Lennox EL296UHV / SL280UHV control 107045 Furnace Codes
Lennox's service literature for the EL296UHV(X) and EL296DFV(X) (1125, 1126) and the SL280UHV/SL280UHNV and SL280DFV (1116, 1117) prints the same 107045 code table. Earlier units have ignition control 103130, which has more codes (E116, E126, E276, E291, E294, E331, E349, E400-E409); see the 103130 chart. The model number doesn't tell you which control is fitted: check the part number on the control's label.
| Code | Meaning | What to check |
|---|---|---|
| E000 | No error in memory. | None. |
| E105 | Device communication problem: no other devices on the RSBus. | Usually electrical noise. Keep high voltage separated from the RSBus wiring; check for miswired or loose connections between the thermostat, indoor and outdoor units; look for a high voltage noise source near the system. Clears when communication returns. How to fix → |
| E110 | Low line voltage (below the nameplate rating). | Check and correct line voltage. Clears 5 seconds after recovery. |
| E111 | Listed as low line voltage; Lennox's action is to reverse the line power wiring (polarity). | Reverse the line power wiring. Resumes 5 seconds after recovery. |
| E112 | Ground not detected; system shuts down. | Provide a proper earth ground. Resumes 5 seconds after recovery. |
| E113 | High line voltage (above the nameplate rating). | Provide voltage within range. Resumes 5 seconds after recovery. |
| E114 | Line voltage frequency out of range. | No 60 Hz power: check voltage and line frequency. Resumes 5 seconds after recovery. |
| E115 | Low 24 V (the control restarts if it recovers). | 24 V range is 18 to 30 V. Check and correct; look for power-robbing equipment on the system; a larger VA transformer may be needed. Clears after recovery. |
| E117 | Poor ground detected (warning only). | Provide proper grounding for the unit. Clears 30 seconds after recovery. |
| E120 | Unresponsive device (communicating only). | Usually the outdoor unit is slow to answer the indoor unit's polling. Cycle power and check all wiring connections. Clears when the device responds. How to fix → |
| E124 | Communicating thermostat signal missing for more than 3 minutes. | Check the four wiring connections and ohm the wires; cycle power at the thermostat. All services stop until the thermostat's heartbeat message returns. How to fix → |
| E125 | Control failed self-check or hardware (flame sense circuit faults, pin shorts, etc.); control not communicating. | Cycle power. Replace the control if the problem persists and prevents service. Critical alert; clears 300 seconds after recovery. |
| E131 | Corrupted control parameters (communicating only). | Reconfigure the system: exit commissioning and run Set Factory Default. Replace the control if heating or cooling isn't available. The control still runs on default settings. |
| E150 | A2L refrigerant leak alarm. | Lennox lists this code on the 107045 control without an action. The newer A2L furnaces (EL297UHVK) say it may mean a leak at or in the indoor coil that must be repaired and the charge verified. |
| E151 | A2L sensor fault (communicating mode only). | Lennox lists this code without an action. Check the refrigerant sensor and its wiring. |
| E180 | Outdoor air temperature sensor failure (shown only if shorted or out of range). | Compare sensor resistance with the temperature/resistance chart in the installation instructions; replace the sensor pack if needed. If no sensor should be installed, redo configuration and make sure it shows not installed on the indoor unit About screen. Clears 30 seconds after recovery. |
| E200 | Hard lockout: rollout circuit open or previously open. | Correct the cause of the rollout trip, or replace the rollout switch. Test operation. Clears after recovery. How to fix → |
| E201 | Indoor blower communication failure: can't communicate with the blower motor. | Includes power outage. Possible causes: motor not powered, loose wiring. The problem can be on the control or the motor side. Clears after recovery. How to fix → |
