnace drops to low fire and keeps running (display alternates h and 57). (1) Blocked or improperly terminated inlet or exhaust vent; (2) vent length or number of elbows over the maximum; (3) faulty or disconnected inducer; (4) faulty control board (inducer relay); (5) high altitude kit not installed at high elevation; (6) loose or faulty wiring; (7) disconnected, blocked, split or cut pressure switch hoses; (8) wind gusts (sporadic); (9) faulty pressure switch. Fix: check the vent for blockage and termination, remove excess venting per the spec sheet, repair or replace the inducer or its wiring, replace the control board, check whether a high altitude kit is needed, fix wiring, replace hoses, and replace the pressure switch. How to fix →
58Water sensor circuit open.No gas heat; other modes work. The control can't see continuity between pins 1 and 2 of connector P4 (both water sensors). Repair damaged wiring, fix the P4 or sensor connections, or replace a missing water sensor. How to fix →
59Water sensed / blocked drain.No gas heat; other modes work. Current flows from P4 pin 1 or 2 to the furnace sheet metal for at least 10 seconds. Clear a blocked condensate drain or trap, repair sensor wiring touching the sheet metal, or put a sensor back in its place in the collector box. How to fix →
61Blower fault: motor can't run.The furnace won't run in any mode. Can follow a main limit open more than 150 seconds four times in one heat call (hard lockout; power reset needed). Causes: motor tripped on its thermal limit (restriction or bearing failure), faulty Power Factor Correction (PFC) choke, faulty or corrupted furnace model data, damaged wiring to the motor or PFC, damaged or loose blower wheel, failed motor. Remove the obstruction or replace the motor, replace the PFC choke, replace the memory card with the correct part, fix wiring, fix the wheel.
93Internal control fault detected.The furnace won't run in any mode. Causes: 24 VAC or similar voltage on the main gas valve circuit unexpectedly, or a failed control software test. Check for miswiring; replace the furnace control.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Rheem Installation Instructions, (-)96P / (-)(-)96MDP 4-position condensing two-stage PSC gas furnaces, 92-24161-122-12, Tables 17-20 pp. 88-98, Lockout p. 99. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.