Payne PG96VTAB Furnace Codes
Payne is a Carrier brand. The earlier series A PG96VTA (PG96VTAA) shows two-digit flash codes and is on the Carrier 59TP6B / 59TP6A / 59TN6A chart. This label's codes are the Carrier 59TP7A list without the InteliSense (19.1) and air temperature sensor (52, 53) codes.
| Code | Meaning | What to check |
|---|---|---|
| 10.1 | L1 polarity fault (LED flashes rapidly). | |
| 12.1 | W on at power up. | |
| 13.1 | Limit lockout: a switch open longer than 3 minutes in the main limit circuit. | How to fix → |
| 14.1 | Ignition lockout after 4 consecutive ignition tries. | How to fix → |
| 14.2 | Flame lost 3 times after 70 seconds of heating. | How to fix → |
| 14.3 | Lockout: 7 loss-of-flame events during a heat request. | How to fix → |
| 14.4 | Lockout: 7 LPS (main pressure switch) open events during a heat request. | How to fix → |
| 15.1 | Lockout: no blower RPM detected. | |
| 21.1 | 24 VAC sensed on the gas valve when it shouldn't be. | |
| 22.1 | False flame. | |
| 23.4 | LPS (main pressure switch) stuck closed. | How to fix → |
| 23.5 | HPS (secondary pressure switch) stuck closed. | How to fix → |
| 24.1 | Fuse fault. | How to fix → |
| 25.1 | No program info in the control. No heating operation. | Reprogram the control with the program number on the rating plate; replace the control if the code remains. |
| 25.2 | Corrupted program file. No heating operation. | Reprogram the control with the service app or a super plug (supplied separately). |
| 25.3 | Twinned units are not identical (program numbers do not match). The main unit will not heat. | Twinned furnaces must have the same program number. |
| 25.4 | Main program invalid; the control runs on its backup program and still operates normally. | Reprogram the control to correct it. |
| 25.5 | Installer settings corrupted; the control runs on default installer settings. | Reselect the installer settings or reprogram the control. |
| 25.6 | Wrong program for this control. No heating operation. | Reprogram the control so the program matches the control. |
| 27.1–27.3 | Program in the super plug is missing, not recognized or corrupted. | Remove the super plug and retry. If 27 returns, try a different super plug; if that fails, replace the control. |
| 31.6 | Open secondary pressure switch (HPS). | How to fix → |
| 31.7 | HPS failed to close within 75 seconds when going from low to high heat. The label calls this "High Heat Only for next cycle". | How to fix → |
| 32.2 | Open main pressure switch (LPS). | How to fix → |
| 33.1 | A switch has opened in the main limit circuit. | How to fix → |
| 33.2 | Lockout. The label reads "High Heat Only for current cycle". | How to fix → |
| 34.1 | Ignition fault during four consecutive ignition trials. | How to fix → |
| 34.5 | Low heat flame lost before the blower on-delay. | How to fix → |
| 34.6 | Low heat flame lost after the blower on-delay. | How to fix → |
| 34.7 | High heat flame lost before the blower on-delay. | How to fix → |
| 34.8 | High heat flame lost after the blower on-delay. | How to fix → |
| 41.1 | No blower RPM at start-up. | |
| 41.2 | No RPM while the blower motor is running. | |
| 43.1 | HPS closed before the LPS. | How to fix → |
| 45.1 | Internal control error. | Cycle power; if 45 repeats, replace the control. |
| 45.2 | Gas valve relay (GVR) not closing. | Cycle power; if 45 repeats, replace the control. |
| 45.3 | Micro EEPROM error. | Cycle power; if 45 repeats, replace the control. |
| 45.4 | Micro loss of communication. | Cycle power; if 45 repeats, replace the control. |
| 46.1 | Momentary loss of power. |
How to read the codes
- The display shows major.minor: the first two digits are the major code and the third is the minor code. The LED through the door flashes the major code only: short flashes for the first digit, then long flashes for the second (31 = 3 short, 1 long).