| E202 | Indoor blower motor mismatch: motor horsepower doesn't match unit capacity. | Wrong unit size code selected. Check the Unit Size Codes on the configuration guide or in the instructions. Clears after the correct match is detected following a reset (remove the thermostat while applying power and reprogramming). |
| E203 | Unit size code not programmed (invalid code). | No unit size code selected. Program it from the Unit Size Codes on the configuration guide or in the instructions. Critical alert; clears after a valid code is read following a reset. |
| E204 | Gas valve miswired. | Check gas valve operation and wiring. Clears when repaired. |
| E205 | Gas valve control relay contact shorted. | Check wiring on the control and gas valve. If the wiring is correct, replace the control. |
| E206 | Gas valve second-stage relay failure. | The furnace runs on first stage for the rest of the heat call. If it still can't run second stage, replace the control. |
| E207 | Hot surface igniter sensed open. | Measure igniter resistance; replace if open or outside the range in the installation instructions. How to fix → |
| E223 | Low pressure switch failed open. | Check pressure (inches w.c.) of the switch closing on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. Resumes after the fault clears. How to fix → |
| E224 | Low pressure switch failed closed. | Check whether the low pressure switch is stuck closed on the heat call for longer than 150 seconds. Measure operating pressure; inspect the vent and inducer. How to fix → |
| E225 | High pressure switch failed open. | Check pressure (inches w.c.) of the switch closing on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. Resumes after the fault clears. How to fix → |
| E226 | High pressure switch failed closed. | Check the high pressure switch closing on the heat call, measure operating pressure, inspect the vent and inducer. How to fix → |
| E227 | Low pressure switch open during trial for ignition or run mode. | Check pressure (inches w.c.) of the switch closing on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. Resumes after the fault clears. How to fix → |
| E228 | Combustion air inducer calibration failure. | The control couldn't calibrate the pressure switch. Check the vent system and pressure switch wiring. How to fix → |
| E229 | Ignition on high fire. | The control switched to high-fire ignition because the low-fire pressure switch didn't close in time. No action needed. |
| E240 | Low flame current, run mode. | Check flame microamps with the control diagnostics (see the flame table above); clean or replace the sensor; measure neutral to ground for a good unit ground. Clears after the heat call completes. How to fix → |
| E241 | Flame sensed out of sequence; flame still present. | Shut off the gas. Check the gas valve for a leak and replace it if needed. Clears when the fault recovers. |
| E250 | Limit switch circuit open. | Check firing rate, blockage in the heater and airflow. If the limit doesn't close within 3 minutes, the unit goes into a 1-hour soft lockout. How to fix → |
| E252 | Discharge air temperature too high (gas heat only). | Check temperature rise, airflow and input rate. Clears when the heat call ends. How to fix → |
| E270 | Soft lockout: too many retries, no flame current sensed. | Check gas flow, that the igniter lights the burner, and flame sensor current. Clears when a heat call finishes successfully. How to fix → |
| E271 | Soft lockout: too many retries; last retry failed when the pressure switch opened. | Check pressure (inches w.c.) of the switch closing on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. Resumes after the fault clears. How to fix → |
| E272 | Soft lockout: too many recycles; last recycle due to the pressure switch opening. | Check whether the low pressure switch is stuck closed, check the high pressure switch closing, measure operating pressure, inspect the vent and inducer. How to fix → |
| E273 | Soft lockout: too many recycles; last recycle due to flame failure. | Check flame microamps, clean or replace the sensor, measure neutral to ground for a good unit ground. How to fix → |
