Goodman / Amana GMH8 / GDH8 / GME95 Furnace Codes

Applies to: Goodman / Amana GMH8 / GDH8 / GME95 (modified two-stage: 80% GMH8, GDH8, Amana AMH8, ADSH8; 95% GME95, Amana AMEH96). Single red diagnostic LED on the integrated control module.

Goodman's GME95/AMEH96 service manual (RS6612005 Rev. 1, Troubleshooting Chart pp. 49-50) prints the same LED table as the GMH8 manual, so both are covered here.

CodeMeaningWhat to check
NoneNo signal: furnace doesn't run.No 115 V or 24 V at the control (disconnect off, door switch open, 24 V wires loose), blown fuse or breaker, or an internal control fault. Check the 3 A fuse and look for shorts in the 115 V and 24 V circuits; replace the fuse only with a 3 A automotive fuse. How to fix →
Steady onNormal operation.None.
1 flashLockout after too many ignition retries (3 total).Failure to establish flame (no gas, front cover pressure switch stuck open, bad igniter or alignment, wrong orifices, coated, oxidized or poorly connected flame sensor) or loss of flame after it was established (interrupted gas, lazy flames from gas pressure or flue/combustion air restriction, front cover pressure switch opening, weak inducer). Goodman says to sand a coated sensor with emery cloth. How to fix →
2 flashesPressure switch circuit closed while the inducer isn't running.Inducer pressure switch contacts sticking, or a short in the pressure switch circuit. How to fix →
3 flashesPressure switch circuit not closed with the inducer running; inducer runs continuously.Pressure switch hose blocked, pinched or misconnected; blocked flue or inlet pipe, blocked drain system or weak inducer; wrong setpoint or bad contacts; loose wiring. How to fix →
4 flashesPrimary limit open; circulator blower runs continuously.Not enough air over the heat exchanger (blocked filters, restrictive ductwork, wrong blower speed, failed blower), a faulty primary limit, or loose wiring. How to fix →
5 flashesFlame sensed with no call for heat; inducer and circulator run continuously.Short to ground in the flame sense circuit (sensor or wiring).
6 flashesRollout limit open, or the control's fuse is blown.Flame rollout, misaligned burners, blocked flue or inlet pipe, failed inducer, loose wiring, a short in the 24 V control or safety circuits, or a faulty rollout limit. Replace the fuse only with a 3 A automotive fuse. How to fix →
7 flashesLow flame sense microamp signal (furnace still runs).Coated or oxidized sensor, sensor out of position, or lazy flame from wrong gas pressure or combustion air. Clean the sensor (sand it, or steel wool per Goodman's notes), check alignment, compare gas pressure with the rating plate. How to fix →
8 flashesProblem with the igniter circuit.Improperly connected or bad igniter, poor unit or burner ground, or a faulty control. Check the igniter wiring and the unit ground; replace the control if the rest checks out. How to fix →
C (continuous flashing)115 V or 24 V polarity reversed; inducer runs continuously.115 V polarity reversed at the furnace or control, the red and blue transformer wires reversed, or a poor unit ground.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Goodman/Amana 80% Modified Two Stage Gas Furnaces AMH8, GMH8, GDH8, ADSH8 Service Instructions RS6612007 Rev. 4 (2022), Troubleshooting Chart pp. 41-42. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.