- Normal displays: idL idle or standby, Ht1/Ht2 low/high heating, CL1/CL2 low/high cooling, HPd heat pump defrost, CFn/CF2/CF3 continuous fan, bLr secondary (twinned) unit running its blower during CFn, CL or Ht. ##.# is an active status code.
- Stored faults: press MENU/SELECT to step through the main menu to FLt (last 7 faults), then NEXT/OPTION to view them. CLr clears the list.
- Component test: with the control in idL and no W, Y or G call, select Ct from the menu. The inducer runs on high (PUr), the hot surface igniter comes on for 15 seconds after a 10 second wait (HSI), the blower runs 10 seconds (Fn), then the inducer runs on low for 10 seconds (End).
Source: Payne PG96VTAB Installation, Start-up, Operating and Service and Maintenance Instructions IM-PG96VTAB-03, Fig. 59 Service Label Information p. 55 (read at 400 dpi); display flow chart Fig. 58. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.
Related
- How to read furnace LED flash codes
- Furnace pressure switch troubleshooting
- Flame sensor microamps and cleaning
Other brands
- Lennox Merit ML180UH (80% single-stage)
- Carrier 58CVA / 58CVX (80% variable-speed two-stage)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) R96MSN / N96MSN (single-stage 35-in. condensing, 4-way multipoise)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) R95MSU (single-stage Ultra Low NOx condensing, upflow/horizontal, 35 in. tall)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N95ESN / R92ESN (single-stage 35-in. condensing, 4-way multipoise; also PG95ESA)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N92ESN (single-stage 35-in. condensing, 4-way multipoise)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N9MSE (90% single-stage condensing, PSC blower)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N8MSN / N8MSL (80% single-stage, PSC blower)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N80ESU / R80ESU (80% single-stage, ECM blower, Ultra Low NOx, minor series 2 and 3)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N80MSU (80% single-stage, ECM blower, Ultra Low NOx, 3-digit display, minor series 3)
- Rheem / Ruud R96P / 96MDP (96% two-stage condensing, PSC blower; model numbers (-)96P and (-)(-)96MDP, e.g. R96PA0702317MSA)
- Rheem / Ruud R96V / 96MDV (96% two-stage communicating)
- Rheem / Ruud R97V (97% modulating communicating, downflow/horizontal)
- Rheem / Ruud R98V (98% modulating communicating, upflow)
- Goodman / Amana GR9S80 / GD9S80 (80% single-stage)
- Trane / American Standard S9X1 / S9X2 / S9B1 (96% condensing)