| E274 | Soft lockout: too many recycles; last recycle failed on the limit circuit, or the limit stayed open over 3 minutes. | 1-hour soft lockout. Check firing rate and airflow; check for blockage. How to fix → |
| E275 | Soft lockout: flame sensed out of sequence; flame signal now gone. | Shut off the gas and check the gas valve for a leak. 1-hour soft lockout; clears when flame is proven stable. |
| E290 | Igniter circuit fault: failed igniter or triggering circuitry. | Measure hot surface igniter resistance; replace if open or out of spec. 1-hour soft lockout. How to fix → |
| E292 | Indoor blower motor can't start (obstructed wheel, seized bearings). | Replace the motor or wheel if the assembly doesn't run or meet performance. 1-hour soft lockout; clears after the blower starts. |
| E295 | Indoor blower motor temperature too high (tripped on its internal protector). | Check motor bearings and amps; replace if needed. Clears after the blower demand is satisfied. |
| E310 | Discharge air temperature sensor failure (shown only if shorted or out of range). | Compare sensor resistance with the chart in the installation instructions; replace if needed. Clears 30 seconds after recovery (communicating) or after the heat call (non-communicating). |
| E311 | Heat rate reduced to match indoor blower airflow (warning only). | The blower is in cutback for restricted airflow and the firing rate drops every 60 seconds to match; 2-stage controls drop to first stage. Check the filter and duct system. How to fix → |
| E312 | Restricted airflow in cooling or continuous fan: below the cfm setting (warning only). | The blower is in cutback to protect the motor outside its design range (0 to 0.8 in. w.c. total external static). Check the filter and duct system. Clears after the current call is satisfied. How to fix → |
| E313 | Indoor and outdoor unit capacity mismatch (communicating only). | Wrong indoor/outdoor capacity code. Check configuration. Warning only: the system runs but may not meet efficiency and capacity. Clears when commissioning is complete. |
| E334 | Relay Y1 stuck on the integrated control. | Replace the integrated control. (The installation instructions list this as E344.) |
| E345 | Relay O failure. | Lennox gives no action for this code. |
| E347 | No 24 V output on Y1 with a non-communicating outdoor unit. | Operation stopped: the Y1 relay or stage 1 failed (pilot relay contacts didn't close or the coil didn't energize). Critical alert; clears after reset when Y1 input is sensed. |
| E348 | No 24 V output on Y2 with a non-communicating outdoor unit. | The Y2 relay or stage 2 failed (pilot relay contacts didn't close or the coil didn't energize). Critical alert; clears after reset (Lennox's text says when Y1 input is sensed). |
| E370 | Interlock switch (DS terminal) sensed open for 2 minutes. | The control saw 24 VAC missing for 2 minutes and stops all services until the interlock closes. Clears when 24 VAC is present on DS for at least 10 seconds, or on a power reset. |
How to read the codes
- Status displays: a blinking decimal point means idle; A blower cfm; C cooling stage then cfm; d dehumidification; h heat pump stage; H gas heat stage then cfm (blinks during ignition); dF defrost; U discharge air temperature.
- Error code recall: hold the push button; a new menu item shows every 5 seconds. Release on E to see the last 10 error codes. Select c to clear them (press again while c flashes to confirm). Hold until a solid ≡ shows to exit.
- Flame signal: release on F to show flame current in microamps. Lennox's table for the EL296UHV: normal 2.6 µA or greater, low 2.5 or less, drop-out 1.1. These are higher than Lennox's figures for some of its other furnaces, so use this table.
- E105, E120, E124, E131 and E313 apply only when the furnace is on a communicating (RSBus) thermostat.
Source: Lennox EL296UHV(X) Unit Information, Service Literature 1125 (revised 08/2022), Ignition Control 107045 Diagnostic Codes pp. 40-44, flame signal table; same table in EL296DFV(X) Service Literature 1126 pp. 22-26. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.
