Goodman / Amana / Daikin GM9S96 / GC9S96 / GM9S92 Furnace Codes

Applies to: Goodman / Amana / Daikin GM9S96 / GC9S96 / GM9S92 (96% and 92% condensing, single-stage). Three-character seven-segment display on the integrated control.

The same service manual covers Amana AM9S92/AM9S96/AC9S96 and Daikin VM9S96/VC9S96. Older production of these models may use a flashing-LED board instead of the three-character display.

CodeMeaningWhat to check
EE0Lockout after too many ignition retries (3 total): failure to establish flame or loss of flame after it was established.Gas supply, igniter, flame sensor, flue and intake blockage. How to fix →
EE1Pressure switch circuit closed at the start of the heating cycle.Stuck pressure switch contacts or a short in the switch wiring. How to fix →
EE2Pressure switch circuit not closed. Inducer runs continuously, no furnace operation.Pressure switch hose, blocked flue or intake pipe, blocked condensate drain, weak inducer, wrong switch, loose wiring. How to fix →
EE3Primary limit circuit open. Circulator blower runs continuously, no furnace operation.Dirty filter, restrictive ductwork, wrong blower speed or failed blower motor, loose limit wiring. How to fix →
EE4Flame sensed with no call for heat. Inducer and blower run continuously.Short to ground in the flame sense circuit; slow-closing gas valve leaving a lingering flame.
EE5Open fuse. No furnace operation.Find the short in the low voltage wiring before replacing the fuse. How to fix →
EE6Low flame sense microamp signal (furnace still runs).Clean the flame sensor, check its position in the flame, check gas pressure and combustion air. How to fix →
EELIgniter circuit problem.Igniter connection or short, unit ground, igniter relay on the control.
EEA115 V AC polarity reversed, or poor unit ground.Swap hot and neutral at the furnace; verify ground.
EEbGas valve not energized when it should be (external gas valve error).Gas valve wiring and coil.
EECGas valve energized when it should not be (internal gas valve error).Control board; shut the gas off if the valve stays open.
E10Grounding fault or poor neutral connection.Ground and neutral at the furnace and the panel.
E11Open rollout switch.Find the cause (blocked flue, cracked heat exchanger, burner problem) before resetting. How to fix →
EEnIgniter open.Measure igniter resistance; check the harness.
EEJInducer relay error.Inducer wiring and the control's inducer relay.
EEHTwinning error (twinned furnaces not working together).Twin wiring between the two controls.
EEEInternal fault or IRQ loss in the control board.Control board.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Goodman Service and Troubleshooting RS6612022R1 (GM9S92/GM9S96/GC9S96), 1 Stage Troubleshooting Codes, pp. 29–30. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.