- Lennox EL296UHV / SL280UHV control 107045 (Elite EL296UHV(X), EL296DFV(X) and SL280UHV/SL280UHNV/SL280DFV, two-stage, variable-speed, communicating; EL296UH045V36B, EL296UH045XV36B, EL296UH070V36B, EL296UH070XV36B, EL296UH090V36C, EL296UH090XV36C, EL296UH090XV48C, EL296UH090V60C, EL296UH090XV60C, EL296UH110V48C, EL296UH110XV48C, EL296UH110V60C, EL296UH110XV60C, EL296UH135V60D, EL296UH135XV60D, EL296DF045XV36B, EL296DF070V48B, EL296DF070XV48B, EL296DF090V60C, EL296DF090XV60C, EL296DF110V60C, EL296DF110XV60C, SL280UH070V36A, SL280UH070XV36A, SL280UH090V36B, SL280UH090V48B, SL280UH090XV48B, SL280UH090V60C, SL280UH090XV60C, SL280UH110V60C, SL280UH110XV60C, SL280UH135V60D, SL280DF070V36A, SL280DF090V48B, SL280DF090V60C, SL280DF110V60C)
- Lennox EL296UHV / SL280UHV control 103130 (Elite EL296UHV(X), EL296DFV(X) and SL280UHV/SL280UHNV/SL280DFV, earlier units: EL296UH045V36B, EL296UH045XV36B, EL296UH070V36B, EL296UH070XV36B, EL296UH090V36C, EL296UH090XV36C, EL296UH090XV48C, EL296UH090V60C, EL296UH090XV60C, EL296UH110V48C, EL296UH110XV48C, EL296UH110V60C, EL296UH110XV60C, EL296UH135V60D, EL296UH135XV60D, EL296DF045XV36B, EL296DF070V48B, EL296DF070XV48B, EL296DF090V60C, EL296DF090XV60C, EL296DF110V60C, EL296DF110XV60C, SL280UH070V36A, SL280UH070XV36A, SL280UH090V36B, SL280UH090V48B, SL280UH090XV48B, SL280UH090V60C, SL280UH090XV60C, SL280UH110V60C, SL280UH110XV60C, SL280UH135V60D, SL280DF070V36A, SL280DF090V48B, SL280DF090V60C, SL280DF110V60C, SL280UH060NV36A, SL280UH080NV48B, SL280UH080NV60C, SL280UH100NV60C)
- Lennox Elite EL297UHVK(X) / EL297DFVK (two-stage, variable-speed, communicating; upflow/horizontal EL297UH045XV36BK, EL297UH070XV36BK, EL297UH090XV36CK, EL297UH090XV48CK, EL297UH090XV60CK, EL297UH110XV48CK, EL297UH110XV60CK, EL297UH135XV60DK; downflow EL297DF045XV36BK, EL297DF070XV48BK, EL297DF090XV60CK, EL297DF110XV60CK; also Merit SL280UHVK and SL280UHNVK: SL280UH070XV36AK, SL280UH090XV48BK, SL280UH090XV60CK, SL280UH110XV60CK, SL280UH070V36AK, SL280UH090V36BK, SL280UH090V48BK, SL280UH090V60CK, SL280UH110V60CK, SL280UH135V60DK, SL280UH060NV36AK, SL280UH080NV48BK, SL280UH080NV60CK, SL280UH100NV60CK)
- Lennox Signature SLP99UHVK (Dave Lennox Signature, variable capacity, variable speed, communicating: SLP99UH070V36BK, SLP99UH070XV36BK, SLP99UH090V36CK, SLP99UH090XV36CK, SLP99UH090V48CK, SLP99UH090XV48CK, SLP99UH090V60CK, SLP99UH090XV60CK, SLP99UH110V60CK, SLP99UH110XV60CK, SLP99UH135V60DK, SLP99UH135XV60DK)
- Lennox Signature SLP99DFV (Dave Lennox Signature downflow, variable capacity, variable speed, communicating: SLP99DF070XV36B, SLP99DF090XV36C, SLP99DF090XV48C, SLP99DF090XV60C, SLP99DF110XV60C)
- Lennox Elite EL296UHE (96% two-stage, constant torque: EL296UH045XE36B, EL296UH070XE36B, EL296UH090XE48C, EL296UH110XE60C, EL296UH135XE60D; also Elite EL280DFE downflow: EL280DF070E36A, EL280DF090E48B)