Related
- How to read furnace LED flash codes
- Furnace pressure switch troubleshooting
- Flame sensor microamps and cleaning
Other brands
- Lennox Merit ML180UH (80% single-stage)
- Carrier 58CVA / 58CVX (80% variable-speed two-stage)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) R96MSN / N96MSN (single-stage 35-in. condensing, 4-way multipoise)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) R95MSU (single-stage Ultra Low NOx condensing, upflow/horizontal, 35 in. tall)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N95ESN / R92ESN (single-stage 35-in. condensing, 4-way multipoise; also PG95ESA)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N92ESN (single-stage 35-in. condensing, 4-way multipoise)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N9MSE (90% single-stage condensing, PSC blower)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N8MSN / N8MSL (80% single-stage, PSC blower)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N80ESU / R80ESU (80% single-stage, ECM blower, Ultra Low NOx, minor series 2 and 3)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N80MSU (80% single-stage, ECM blower, Ultra Low NOx, 3-digit display, minor series 3)
- Rheem / Ruud R96P / 96MDP (96% two-stage condensing, PSC blower; model numbers (-)96P and (-)(-)96MDP, e.g. R96PA0702317MSA)
- Rheem / Ruud R96V / 96MDV (96% two-stage communicating)
- Rheem / Ruud R97V (97% modulating communicating, downflow/horizontal)
- Rheem / Ruud R98V (98% modulating communicating, upflow)
- Goodman / Amana GR9S80 / GD9S80 (80% single-stage)
- Trane / American Standard S9X1 / S9X2 / S9B1 (96% condensing)
- Lennox EL296UHV / SL280UHV control 103130 (Elite EL296UHV(X), EL296DFV(X) and SL280UHV/SL280UHNV/SL280DFV, earlier units: EL296UH045V36B, EL296UH045XV36B, EL296UH070V36B, EL296UH070XV36B, EL296UH090V36C, EL296UH090XV36C, EL296UH090XV48C, EL296UH090V60C, EL296UH090XV60C, EL296UH110V48C, EL296UH110XV48C, EL296UH110V60C, EL296UH110XV60C, EL296UH135V60D, EL296UH135XV60D, EL296DF045XV36B, EL296DF070V48B, EL296DF070XV48B, EL296DF090V60C, EL296DF090XV60C, EL296DF110V60C, EL296DF110XV60C, SL280UH070V36A, SL280UH070XV36A, SL280UH090V36B, SL280UH090V48B, SL280UH090XV48B, SL280UH090V60C, SL280UH090XV60C, SL280UH110V60C, SL280UH110XV60C, SL280UH135V60D, SL280DF070V36A, SL280DF090V48B, SL280DF090V60C, SL280DF110V60C, SL280UH060NV36A, SL280UH080NV48B, SL280UH080NV60C, SL280UH100NV60C)
- Lennox Elite EL297UHVK(X) / EL297DFVK (two-stage, variable-speed, communicating; upflow/horizontal EL297UH045XV36BK, EL297UH070XV36BK, EL297UH090XV36CK, EL297UH090XV48CK, EL297UH090XV60CK, EL297UH110XV48CK, EL297UH110XV60CK, EL297UH135XV60DK; downflow EL297DF045XV36BK, EL297DF070XV48BK, EL297DF090XV60CK, EL297DF110XV60CK; also Merit SL280UHVK and SL280UHNVK: SL280UH070XV36AK, SL280UH090XV48BK, SL280UH090XV60CK, SL280UH110XV60CK, SL280UH070V36AK, SL280UH090V36BK, SL280UH090V48BK, SL280UH090V60CK, SL280UH110V60CK, SL280UH135V60DK, SL280UH060NV36AK, SL280UH080NV48BK, SL280UH080NV60CK, SL280UH100NV60CK)
