Lennox Merit ML196UHEK / Elite EL196UHEK Furnace Codes

Applies to: Lennox Merit ML196UHEK / Elite EL196UHEK (80% single-stage, constant torque: ML196UH030XE36BK, ML196UH045XE36BK, ML196UH070XE36BK, ML196UH070XE48BK, ML196UH090XE36CK, ML196UH090XE48CK, ML196UH090XE60CK, ML196UH110XE60CK, ML196UH135XE60DK, EL196UH030XE36BK, EL196UH045XE36BK, EL196UH070XE36BK, EL196UH090XE48CK, EL196UH110XE60CK; same control and codes: Elite EL180UHNEK, Merit ML180UHEK, ML193DFEK, Elite EL195UHNEK: EL180UH040NE36AK, EL180UH060NE36AK, EL180UH080NE48BK, EL180UH100NE60CK, ML180UH045E36AK, ML180UH045XE36AK, ML180UH070E36AK, ML180UH070E36BK, ML180UH070XE36BK, ML180UH090E48BK, ML180UH090XE48BK, ML180UH090E60CK, ML180UH110E60CK, ML180UH110XE60CK, ML180UH135E60DK, ML193DF045XE36BK, ML193DF070XE36BK, ML193DF090XE48CK, EL195UH040NE36BK, EL195UH060NE36BK, EL195UH080NE48CK, EL195UH100NE60CK; variable-speed Merit ML180UHVK: ML180UH030V36AK, ML180UH045V36AK, ML180UH070V36AK, ML180UH070V36BK, ML180UH070V48BK, ML180UH090V48BK, ML180UH110V60CK, ML180UH135V60DK). Seven-segment diagnostic LED and push button on the integrated control (107792-01, single-stage, constant torque, non-communicating).

The Elite EL196UHEK instructions (508573-01) print the same diagnostic code list as the Merit ML196UHEK (508569-01). This is the A2L-ready K version with control 107792-01. Lennox's service literature for the ML196UHEK (100165), EL180UHNEK (100157), ML180UHEK (100161), ML193DFEK (100162) and EL195UHNEK (100158) prints the same table for control 107792. The variable-speed ML180UHVK (508547-01, pp. 47-49) prints the same table plus E292.

