Goodman / Amana / Daikin AMVC96 / DM96VC / DM80VC ComfortNet Furnace Codes

Applies to: Goodman / Amana / Daikin AMVC96 / DM96VC / DM80VC ComfortNet (two-character codes: AMVC96, ACVC96, GMVC96, GCVC96 before the BA revision; DM96VC0403BN, DM96VC0603BN, DM96VC0803BN, DM96VC0804CN, DM96VC1005CN, DM96VC1005DN, DM96VC1205DN, DC96VC0403BN, DC96VC0603BN, DC96VC0803BN, DC96VC0804CN, DC96VC1005CN, DC96VC1205DN, DM80VC0603B, DM80VC0604B, DM80VC0805C, DM80VC1005C, DD80VC0603B, DD80VC0805C, DD80VC1005C). Two-character LED display on the integrated control module (ComfortNet).

Goodman/Amana *MVC96/*CVC96 service instructions RS6612010 (August 2014) and Daikin DM80VC/DD80VC RSD6621001r6 (July 2016, controls PCBKF103/104/105) print the same troubleshooting chart; the older editions say to sand the flame sensor with emery cloth where the DM96VC edition says clean it. The later GMVC96 BA revision uses three-character codes (EE0 and so on); see that chart.

CodeMeaningWhat to check
Blank (EE on thermostat)Internal control fault, or no 115 V or 24 V power to the integrated control.Manual disconnect off, door switch open or 24 V wire loose; blown fuse or tripped breaker; or an internal control fault. Confirm 115 V and 24 V, check the control's 3A fuse, check for shorts in the 115 V and 24 V circuits, and replace a bad control. How to fix →
OnNormal operation.
E0Lockout after excessive ignition retries (3 total).Failure to establish flame (no gas, front cover pressure switch stuck open, bad or misaligned igniter, wrong orifices, coated/oxidized or misconnected flame sensor) or loss of flame after it was established (interrupted gas, lazy flames from wrong gas pressure or a flue or combustion air restriction, front cover pressure switch opening, poor inducer performance). Locate and fix the gas interruption, check the front cover pressure switch, replace or realign the igniter, clean the flame sensor, check the flue piping and the inducer. How to fix →
E1Low stage pressure switch closed at the start of the heating cycle (PS1 CLOSED).Sticking switch contacts or a short in the switch wiring. Replace the low stage pressure switch or repair the wiring. How to fix →
E2Low stage pressure switch not closed (PS1 OPEN). Inducer runs continuously with no further furnace operation.Switch hose blocked, pinched or misconnected; blocked flue or inlet air pipe, blocked drain or weak inducer; wrong switch set point or bad contacts; loose wiring. Inspect and fix each; check inducer performance. How to fix →
E3Primary limit, auxiliary limit or rollout limit circuit open (HIGH LIMIT OPEN). Circulator blower runs continuously.Too little airflow over the heat exchanger (dirty filters, restrictive ducts, wrong blower speed, failed blower motor), flame rollout, misaligned burners, blocked flue or inlet pipe or failed inducer, loose wiring. Check filters and ducts, blower speed and performance against the rating plate's rise range, burner alignment, flue and inlet piping, inducer and wiring. How to fix →
E4Flame sensed with no call for heat (IMPROPER FLAME). Inducer and circulator run continuously.Short to ground in the flame sense circuit, lingering burner flame or a slow-closing gas valve. Fix the short, check for lingering flame and verify gas valve operation. How to fix →
E5Open fuse. No furnace operation.Short in the low voltage wiring. Find and fix it, then replace the fuse with a 3-amp automotive type. A ComfortNet thermostat shows Battery Power. How to fix →
E6Low flame sense signal (WEAK FLAME). Furnace still runs.Coated or oxidized sensor, sensor mispositioned in the flame, or a lazy flame from wrong gas pressure or combustion air. Clean the sensor, check its alignment and the inlet air piping, and compare gas pressure to the rating plate. How to fix →
E7Igniter circuit problem (IGNITER FAULT).Improperly connected or shorted igniter, poor unit ground, or an igniter relay fault on the control. Check igniter wiring, replace a shorted igniter, check unit ground, check the control's igniter output. How to fix →
E8High stage pressure switch closed at the start of the heating cycle (PS2 CLOSED). Furnace runs on low stage only.Sticking switch contacts or a short in the switch wiring. Replace the high stage pressure switch or repair the wiring. How to fix →
E9High stage pressure switch not closed (PS2 OPEN). Furnace runs on low stage only.Same causes and checks as E2, for the high stage switch. How to fix →
EA115 V polarity reversed (REVERSED PLTY).Check polarity against the wiring diagram, the unit ground and the wiring.
EFAux switch open (Aux Alarm Fault).High water level in the evaporator coil. Check the overflow pan and service it. How to fix →
d0Data not yet on network (NO NET DATA): the furnace has no shared data.Populate the shared data set with the memory card for this model. Insert the card before turning power on; remove it after data loads and power is off. The code clears once data is loaded.
d4Invalid memory card data (INVALID MC DATA).The control rejected the shared data set. Confirm it's right for the model and reload with the correct memory card if needed.
b0Circulator blower motor not running when it should be (MOTOR NOT RUN).Loose motor power leads or disconnected power, open or loose inductor (3/4 and 1 hp models), or a failed motor. Fix wiring, check the inductor for continuity, check or replace the motor.
b1Control lost communication with the circulator blower motor (MOTOR COMM).Loose motor control leads, failed motor or failed control. Fix the wiring; check and replace the motor or control as needed. How to fix →
b2Motor horsepower in the shared data set doesn't match the motor (MOTOR MISMATCH).Wrong motor in the furnace, or the wrong shared data set. Verify the motor horsepower for this model and the shared data; reload with the correct memory card if needed.
b3Circulator blower motor running in a power, temperature or speed limit (MOTOR LIMITS). Reduced performance.Blocked filters, restrictive or undersized ducts, or high ambient temperatures. Clean filters, open all registers, check duct sizing. How to fix →
b4Motor senses loss of rotor control or high current (MOTOR TRIPS).Abnormal motor loading, a sudden change in speed or torque, or sudden blockage of the air inlet or outlet. Check filters, grilles, registers, ducts and the furnace inlet/outlet. How to fix →
b5Circulator blower motor failed to start 10 consecutive times (MOTOR LCKD ROTOR).Obstruction in the blower housing, seized bearings or a failed motor. Clear obstructions, check shaft rotation, replace the motor or wheel if needed.
b6Motor shut down for over or under voltage, or over temperature on its power module (MOTOR VOLTS).High or low AC line voltage or high ambient temperature. Verify line voltage is within the rating plate range and installation requirements are met.
b7Motor doesn't have enough information to run, or failed to start 40 consecutive times (MOTOR PARAMS).An integrated control error or a locked rotor. Verify the control is populated with the correct shared data, and check for a locked rotor (see b5).
b9Airflow lower than demanded (LOW ID AIRFLOW). Reduced performance, or runs low stage when high is expected.Blocked filters, restrictive or undersized ducts. Clean filters, open registers, resize or replace ducts if needed. How to fix →

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Daikin DC96VC/DM96VC Service Instructions RSD6612010r5 (2017), troubleshooting chart pp. 45-49 and status code list p. 50; same chart in Goodman RS6612010 (2014) and Daikin RSD6621001r6 (2016). The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.