- Lennox Signature SLP99UHVK (Dave Lennox Signature, variable capacity, variable speed, communicating: SLP99UH070V36BK, SLP99UH070XV36BK, SLP99UH090V36CK, SLP99UH090XV36CK, SLP99UH090V48CK, SLP99UH090XV48CK, SLP99UH090V60CK, SLP99UH090XV60CK, SLP99UH110V60CK, SLP99UH110XV60CK, SLP99UH135V60DK, SLP99UH135XV60DK)
- Lennox Signature SLP99DFV (Dave Lennox Signature downflow, variable capacity, variable speed, communicating: SLP99DF070XV36B, SLP99DF090XV36C, SLP99DF090XV48C, SLP99DF090XV60C, SLP99DF110XV60C)
- Lennox Elite EL296UHE (96% two-stage, constant torque: EL296UH045XE36B, EL296UH070XE36B, EL296UH090XE48C, EL296UH110XE60C, EL296UH135XE60D; also Elite EL280DFE downflow: EL280DF070E36A, EL280DF090E48B)
- Lennox Elite EL297UHEK (two-stage, constant torque, non-communicating: EL297UH045XE36BK, EL297UH070XE36BK, EL297UH090XE48CK, EL297UH110XE60CK, EL297UH135XE60DK; same control and codes: Elite EL280UHEK and EL280DFEK (80%): EL280UH045E36AK, EL280UH070E36AK, EL280UH070XE36AK, EL280UH090E36BK, EL280UH090E48BK, EL280UH090XE48BK, EL280UH110E48CK, EL280UH110E60CK, EL280UH110XE60CK, EL280DF070E36AK, EL280DF090E48BK)
- Lennox Merit ML196UHEK / Elite EL196UHEK (80% single-stage, constant torque: ML196UH030XE36BK, ML196UH045XE36BK, ML196UH070XE36BK, ML196UH070XE48BK, ML196UH090XE36CK, ML196UH090XE48CK, ML196UH090XE60CK, ML196UH110XE60CK, ML196UH135XE60DK, EL196UH030XE36BK, EL196UH045XE36BK, EL196UH070XE36BK, EL196UH090XE48CK, EL196UH110XE60CK; same control and codes: Elite EL180UHNEK, Merit ML180UHEK, ML193DFEK, Elite EL195UHNEK: EL180UH040NE36AK, EL180UH060NE36AK, EL180UH080NE48BK, EL180UH100NE60CK, ML180UH045E36AK, ML180UH045XE36AK, ML180UH070E36AK, ML180UH070E36BK, ML180UH070XE36BK, ML180UH090E48BK, ML180UH090XE48BK, ML180UH090E60CK, ML180UH110E60CK, ML180UH110XE60CK, ML180UH135E60DK, ML193DF045XE36BK, ML193DF070XE36BK, ML193DF090XE48CK, EL195UH040NE36BK, EL195UH060NE36BK, EL195UH080NE48CK, EL195UH100NE60CK; variable-speed Merit ML180UHVK: ML180UH030V36AK, ML180UH045V36AK, ML180UH070V36AK, ML180UH070V36BK, ML180UH070V48BK, ML180UH090V48BK, ML180UH110V60CK, ML180UH135V60DK)
- Lennox Merit ML196UHE / ML196DFE / ML193UHE (single-stage, red LED controls 103217-03 and 107163-01: ML196UH030XE36B, ML196UH045XE36B, ML196UH070XE36B, ML196UH070XE48B, ML196UH090XE36C, ML196UH090XE48C, ML196UH090XE60C, ML196UH110XE60C, ML196UH135XE60D, ML196DF045XE36B, ML196DF070XE48B, ML196DF090XE48C, ML196DF110XE60C, ML193UH030XE36B, ML193UH045XE36B, ML193UH070XE36B, ML193UH090XE36C, ML193UH090XE48C, ML193UH110XE48C, ML193UH110XE60C; also ML180UHE and ML180DFE: ML180UH045E36A, ML180UH045XE36A, ML180UH070E36A, ML180UH070XE36A, ML180UH070E36B, ML180UH070XE36B, ML180UH090E48B, ML180UH090XE48B, ML180UH090E60C, ML180UH110E60C, ML180UH110XE60C, ML180UH135E60D, ML180DF045E36A, ML180DF070E36A, ML180DF070E36B, ML180DF090E48B, ML180DF110E60C; ML180UHV: ML180UH030V36A, ML180UH045V36A, ML180UH070V36A, ML180UH070V36B, ML180UH070V48B, ML180UH090V48B, ML180UH110V60C; Elite EL195UH (2011): EL195UH045P24B, EL195UH045P36B, EL195UH070P36B, EL195UH070P48B, EL195UH090P36C, EL195UH090P48C, EL195UH090P60C, EL195UH110P48C, EL195UH110P60C, EL195UH135P60D)
