Goodman / Amana GRVM97 Furnace Codes

Applies to: Goodman / Amana GRVM97 (R-32 era 97% modulating, variable-speed communicating; also GDVM97, ARVM97, ADVM97, DR97MC, DD97MC). Three-character seven-segment display on the integrated control.

Covers Goodman GRVM97/GDVM97 and Amana ARVM97/ADVM97 (RS6612306 Rev. 1, pp. 41-44). Daikin's DR97MC/DD97MC service instructions (RSD6612306 Rev. 1, pp. 41-44) list the same codes and fault descriptions. The older R-410A GMVM97 ComfortBridge has its own chart.

CodeMeaningWhat to check
IdLIdle: normal operation.
nonENo display: no 120 VAC to the furnace or no 24 V to the integrated control.Breaker, manual disconnect and door switch; 120 VAC on the transformer primary and 24 V on the secondary; 24 V wires to the 12-pin harness. Replace the control only after the wiring checks out.
Eb0Circulator blower motor not running when it should be.Loose motor power leads; open circuit or loose wiring at the inductor (3/4 and 1 HP models); failed motor.
Eb1The control has lost communication with the circulator blower motor.Loose wiring at the motor leads; check the motor and the control and replace whichever has failed.
Eb2Blower motor horsepower in the shared data set doesn't match the motor.Make sure the motor horsepower is the one specified for the model; make sure the shared data set is correct and re-populate it with the CoolCloud HVAC app. The code clears once they match.
Eb3Blower motor running in a power, temperature or speed limiting condition; the furnace runs at reduced performance with less airflow.Blocked filters, restrictive or undersized ductwork (all registers open), high ambient temperature.
Eb4Blower motor senses a loss of rotor control or high current.Abnormal motor loading or a sudden blockage: check filters, filter grilles, registers, the duct system and the furnace air inlet and outlet.
Eb5Blower motor failed to start 10 consecutive times.Obstruction in the blower housing, seized bearings or a failed motor; repair or replace the wheel or motor.
Eb6Blower motor shut down on over or under voltage, or on over-temperature of its power module.Line voltage must be within the range on the rating plate; high ambient temperature.
Eb7Blower motor doesn't have enough information to operate, or failed to start 40 consecutive times.Make sure the control has the correct shared data set; check for a locked rotor.
Eb9Airflow lower than demanded; reduced performance or low stage when high stage is expected.Blocked filters, restrictive or undersized ductwork (all registers open), high ambient temperature.
Ed0Data not yet on network.Populate the shared data set with the CoolCloud HVAC app; the code clears once the data is downloaded.
Ed1Invalid shared data; operation different than expected, or none.Make sure the shared data set is right for the model and re-populate it with the CoolCloud HVAC app.
EE0Lockout after too many ignition retries (3 total): failure to establish flame, or loss of flame after it was established.Gas supply and pressure; front cover pressure switch and drainage; igniter and its alignment; restricted orifices; flame sensor (clean with steel wool); flue blockage, length and elbows; combustion air; inducer performance. How to fix →
EE1Low-stage pressure switch circuit closed at the start of the heating cycle.Sticking switch contacts or a short in the switch wiring. How to fix →
EE2Low-stage pressure switch circuit open; the inducer runs with no further operation.Pressure switch hose blocked, pinched or misconnected; blocked flue or inlet pipe; blocked drain system; weak inducer; wrong switch set point or bad contacts; loose wiring. How to fix →
EE3Primary limit circuit open; the circulator blower runs with no furnace operation.Blocked filters or restrictive ductwork; blower speed and motor; loose wiring in the limit circuit. Check the temperature rise against the specification sheet. How to fix →
EE4Flame sensed with no call for heat; inducer and circulator run continuously.Short to ground in the flame sense circuit, a lingering burner flame, or a slow-closing gas valve. How to fix →
EE5Open fuse.Replace the fuse (3-amp automotive type) and find the short in the low-voltage wiring, or the back of the control touching the mounting panel because standoffs are missing. How to fix →
EE6Low flame sense microamp signal (furnace still runs).Clean a coated or oxidized flame sensor with steel wool; check its position in the flame; check the inlet air piping for blockage, length, elbows and termination; compare gas pressure with the rating plate. How to fix →
EE7Problem with the igniter circuit.Wiring from the control to the igniter; a shorted igniter; the furnace ground; the igniter output from the control (igniter relay fault). How to fix →