- Lennox Elite EL297UHEK (two-stage, constant torque, non-communicating: EL297UH045XE36BK, EL297UH070XE36BK, EL297UH090XE48CK, EL297UH110XE60CK, EL297UH135XE60DK; same control and codes: Elite EL280UHEK and EL280DFEK (80%): EL280UH045E36AK, EL280UH070E36AK, EL280UH070XE36AK, EL280UH090E36BK, EL280UH090E48BK, EL280UH090XE48BK, EL280UH110E48CK, EL280UH110E60CK, EL280UH110XE60CK, EL280DF070E36AK, EL280DF090E48BK)
- Lennox Merit ML196UHEK / Elite EL196UHEK (80% single-stage, constant torque: ML196UH030XE36BK, ML196UH045XE36BK, ML196UH070XE36BK, ML196UH070XE48BK, ML196UH090XE36CK, ML196UH090XE48CK, ML196UH090XE60CK, ML196UH110XE60CK, ML196UH135XE60DK, EL196UH030XE36BK, EL196UH045XE36BK, EL196UH070XE36BK, EL196UH090XE48CK, EL196UH110XE60CK; same control and codes: Elite EL180UHNEK, Merit ML180UHEK, ML193DFEK, Elite EL195UHNEK: EL180UH040NE36AK, EL180UH060NE36AK, EL180UH080NE48BK, EL180UH100NE60CK, ML180UH045E36AK, ML180UH045XE36AK, ML180UH070E36AK, ML180UH070E36BK, ML180UH070XE36BK, ML180UH090E48BK, ML180UH090XE48BK, ML180UH090E60CK, ML180UH110E60CK, ML180UH110XE60CK, ML180UH135E60DK, ML193DF045XE36BK, ML193DF070XE36BK, ML193DF090XE48CK, EL195UH040NE36BK, EL195UH060NE36BK, EL195UH080NE48CK, EL195UH100NE60CK; variable-speed Merit ML180UHVK: ML180UH030V36AK, ML180UH045V36AK, ML180UH070V36AK, ML180UH070V36BK, ML180UH070V48BK, ML180UH090V48BK, ML180UH110V60CK, ML180UH135V60DK)
- Lennox Merit ML196UHE / ML196DFE / ML193UHE (single-stage, red LED controls 103217-03 and 107163-01: ML196UH030XE36B, ML196UH045XE36B, ML196UH070XE36B, ML196UH070XE48B, ML196UH090XE36C, ML196UH090XE48C, ML196UH090XE60C, ML196UH110XE60C, ML196UH135XE60D, ML196DF045XE36B, ML196DF070XE48B, ML196DF090XE48C, ML196DF110XE60C, ML193UH030XE36B, ML193UH045XE36B, ML193UH070XE36B, ML193UH090XE36C, ML193UH090XE48C, ML193UH110XE48C, ML193UH110XE60C; also ML180UHE and ML180DFE: ML180UH045E36A, ML180UH045XE36A, ML180UH070E36A, ML180UH070XE36A, ML180UH070E36B, ML180UH070XE36B, ML180UH090E48B, ML180UH090XE48B, ML180UH090E60C, ML180UH110E60C, ML180UH110XE60C, ML180UH135E60D, ML180DF045E36A, ML180DF070E36A, ML180DF070E36B, ML180DF090E48B, ML180DF110E60C; ML180UHV: ML180UH030V36A, ML180UH045V36A, ML180UH070V36A, ML180UH070V36B, ML180UH070V48B, ML180UH090V48B, ML180UH110V60C; Elite EL195UH (2011): EL195UH045P24B, EL195UH045P36B, EL195UH070P36B, EL195UH070P48B, EL195UH090P36C, EL195UH090P48C, EL195UH090P60C, EL195UH110P48C, EL195UH110P60C, EL195UH135P60D)
- Lennox Merit ML296UHVK / ML296DFVK / ML297UHVK (two-stage, variable-speed; upflow/horizontal ML296UH045XV36BK, ML296UH070XV36BK, ML296UH090XV48CK, ML296UH110XV60CK; downflow ML296DF045XV36BK, ML296DF070XV48BK, ML296DF090XV60CK; ML297UH045XV36BK, ML297UH070XV36BK, ML297UH090XV36CK, ML297UH090XV60CK, ML297UH110XV60CK, ML297UH135XV60DK)