- Lennox Merit ML296UHVK / ML296DFVK / ML297UHVK (two-stage, variable-speed; upflow/horizontal ML296UH045XV36BK, ML296UH070XV36BK, ML296UH090XV48CK, ML296UH110XV60CK; downflow ML296DF045XV36BK, ML296DF070XV48BK, ML296DF090XV60CK; ML297UH045XV36BK, ML297UH070XV36BK, ML297UH090XV36CK, ML297UH090XV60CK, ML297UH110XV60CK, ML297UH135XV60DK)
- Lennox SL280UHV (80% two-stage variable speed)
- Goodman / Amana / Daikin GM9S96 / GC9S96 / GM9S92 (96% and 92% condensing, single-stage; also Daikin DM96SN, DM92SN, DC96SN: DM96SN0403AN, DM96SN0603BN, DM96SN0803BN, DM96SN0804CN, DM96SN0805CN, DM96SN1005CN, DM96SN1205DN, DM92SN0403AN, DM92SN0603BN, DM92SN0803BN, DM92SN0804CN, DM92SN0805CN, DM92SN1004CN, DM92SN1005CN, DM92SN1205DN, DC96SN0403BN, DC96SN0603BN, DC96SN0804CN, DC96SN1005CN, DC96SN1205DN)
- Payne PG96VTAB (two-stage condensing, variable-speed, non-communicating, 4-way multipoise)
- Payne PG9YAA / PG9YAB (95% single-stage condensing, direct or non-direct vent)
- Carrier 59TP6C (two-stage condensing with InteliSense, Performance series; also 926TC)
- Lennox G60DF / G60DFV (older two-stage SureLight boards 18M3401, 46M9901, 18M9901, 49M5901)
- Lennox G60UH / G60UHV (SureLight boards 100869 and 100870)
- Rheem / Ruud R801T Ultra Low NOx (14 ng/J) single-stage upflow/horizontal, constant-torque blower
- Rheem / Ruud 802V / 80MDV (80% two-stage communicating, ECM blower; model numbers (-)802V and (-)(-)80MDV)
- Trane / American Standard S8B1 / S8X1 / S8X2 (80% single-stage and two-stage)
- Trane / American Standard A801X060AM3S (80% single-stage, 2024 installation manual)
- Trane / American Standard A801X (80% single-stage: A801X040AM3SD, A801X040BM2SD, A801X060BM4SD, A801X080BM4SD, A801X080CM5SD, A801X100CM5SD, A801X120DM5SD)
- Goodman / Amana GMEC96 / GCEC96 (two-stage, multi-speed ECM: GMEC96, GCEC96, Amana AMEC96, ACEC96)
- Goodman / Amana / Daikin GMSS92 / GMSS96 / GCSS9 (single-stage, 92% and 96%: GMSS92, GMSS96, GCSS92, GCSS96, Amana AMSS92, AMSS96, ACSS92, ACSS96, Daikin VMSS9, VCSS9)
- Goodman / Amana / Daikin GMES92 / GMES96 / GCES96 (single-stage, 92% and 96%: GMES92, GMES96, GCES96, Amana AMES92, AMES96, ACES96, Daikin VMES96, VCES96)
- Goodman / Amana GM9C96 / GC9C96 (two-stage, nine-speed ECM: GM9C96, GC9C96, Amana AM9C96, AC9C96)
- Goodman / Amana GMH8 / GDH8 / GME95 (modified two-stage: 80% GMH8, GDH8, Amana AMH8, ADSH8; 95% GME95, Amana AMEH96)
- Goodman / Amana / Daikin GMS8 / GDS8 (80% single-stage: GMS8, GDS8, Amana AMS8, ADSS8, Daikin VMS8, VDS8)
- Goodman / Amana GMES96 U Ultra-Low NOx (single-stage 96%, U models: GMES96, Amana AMES96)
- Goodman / Amana GM9S96 U Ultra-Low NOx (single-stage 96%, U models: GM9S96, Amana AM9S96; Daikin DM96SN U: DM96SN0403BU, DM96SN0603BU, DM96SN0805CU)