EE8High-stage pressure switch circuit closed at the start of the heating cycle; the furnace won't run on high stage but runs normally on low.Sticking high-stage switch contacts or a short in the switch wiring. How to fix →
EE9High-stage pressure switch circuit open; the furnace won't run on high stage but runs normally on low.Pressure switch hose blocked, pinched or misconnected; blocked flue or inlet pipe; blocked drain system; weak inducer; wrong switch set point or bad contacts; loose wiring. How to fix →
E10Grounding fault.Poor neutral connection: verify the neutral wire to the furnace and continuity to the ground source.
E11Open rollout switch.Gas pressure too high, misaligned burners, or a restricted heat exchanger or vent. How to fix →
E15External return air temperature sensor circuit open (no return reading in the CoolCloud app).Allow up to 90 seconds for the control to detect sensors. Make sure the probe is plugged in all the way and its connector is crimped properly; the probe should read 10 kΩ at 77°F (lower when warmer, higher when colder); otherwise replace the control board.
E16External return air temperature sensor circuit shorted.Check the probe terminals and conductors for a short; if the error shows with the probe unplugged, check the board connector for a short; replace the control board.
E17External supply air temperature sensor circuit open (no supply reading in the CoolCloud app).Allow up to 90 seconds for detection. Probe plugged in all the way, connector crimped properly, 10 kΩ at 77°F; otherwise replace the control board.
E18External supply air temperature sensor circuit shorted.Check the probe terminals and conductors for a short; if the error shows with the probe unplugged, check the board connector; replace the control board.
E19Onboard return air temperature sensor unplugged.Power cycle (allow up to 90 seconds for detection); look for damage to the onboard sensor (R311); replace the control board.
E1AOnboard return air temperature sensor shorted.Power cycle (allow up to 90 seconds); make sure nothing on the board is shorting the onboard sensor (R311); replace the control board.
EEA115 VAC polarity reversed.Correct the polarity per the wiring diagram and verify the furnace ground.
EEbThe control is not energizing the gas valve when it should.Check the gas valve circuit wiring; if it is good, replace the integrated control. Goodman says not to replace the gas valve for this code.
EECGas valve energized when it should be off.Cycle 120 VAC. If EEC stays, it is a wiring problem outside the control: inspect the system wiring and replace the system harness; if EEC still stays, replace the control.
EEdAuxiliary limit switch open (blower compartment).120 V power shut off during a heat cycle; not enough air over the heat exchanger (blocked filters, restrictive ducts, blower speed or failed blower motor); loose wiring in the limit circuit. How to fix →
EEEThe control has detected an internal fault.Power off for at least 3 minutes and back on; inspect the 120 V and 24 V wiring and the ground. Replace the control; don't replace other parts based on this code.
EEFAUX switch (condensate switch) open.High water in the evaporator coil drain pan or auxiliary drain pan: check the pan, the drain piping and the auxiliary pan.
EbFInducer communicating error.Make sure the inducer connector is fully inserted and the integrated control is properly grounded.
ECFGas valve stepper motor communication error.No power to the gas valve: verify the voltage to the gas valve.
EAFLost communication with the R-32 sensor; the furnace is in mitigation mode (fan only).The furnace may not be paired with an R-32 cooling unit: see the manual's R-32 information section. Otherwise check the sensor wire and connection, and replace the sensor if needed.
EA0The R-32 sensor has detected a refrigerant leak; mitigation mode (fan only).Look for a leak at the indoor coil. Heating resumes once no leak is detected and the 5-minute delay is over.
EA1The R-32 sensor has detected a fault; mitigation mode (fan only).Check the R-32 sensor and replace it if necessary.
EA2The control has detected a problem with its internal A2L relay and is running mitigation mode.Disconnect any wire on the control's ALARM terminal and cycle power. If the code clears, repair the ALARM wiring; if not, replace the control.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Goodman Service Instructions, GRVM97/GDVM97 and Amana ARVM97/ADVM97 97% Modulating Gas Furnaces with Variable-Speed ECM Motor, RS6612306 Rev. 1, Troubleshooting pp. 41-44 (read from page images). The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.