Carrier 58STA / 58STX Furnace Codes

Applies to: Carrier 58STA / 58STX (80% single-stage, 4-way multipoise). LED on the furnace control, two-digit status codes.

Similar two-digit status codes are used on many Carrier, Bryant and Payne furnaces, but titles and causes vary by model. Check the service label on the blower door.

CodeMeaningWhat to check
11No previous code.
12Blower on after power up (normal).Blower runs for 90 seconds if the unit is powered up during a call for heat, or when R-W opens during the blower on-delay.
13Limit circuit lockout.The limit, draft safeguard, flame rollout or blocked vent switch (if used) stayed open longer than 3 minutes. Auto-resets after three hours. See code 33. How to fix →
14Ignition lockout.Auto-resets after three hours. See code 34. How to fix →
21Gas heating lockout. The control will not auto reset.Mis-wired gas valve, or a defective control (valve relay).
22Abnormal flame-proving signal.Flame is proved while the gas valve is de-energized; the inducer runs until it clears. Leaky or stuck-open gas valve. How to fix →
23Pressure switch did not open.Obstructed pressure tubing, or pressure switch stuck closed. How to fix →
24Secondary voltage fuse is open.Short circuit in the 24 VAC wiring. How to fix →
31Pressure switch did not close or reopened.Vent sizing or restriction, low inducer voltage, combustion air, low inlet gas pressure (if LGPS used), inducer motor, pressure switch, pressure tubing, wind. Open more than five minutes: inducer shuts off for 15 minutes before retrying. How to fix →
33Limit circuit fault.Limit, draft safeguard, flame rollout or blocked vent switch is open. Dirty filter or restricted ducts, loose blower wheel, blower motor or capacitor, vent sizing, combustion air. Rollout and blocked vent switches are manual reset. How to fix →
34Ignition proving failure.The control tries three more times before code 14. Clean the flame sensor (0.5 microamps DC minimum), gas valve and manual shut-off, igniter, ground continuity, inlet gas pressure, flame carryover. How to fix →
45Control circuitry lockout.Gas valve relay stuck open, flame sense circuit failure, or a software check error. Auto-resets after one hour. Reset power; replace the control if the code repeats.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Carrier 58STA/58STX Installation, Start-up, Operating and Service and Maintenance Instructions, Form 58ST-24SI, Fig. 45 Service Label (327596-101 Rev. B), p. 43. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.