Home / Charts / Rheem / Ruud furnace codes

Rheem / Ruud 802V / 80MDV Furnace Codes

Applies to: Rheem / Ruud 802V / 80MDV (80% two-stage communicating, ECM blower; model numbers (-)802V and (-)(-)80MDV). Dual seven-segment display on the integrated furnace control.

The (-) in the model number stands for the brand prefix (Rheem or Ruud). Other Rheem two-stage furnaces use different code lists; check the installation instructions for your model.

CodeMeaningWhat to check
d1No model data (critical; furnace won't run in any mode).Memory card missing or disconnected from connector P6 on the control. Cycle power after reinstalling it.
d4No valid model data on the memory card (furnace still runs using model data in the control).Replace with the original or correct memory card for this furnace.
d6Horsepower conflict on the memory card.Wrong replacement blower motor, or the wrong memory card or control was installed.
10One-hour lockout. Alternates with the code that caused it. How to fix →
11Failed ignition. After four in a row the control enters one-hour lockout.Flame rod, gas valve off, igniter, control, or flame not carrying from the first burner (check manifold pressure). How to fix →
12Low flame sense (furnace keeps running). How to fix →
13Flame lost after it was established.Flame sensor, sensor mounting or ground, unstable flame, burner compartment seals. How to fix →
14Flame present with the gas valve off.24 V miswired to the gas valve, valve stuck open, or a faulty control.
22Main limit open.Airflow first: blower, filter, ductwork and static pressure, then firing rate. Open more than 150 seconds brings code 61. How to fix →
23HALC open.No continuity between pins 3 and 5 of connector P1; repair the jumper.
26Line and neutral reversed, or poor ground.Check polarity at the furnace and at the disconnect or breaker, and the cabinet ground.
30Open fuse.24 V short to common or ground. Fix the short, then replace the fuse. How to fix →
33Over-temperature (rollout) switch open, manual reset (MRLC).Venting, pressure switch bypassed, wiring, unstable flame, burner and door seals, damaged heat exchanger. How to fix →
44Low pressure switch closed with the inducer off.Welded or bypassed switch, wiring, or abnormal vent draft. How to fix →
45Low pressure switch open with the inducer on high speed.Blocked or overlong vent, inducer, control relay, wiring, pressure hoses, wind, switch. How to fix →
46Low pressure switch open with the inducer on low speed.Same as 45, plus a missing high altitude kit. How to fix →
55High pressure switch closed with the inducer off.Welded or bypassed switch, wiring, or abnormal vent draft. How to fix →
57High pressure switch open with the inducer on high speed. The furnace may continue on low fire.Vent, inducer, control relay, high altitude kit, wiring, hoses, wind, switch. How to fix →
58Water circuit open (gas heat stops; cooling still works).No continuity between pins 1 and 2 of connector P4; repair the jumper or connector.
60Blower fault, blower can still run (non-critical).Blower at its speed or torque limit: static pressure too high. How to fix →
61Blower fault, motor can't run (critical).Motor thermal trip, power factor correction choke, memory card, wiring, loose blower wheel, failed motor.
66Blower cutback (operating indicator, not a true fault).Static pressure too high for the airflow the blower is asked for. How to fix →
68No blower communications.Motor wiring and connections, line voltage to the motor and choke, memory card, failed motor.
93Internal control fault.Voltage on the gas valve circuit when there shouldn't be (miswiring), or a failed control.
99Fault history reset (notification only).

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Rheem Installation Instructions, (-)802V / (-)(-)80MDV two-stage communicating gas furnaces, 92-24161-148-04, Tables 12 and 13 (pp. 64-73). The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.