- Goodman / Amana GMVS80 U Ultra-Low NOx (80% single-stage, variable-speed communicating: GMVS80, Amana AMVS80)
- Goodman / Amana GKS9 / AKSS92 (92% single-stage upflow: GKS9, Amana AKSS92)
- Goodman / Amana GMVM97 / GCVM97 ComfortBridge (97% modulating, BA revision and later: GMVM97, GCVM97, Amana AMVM97, ACVM97)
- Goodman / Amana GMVC96 / GCVC96 (96% two-stage variable-speed, *MVC96*BA and *CVC96*BA)
- Goodman / Amana GMVC96 / GCVC96 BB ComfortBridge (96%, BB revision: GMVC96, GCVC96, Amana AMVC96, ACVC96)
- Goodman / Amana / Daikin AMVC96 / DM96VC / DM80VC ComfortNet (two-character codes: AMVC96, ACVC96, GMVC96, GCVC96 before the BA revision; DM96VC0403BN, DM96VC0603BN, DM96VC0803BN, DM96VC0804CN, DM96VC1005CN, DM96VC1005DN, DM96VC1205DN, DC96VC0403BN, DC96VC0603BN, DC96VC0803BN, DC96VC0804CN, DC96VC1005CN, DC96VC1205DN, DM80VC0603B, DM80VC0604B, DM80VC0805C, DM80VC1005C, DD80VC0603B, DD80VC0805C, DD80VC1005C)
- Goodman / Amana GMVS96 / AMVS96 U-revision (96% variable-speed with analog pressure sensor, model numbers GMVS96*U and AMVS96*U; also Daikin DM96SC U: DM96SC0603BU, DM96SC0805CU)
- Goodman / Amana GMVM96 / GCVM96 / AMVM96 / ACVM96 (96% modulating, model numbers *MVM96 and *CVM96; also Daikin DM97MC/DC97MC: DM97MC0603BNA, DM97MC0803BNA, DM97MC0804CNA, DM97MC1005CNA, DM97MC1205DNA, DC97MC0603BNA, DC97MC0803BNA, DC97MC0804CNA, DC97MC1005CNA)
- Rheem / Ruud R801T / 80MSX (80% single-stage, constant-torque blower; model numbers (-)801T and (-)(-)80MSX)
- Rheem / Ruud 802P / 80MDP (80% two-stage, model numbers (-)802P and (-)(-)80MDP)
- Rheem / Ruud 802T / 80MDT (80% two-stage with constant-torque blower, model numbers (-)802T and (-)(-)80MDT)
- Rheem / Ruud 801S / 801P / 80MSS / 80MSP (80% single-stage, model numbers (-)801S, (-)801P, (-)(-)80MSS and (-)(-)80MSP)
- Rheem / Ruud W801T (Rheem Select 80% downflow single-stage)
- Rheem / Ruud R951T / R95T / R92T (90%+ single-stage condensing, constant-torque blower; model numbers (-)951T, (-)95T, (-)(-)95MSX, (-)92T, (-)(-)92MSX, e.g. R95TC0701317MSA, R92TC0701317MSA)
- Rheem / Ruud 801V Ultra Low NOx (80% communicating, constant CFM blower, upflow/horizontal)
- Carrier 58STA / 58STX (80% single-stage, 4-way multipoise; also 313AAV, 313JAV)
- Carrier 58CTA / 58CTX (80% two-stage, 4-way multipoise, Series 140/E)
- York TG9S (95.5% AFUE single-stage PSC, multi-position)
- York TM9T (96% AFUE two-stage PSC, multi-position)
- York TM9X (95.5% AFUE single-stage ECM, multi-position: TM9X040A10MP11, TM9X060B12MP11, TM9X080B12MP11, TM9X080C16MP11, TM9X100C16MP11, TM9X100C20MP11, TM9X120D20MP11)
- York TM9M (97% AFUE modulating PSC, multi-position)
- York YP9C / TP9C / CP9C / LP9C (up to 98% AFUE modulating ECM, multi-position)
- York TM9V (96% AFUE two-stage variable-speed ECM, multi-position)
- York UTEC Board (single- and two-stage furnaces from August 2009; SAP 539617, 542760, 542767, 542766; Source 1 S1-33102956000, S1-03102951001, S1-33102954000, S1-33102955000)
