York YP9C / TP9C / CP9C / LP9C Furnace Codes

Applies to: York YP9C / TP9C / CP9C / LP9C (up to 98% AFUE modulating ECM, multi-position). LED on the furnace control board that flashes red, green or amber, seen through the clear view port in the lower door.

Johnson Controls also sells furnaces under the Coleman and Luxaire names. Codes match only when the control board is the same, so check the label inside the blower door. TP9C, CP9C and LP9C are the same furnace under other brand names (one installation manual covers all four). The codes match the TM9M except 4, 5 and 6 red.

CodeMeaningWhat to check
Steady offNo 24 V power to the board.Check the 24 V control circuit fuse on the board, the circuit breaker or fuse on the 115 V supply, and the 24 V transformer. How to fix →
1 greenNormal operation with no call for heat.
2 greenNo error codes in memory (shown during fault code retrieval).
3 greenError codes cleared from memory.
Rapid greenControl is in factory speed-up mode.Used only during factory run-testing. Cycle power to the furnace off and back on to stop it.
1 amberNormal operation with call for cooling.
2 amberNormal operation with call for heat.
3 amberNormal: burner on at the end of the heating cycle after the thermostat is satisfied.
4 amberHeating capacity reduced by a restriction in the circulating air system.Check for a dirty filter or closed registers. How to fix →
5 amberHeating capacity reduced by a restriction in the combustion air or vent system.Check for blocked vent/air pipe or a clogged condensate drain. Above 4,000 ft this may also indicate automatic, normal derating for altitude. How to fix →
6 amberHeat pump applications only: normal operation with call for heat pump heating.
Rapid amberLow flame sense current.Check for a dirty or mislocated flame sensor rod. How to fix →
1 redFlame present with no power to the gas valve.A gas valve that is slow to close or leaks gas through to the burners. How to fix →
2 redPressure switch closed with inducer pressure below the switch setpoint (closed when it should be open).Check the pressure switch and pressure transducer. How to fix →
3 redPressure switch open with inducer pressure above the switch setpoint (open when it should be closed).Check the pressure switch and pressure transducer. How to fix →
4 redHigh limit switch open, defective temperature sensor, or open 24 V fuse.Can be caused by a dirty air filter, improperly sized ducts, a faulty blower motor, restricted circulating airflow or an open fuse on the control board. How to fix →
5 redRollout switch or condensate pressure switch open.Check the rollout switch(es) on the burner assembly. It is manual reset: push the small button in the center of the switch. If it can't be reset or trips again, have a qualified service technician find the cause. How to fix →
6 redGas valve communication error.York gives no further steps here. Check the wiring between the control board and the gas valve.
7 redLockout: no ignition after three tries.Locks out for one hour, then tries again. Check gas supply, igniter, gas valve and flame sensor. How to fix →
8 redLockout: too many flame recycles (flame lost five times during one heating cycle).Faulty gas valve, low gas pressure or dirty flame sensor. Locks out for one hour, then tries again. How to fix →
9 redReversed line polarity or improper grounding.Check polarity of the incoming power and the grounding of the furnace, including the transformer ground and the L1 and neutral connections.
10 redGas valve circuit shorted.Check the gas valve wiring. If it's correct, replace the gas valve.
11 redMain blower failure: main limit opened and didn't reclose within five minutes.The blower motor or blower wheel has failed. How to fix →
12 redID plug missing or not connected properly.Check for a loose plug or loose wires in the plug.
Steady on redControl fault, or 115 V present without 24 V.Check whether both 24 V and 115 V are supplied to the board. If not, correct the voltage problem. If both are there, replace the control board.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: York YP9C/CP9C/LP9C/TP9C Installation Manual, 1083292-UIM-A-0114, Furnace Control Diagnostics and Fault Code Storage and Retrieval p. 41. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.