- Lennox SL280UHV (80% two-stage variable speed)
- Goodman / Amana / Daikin GM9S96 / GC9S96 / GM9S92 (96% and 92% condensing, single-stage; also Daikin DM96SN, DM92SN, DC96SN: DM96SN0403AN, DM96SN0603BN, DM96SN0803BN, DM96SN0804CN, DM96SN0805CN, DM96SN1005CN, DM96SN1205DN, DM92SN0403AN, DM92SN0603BN, DM92SN0803BN, DM92SN0804CN, DM92SN0805CN, DM92SN1004CN, DM92SN1005CN, DM92SN1205DN, DC96SN0403BN, DC96SN0603BN, DC96SN0804CN, DC96SN1005CN, DC96SN1205DN)
- Payne PG9YAA / PG9YAB (95% single-stage condensing, direct or non-direct vent)
- Carrier 59TP6C (two-stage condensing with InteliSense, Performance series; also 926TC)
- Lennox G60DF / G60DFV (older two-stage SureLight boards 18M3401, 46M9901, 18M9901, 49M5901)
- Lennox G60UH / G60UHV (SureLight boards 100869 and 100870)
- Rheem / Ruud R801T Ultra Low NOx (14 ng/J) single-stage upflow/horizontal, constant-torque blower
- Rheem / Ruud 802V / 80MDV (80% two-stage communicating, ECM blower; model numbers (-)802V and (-)(-)80MDV)
- Trane / American Standard S8B1 / S8X1 / S8X2 (80% single-stage and two-stage)
- Trane / American Standard A801X060AM3S (80% single-stage, 2024 installation manual)
- Trane / American Standard A801X (80% single-stage: A801X040AM3SD, A801X040BM2SD, A801X060BM4SD, A801X080BM4SD, A801X080CM5SD, A801X100CM5SD, A801X120DM5SD)
- Goodman / Amana GMEC96 / GCEC96 (two-stage, multi-speed ECM: GMEC96, GCEC96, Amana AMEC96, ACEC96)
- Goodman / Amana / Daikin GMSS92 / GMSS96 / GCSS9 (single-stage, 92% and 96%: GMSS92, GMSS96, GCSS92, GCSS96, Amana AMSS92, AMSS96, ACSS92, ACSS96, Daikin VMSS9, VCSS9)
- Goodman / Amana / Daikin GMES92 / GMES96 / GCES96 (single-stage, 92% and 96%: GMES92, GMES96, GCES96, Amana AMES92, AMES96, ACES96, Daikin VMES96, VCES96)
- Goodman / Amana GM9C96 / GC9C96 (two-stage, nine-speed ECM: GM9C96, GC9C96, Amana AM9C96, AC9C96)
- Goodman / Amana GMH8 / GDH8 / GME95 (modified two-stage: 80% GMH8, GDH8, Amana AMH8, ADSH8; 95% GME95, Amana AMEH96)
- Goodman / Amana / Daikin GMS8 / GDS8 (80% single-stage: GMS8, GDS8, Amana AMS8, ADSS8, Daikin VMS8, VDS8)
- Goodman / Amana GMES96 U Ultra-Low NOx (single-stage 96%, U models: GMES96, Amana AMES96)
- Goodman / Amana GM9S96 U Ultra-Low NOx (single-stage 96%, U models: GM9S96, Amana AM9S96; Daikin DM96SN U: DM96SN0403BU, DM96SN0603BU, DM96SN0805CU)
- Goodman / Amana GMVS80 U Ultra-Low NOx (80% single-stage, variable-speed communicating: GMVS80, Amana AMVS80)
- Goodman / Amana GKS9 / AKSS92 (92% single-stage upflow: GKS9, Amana AKSS92)
- Goodman / Amana GMVM97 / GCVM97 ComfortBridge (97% modulating, BA revision and later: GMVM97, GCVM97, Amana AMVM97, ACVM97)
- Goodman / Amana GMVC96 / GCVC96 (96% two-stage variable-speed, *MVC96*BA and *CVC96*BA)
