Goodman / Amana GMVC96 / GCVC96 Furnace Codes

Applies to: Goodman / Amana GMVC96 / GCVC96 (96% two-stage variable-speed, *MVC96*BA and *CVC96*BA). Dual seven-segment display on the integrated control module.

The * in the model number is the brand letter, so the same instructions cover Amana AMVC96 and ACVC96 in the BA revision. Other revisions may differ; check the instructions for yours.

CodeMeaningWhat to check
d0Equipment lacks shared data.Populate the shared data set using the memory card.
Eb0Circulator blower motor is not running when it should be running.Wiring connections, continuity through the inductor, the motor.
Eb1Integrated control module has lost communications with the circulator blower motor.Wiring connections, motor, then the control.
Eb2Circulator blower motor horsepower in the shared data set does not match the motor.Motor horsepower against the nameplate; reload shared data with the correct memory card.
Eb3Circulator blower motor is operating in a power, temperature, or speed limiting condition.Filters, blocked ductwork, closed registers, duct sizing. How to fix →
Eb4Circulator blower motor senses a loss of rotor control or high current.Filters, grilles, registers and ducts for blockage. How to fix →
Eb5Circulator blower motor fails to start 10 consecutive times.Obstruction in the blower, wheel and shaft rotation, motor.
Eb6Circulator blower motor shuts down for over or under voltage, or for over temperature on the power module.Voltage to the furnace against the nameplate range.
Eb7Circulator blower motor lacks information to operate properly, or fails to start 40 consecutive times.Locked rotor; confirm the control has the correct shared data.
Eb9Airflow is lower than demanded.Filters, blocked ductwork, closed registers, duct sizing. How to fix →
E10Grounding fault or poor neutral connection.Neutral connection to the furnace and continuity to ground.
E11Open rollout switch.Gas pressure, burner alignment, burner restriction. How to fix →
Ed0Data not yet on network.Populate the shared data set using the memory card.
Ed1Invalid memory card data.Confirm the shared data set is right for the model; reload with the correct memory card.
EE0Lockout after too many ignition retries (3 total): failure to establish flame or loss of flame after it was established.Gas supply, front cover pressure switch and drainage, igniter, flame sensor, flue piping, inducer. How to fix →
EE1Low stage pressure switch circuit is closed at the start of the heating cycle.Sticking switch contacts or a short in the switch wiring. How to fix →
EE2Low stage pressure switch circuit is not closed. Inducer runs continuously with no furnace operation.Switch hose, blocked flue or inlet pipe, blocked drain, weak inducer, wrong switch, loose wiring. How to fix →
EE3Primary limit circuit is open. Circulator blower runs continuously.Filters, restrictive ductwork, blower speed or failed blower motor, limit wiring. How to fix →
EE4Flame sensed with no call for heat. Inducer and blower run continuously.Short to ground in the flame sense circuit; lingering flame from a slow-closing gas valve.
EE5Open fuse.Short in the low voltage wiring. Fix it, then replace the fuse. How to fix →
EE6Flame sense microamp signal is low (furnace still operates).Coated or mispositioned flame sensor; lazy flame from gas pressure or combustion air. How to fix →
EE7Problem with the igniter circuit.Igniter wiring, shorted igniter, unit ground, igniter relay on the control. How to fix →
EE8High stage pressure switch circuit is closed at the start of the heating cycle. Furnace runs on low stage only.Sticking switch contacts or a short in the switch wiring. How to fix →
EE9High stage pressure switch circuit is not closed. Furnace runs on low stage only.Switch hose, flue and inlet piping, drain, inducer, wiring. How to fix →
EEAPolarity of 115 volt AC is reversed, or poor unit ground.Correct polarity and ground.
EEbGas valve is not energized when it should be (external gas valve error).Gas valve circuit wiring; control board.
EECGas valve is energized when it should not be (internal gas valve error).Gas valve circuit wiring; control board.
EEdAux limit switch open (blower compartment).Filters, ductwork, blower speed and motor, wiring. How to fix →
EEFAux switch (condensate switch) open.Evaporator drain pan, trap and piping. How to fix →

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Goodman Installation Instructions for *CVC96*BA and *MVC96*BA two-stage gas furnaces, IOG-2015A (5/2018), Status Codes and Troubleshooting Chart, pp. 44-48. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.