CodeMeaningWhat to check
E000No error in memory.No active fault, or all faults have been cleared.
E106Twin communication fault.Power removed from one twinned furnace but not the other, or the 24 VAC supplies to the twins are not in phase.
E110Low line voltage (below the nameplate rating).Check and correct line voltage. Clears 5 seconds after recovery.
E111Line voltage polarity reversed.Reverse the line power wiring. Resumes 5 seconds after recovery.
E112Ground not detected; system shuts down.Provide a proper earth ground. Resumes 5 seconds after recovery.
E113High line voltage (above the nameplate rating).Provide voltage within range. Resumes 5 seconds after recovery.
E114Line voltage frequency out of range.No 60 Hz power: check voltage and line frequency. Resumes 5 seconds after recovery.
E115Low 24 V (the control restarts if it recovers).24 V range is 18 to 30 V. Check and correct; look for power-robbing equipment on the system; a larger VA transformer may be needed. Clears after recovery.
E117Poor ground detected (warning only).Check for proper earth ground. Clears 30 seconds after recovery.
E125Control failed self-check or hardware (flame sense circuit faults, pin shorts, etc.); control not communicating.Cycle power. Replace the control if the problem persists and prevents service. Critical alert; clears 300 seconds after recovery.
E150Refrigerant leak detected.May mean a leak at or in the indoor coil that must be repaired, and the charge verified. Can't be cleared while the sensor still reports a leak.
E151Refrigerant leak detector sensor #1 fault.The sensor reports a problem that stops it working; it may need replacing. Clears when it no longer reports a fault.
E152Refrigerant leak detector sensor #2 fault.The sensor reports a problem that stops it working; it may need replacing. Clears when it no longer reports a fault.
E154Refrigerant leak detector sensor #1 communication lost, or invalid sensor DIP switch setting (disable/enable).Check the wiring harness and connector between the sensor and the furnace control for damage or poor connection, and the sensor for damage or an obstructed harness plug. Clears when communication returns, but the blower latches on for at least 5 minutes. Retest with the Low GWP test button on the control. May also mean the Low GWP DIP switches are set wrong.
E155Refrigerant leak detector sensor #2 communication lost.Check the wiring harness and connector between the sensor and the furnace control for damage or poor connection, and the sensor for damage or an obstructed harness plug. Clears when communication returns, but the blower latches on for at least 5 minutes. Retest with the Low GWP test button on the control.
E160Refrigerant leak detector sensor #1 is the wrong type.Replace it with a Lennox-approved sensor. Clears when a suitable sensor is detected; the blower latches on for at least 5 minutes.
E161Refrigerant leak detector sensor #2 is the wrong type.Replace it with a Lennox-approved sensor. Clears when a suitable sensor is detected; the blower latches on for at least 5 minutes.
E163Furnace control board failure.May need a new control board. Clears when the control operates normally.
E164Low GWP test.Test mode started with the Low GWP test button; normal operation resumes and the code clears after 1 minute.
E200Hard lockout: rollout circuit open or previously open.Correct the cause of the rollout trip, or replace the rollout switch. Test operation. Clears after recovery. How to fix →
E204Gas valve miswired.Check gas valve operation and wiring. Clears when repaired.
E223Pressure switch failed open.Check pressure (inches w.c.) of the switch closing on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. How to fix →
E224Pressure switch failed closed.Check pressure (inches w.c.) of the switch closing on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. How to fix →
E227Pressure switch open during trial for ignition or run mode.Check pressure (inches w.c.) of the switch closing on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. How to fix →
E240Low flame current, run mode.Check flame current with the control diagnostics; clean or replace the sensor; measure neutral to ground for a good unit ground. Clears after the heat call completes. How to fix →
E241Flame sensed out of sequence; flame still present.Shut off the gas. Check the gas valve for a leak and replace it if needed.
E250Limit switch circuit open.Proper firing rate, no blockage in the heater, proper airflow. If the limit doesn't close within 3 minutes, the unit goes into a 1-hour soft lockout. How to fix →
E270Soft lockout: too many retries, no flame current sensed.Proper gas flow, igniter lighting the burner, flame sensor current. How to fix →
E271Soft lockout: too many retries; last retry failed when the pressure switch opened.Check pressure (inches w.c.) of the switch closing on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. How to fix →
E272Soft lockout: too many recycles; last recycle due to the pressure switch opening.Check whether the pressure switch is stuck closed on the heat call, measure operating pressure, inspect the vent and inducer. How to fix →
E273Soft lockout: too many recycles; last recycle due to flame failure.Check flame current, clean or replace the sensor, measure neutral to ground for a good unit ground. How to fix →
E274Soft lockout: too many recycles; last recycle failed on the limit circuit, or the limit stayed open over 3 minutes.1-hour soft lockout. Check firing rate and airflow; check for blockage. How to fix →
E275Soft lockout: flame sensed out of sequence; flame signal now gone.Shut off the gas and check the gas valve for a leak. 1-hour soft lockout; clears when flame is proven stable.
E290Igniter circuit fault: failed igniter or triggering circuitry.Measure hot surface igniter resistance; replace if open or out of spec. 1-hour soft lockout. How to fix →
E292Indoor blower motor can't start (obstructed wheel, seized bearings). Listed for the variable-speed ML180UHVK.Replace the motor or wheel if the assembly doesn't run or meet performance. 1-hour soft lockout; clears after the blower starts.
E390Low GWP relay stuck.A problem with the Low GWP relay on the control; may need a new control board. Clears when the relay works normally.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Lennox ML196UHEK Merit Series Gas Furnace Installation Instructions 508569-01 (2026), Integrated Diagnostic Codes pp. 44-46, Table 21 flame signal p. 58; same list in EL196UHEK Installation Instructions 508573-01. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.