- Goodman / Amana GMVC96 / GCVC96 BB ComfortBridge (96%, BB revision: GMVC96, GCVC96, Amana AMVC96, ACVC96)
- Goodman / Amana / Daikin AMVC96 / DM96VC / DM80VC ComfortNet (two-character codes: AMVC96, ACVC96, GMVC96, GCVC96 before the BA revision; DM96VC0403BN, DM96VC0603BN, DM96VC0803BN, DM96VC0804CN, DM96VC1005CN, DM96VC1005DN, DM96VC1205DN, DC96VC0403BN, DC96VC0603BN, DC96VC0803BN, DC96VC0804CN, DC96VC1005CN, DC96VC1205DN, DM80VC0603B, DM80VC0604B, DM80VC0805C, DM80VC1005C, DD80VC0603B, DD80VC0805C, DD80VC1005C)
- Goodman / Amana GMVS96 / AMVS96 U-revision (96% variable-speed with analog pressure sensor, model numbers GMVS96*U and AMVS96*U; also Daikin DM96SC U: DM96SC0603BU, DM96SC0805CU)
- Goodman / Amana GMVM96 / GCVM96 / AMVM96 / ACVM96 (96% modulating, model numbers *MVM96 and *CVM96; also Daikin DM97MC/DC97MC: DM97MC0603BNA, DM97MC0803BNA, DM97MC0804CNA, DM97MC1005CNA, DM97MC1205DNA, DC97MC0603BNA, DC97MC0803BNA, DC97MC0804CNA, DC97MC1005CNA)
- Rheem / Ruud R801T / 80MSX (80% single-stage, constant-torque blower; model numbers (-)801T and (-)(-)80MSX)
- Rheem / Ruud 802P / 80MDP (80% two-stage, model numbers (-)802P and (-)(-)80MDP)
- Rheem / Ruud 802T / 80MDT (80% two-stage with constant-torque blower, model numbers (-)802T and (-)(-)80MDT)
- Rheem / Ruud 801S / 801P / 80MSS / 80MSP (80% single-stage, model numbers (-)801S, (-)801P, (-)(-)80MSS and (-)(-)80MSP)
- Rheem / Ruud W801T (Rheem Select 80% downflow single-stage)
- Rheem / Ruud R951T / R95T / R92T (90%+ single-stage condensing, constant-torque blower; model numbers (-)951T, (-)95T, (-)(-)95MSX, (-)92T, (-)(-)92MSX, e.g. R95TC0701317MSA, R92TC0701317MSA)
- Rheem / Ruud 801V Ultra Low NOx (80% communicating, constant CFM blower, upflow/horizontal)
- Carrier 58STA / 58STX (80% single-stage, 4-way multipoise; also 313AAV, 313JAV)
- Carrier 58CTA / 58CTX (80% two-stage, 4-way multipoise, Series 140/E)
- York TG9S (95.5% AFUE single-stage PSC, multi-position)
- York TM9T (96% AFUE two-stage PSC, multi-position)
- York TM9X (95.5% AFUE single-stage ECM, multi-position: TM9X040A10MP11, TM9X060B12MP11, TM9X080B12MP11, TM9X080C16MP11, TM9X100C16MP11, TM9X100C20MP11, TM9X120D20MP11)
- York TM9M (97% AFUE modulating PSC, multi-position)
- York YP9C / TP9C / CP9C / LP9C (up to 98% AFUE modulating ECM, multi-position)
- York TM9V (96% AFUE two-stage variable-speed ECM, multi-position)
- York UTEC Board (single- and two-stage furnaces from August 2009; SAP 539617, 542760, 542767, 542766; Source 1 S1-33102956000, S1-03102951001, S1-33102954000, S1-33102955000)
- York White-Rodgers Board (the generation before the 2009 UTEC boards; 265901, S1-33109167000 / 265902, S1-33109168000 / 265903, S1-33109169000 / 265904)