- York White-Rodgers Board (the generation before the 2009 UTEC boards; 265901, S1-33109167000 / 265902, S1-33109168000 / 265903, S1-33109169000 / 265904)
- York TI Board (older furnaces; 031-01972-000 TI 6DT-1, 031-01973-000 TI 6DT-2, 031-09117-000 TI 6MD-1, 031-09118-000 TI 6MI-1)
- Carrier 58TN0A / 58TN1A (80% two-stage, variable-speed, 4-way multipoise; also 880TA, 881TA)
- Carrier 58TN0B / 58TN1B (80% two-stage, variable-speed, 4-way multipoise)
- Carrier 58TP0A / 58TP1A (80% two-stage, variable-speed ECM, 4-way multipoise; also PG80VTLA)
- Carrier 58TP0B / 58TP1B InteliSense (80% two-stage, variable 25-speed ECM, 4-way multipoise)
- Carrier 59SC5A (single-stage condensing, 4-way multipoise; also 912SB, 912SC, 922SA, 925SA, PG92SAS, PG92SCS, PG95SAS)
- Bryant 925TA (two-stage condensing, 4-way multipoise; also PG95XAT)
- Bryant 926SA (single-stage condensing, multi-speed ECM, multipoise)
- Bryant 926SB (single-stage condensing, 25-speed ECM, InteliSense)
- Carrier 59SC5B / 59SC2D (single-stage 35-in. condensing, 4-way multipoise; also 912SD, 915SB)
- Carrier 59MN7A / 59MN7B (modulating condensing, 4-way multipoise; also 987MA, 987MB)
- Carrier 59MN7C modulating condensing (59MN7C060C17, 59MN7C060C21, 59MN7C080C17, 59MN7C080C21, 59MN7C100C21, 59MN7C120C24; also 987MC)
- Carrier 59TP6B / 59TP6A / 59TN6A two-stage (condensing, two-digit codes; also 926TA, 926TB, 986TB, PG96VAT, PG96VTAA)
- Carrier 59TN6B two-stage condensing (variable-speed: 59TN6B060C17, 59TN6B080C17, 59TN6B080C21, 59TN6B100C21, 59TN6B120C24; also 986TC)
- Carrier 59TN6C two-stage condensing (variable-speed, 35 in. tall: 59TN6C040C14, 59TN6C060C17, 59TN6C080C17, 59TN6C080C21, 59TN6C100C21, 59TN6C120C24)
- Carrier 59TN7A two-stage condensing (variable-speed, 35 in. tall: 59TN7A060C17, 59TN7A080C17, 59TN7A080C21, 59TN7A100C21, 59TN7A120C24)
- Carrier 59SU5A (single-stage Ultra Low NOx condensing, upflow/horizontal, 35 in. tall)
- Carrier 59SU5B single-stage Ultra Low NOx (condensing, 35 in. tall: 59SU5B040M17, 59SU5B060M17, 59SU5B080M21, 59SU5B100M21; also PG95MSUA)
- Carrier 59TP7A two-stage InteliSense (condensing, variable-speed, non-communicating: 59TP7A060V17, 59TP7A080V17, 59TP7A080V21, 59TP7A100V21, 59TP7A120V24)
- Carrier 59SC2E / 59SC6A (single-stage 35-in. condensing, 4-way multipoise; also 912SE, PG96MSAA)
- Carrier 58CU0A (80% communicating, Ultra Low NOx, 4-way multipoise)
- Carrier 58SU0A (80% single-stage, ECM blower, Ultra Low NOx, 4-way multipoise; also 830SA)
- Carrier 58SU0B (80% single-stage, ECM blower, Ultra Low NOx, 3-digit display)
- Carrier 58SB0B / 58SB1B / 58SC0B / 58SC1B (80% single-stage, multi-speed ECM, 4-way multipoise; also PG80MSA, PG80MSLA)
- Bryant 820SA / 821SA (80% single-stage, 4-way multipoise)
- Carrier 58SB0A / 58SB1A / 58SC0A / 58SC1A (single-stage, non-condensing; 58SC is the multi-speed ECM version; also 800SA, 801SA, PG80ESAA, PG80ESLA)