- York TI Board (older furnaces; 031-01972-000 TI 6DT-1, 031-01973-000 TI 6DT-2, 031-09117-000 TI 6MD-1, 031-09118-000 TI 6MI-1)
- Carrier 58TN0A / 58TN1A (80% two-stage, variable-speed, 4-way multipoise; also 880TA, 881TA)
- Carrier 58TN0B / 58TN1B (80% two-stage, variable-speed, 4-way multipoise)
- Carrier 58TP0A / 58TP1A (80% two-stage, variable-speed ECM, 4-way multipoise; also PG80VTLA)
- Carrier 58TP0B / 58TP1B InteliSense (80% two-stage, variable 25-speed ECM, 4-way multipoise)
- Carrier 59SC5A (single-stage condensing, 4-way multipoise; also 912SB, 912SC, 922SA, 925SA, PG92SAS, PG92SCS, PG95SAS)
- Bryant 925TA (two-stage condensing, 4-way multipoise; also PG95XAT)
- Bryant 926SA (single-stage condensing, multi-speed ECM, multipoise)
- Bryant 926SB (single-stage condensing, 25-speed ECM, InteliSense)
- Carrier 59SC5B / 59SC2D (single-stage 35-in. condensing, 4-way multipoise; also 912SD, 915SB)
- Carrier 59MN7A / 59MN7B (modulating condensing, 4-way multipoise; also 987MA, 987MB)
- Carrier 59MN7C modulating condensing (59MN7C060C17, 59MN7C060C21, 59MN7C080C17, 59MN7C080C21, 59MN7C100C21, 59MN7C120C24; also 987MC)
- Carrier 59TP6B / 59TP6A / 59TN6A two-stage (condensing, two-digit codes; also 926TA, 926TB, 986TB, PG96VAT, PG96VTAA)
- Carrier 59TN6B two-stage condensing (variable-speed: 59TN6B060C17, 59TN6B080C17, 59TN6B080C21, 59TN6B100C21, 59TN6B120C24; also 986TC)
- Carrier 59TN6C two-stage condensing (variable-speed, 35 in. tall: 59TN6C040C14, 59TN6C060C17, 59TN6C080C17, 59TN6C080C21, 59TN6C100C21, 59TN6C120C24)
- Carrier 59TN7A two-stage condensing (variable-speed, 35 in. tall: 59TN7A060C17, 59TN7A080C17, 59TN7A080C21, 59TN7A100C21, 59TN7A120C24)
- Carrier 59SU5A (single-stage Ultra Low NOx condensing, upflow/horizontal, 35 in. tall)
- Carrier 59SU5B single-stage Ultra Low NOx (condensing, 35 in. tall: 59SU5B040M17, 59SU5B060M17, 59SU5B080M21, 59SU5B100M21; also PG95MSUA)
- Carrier 59TP7A two-stage InteliSense (condensing, variable-speed, non-communicating: 59TP7A060V17, 59TP7A080V17, 59TP7A080V21, 59TP7A100V21, 59TP7A120V24)
- Carrier 59SC2E / 59SC6A (single-stage 35-in. condensing, 4-way multipoise; also 912SE, PG96MSAA)
- Carrier 58CU0A (80% communicating, Ultra Low NOx, 4-way multipoise)
- Carrier 58SU0A (80% single-stage, ECM blower, Ultra Low NOx, 4-way multipoise; also 830SA)
- Carrier 58SU0B (80% single-stage, ECM blower, Ultra Low NOx, 3-digit display)
- Carrier 58SB0B / 58SB1B / 58SC0B / 58SC1B (80% single-stage, multi-speed ECM, 4-way multipoise; also PG80MSA, PG80MSLA)
- Bryant 820SA / 821SA (80% single-stage, 4-way multipoise)
- Carrier 58SB0A / 58SB1A / 58SC0A / 58SC1A (single-stage, non-condensing; 58SC is the multi-speed ECM version; also 800SA, 801SA, PG80ESAA, PG80ESLA)