Carrier 58TN0B / 58TN1B Furnace Codes

Applies to: Carrier 58TN0B / 58TN1B (80% two-stage, variable-speed, 4-way multipoise). Three-digit display on the furnace control (major.minor code); the LED seen through the door sight glass flashes the major code.

The older 58TN0A / 58TN1A use two-digit codes and have their own chart.

CodeMeaningWhat to check
10.1L1 polarity fault (rapid flash LED).Correct the 115 V wiring polarity.
10.2Dissipation system active, operate blower.Listed on the service label and guide with no further checks.
otAFirmware install in process.Wait for the install to finish.
btLFailed to load; retry the firmware install.Retry the firmware install.
12.1W on at power up (normal).Blower runs 90 seconds if power comes on during a call for heat, or when R-W opens during the blower on-delay.
13.1Limit lockout (3 hr): limit, draft safeguard, flame rollout or blocked vent switch open longer than 3 minutes.Auto-resets after 3 hours. See 33.1. How to fix →
14.1Ignition lockout (3 hr) after 4 consecutive ignition tries.Auto-resets after 3 hours. See code 34. How to fix →
14.2Flame lost 3 times after 70 seconds of heating.See code 34. How to fix →
14.3Lockout: 7 loss-of-flame events during a heat request.See code 34. How to fix →
15.1Lockout (3 hr): no blower RPM detected.Loose blower wire connections, failed blower motor.
15.2Lockout: failed to reach 500 RPM after retry.Loose blower wire connections, failed blower motor.
17.1BTM communication loss.Listed on the service label; no guide entry.
21.124 VAC sensed on the gas valve when it shouldn't be; power reset only.Turn off power and wait 5 minutes to retry. Stuck-closed gas valve relay on the control, or a miswire or short at the gas valve wire.
22.1False flame: flame proved while the gas valve is off; inducer runs until it clears.Stuck-open or leaky gas valve.
23.4LPS (low pressure switch) stuck closed.Obstructed pressure tube, or the switch stuck closed. How to fix →
23.5HPS (high pressure switch) stuck closed.Obstructed pressure tube, or the switch stuck closed. How to fix →
24.1Fuse fault.Short in the 24 V wiring, including thermostat leads; disconnect the thermostat leads to isolate it. How to fix →
25.1No program; no heating.Reprogram the control with the correct program number from the rating plate (service app or super plug); replace the control if the issue remains.
25.2Corrupted program file; no heating.Reprogram the control (service app or super plug).
25.4Main program invalid; running on the backup program.Reprogram the control. It still operates normally.
25.5Installer settings corrupted.Reselect the installer settings or reprogram; runs on default settings meanwhile.
25.6Wrong program for the control; no heating.Reprogram the control with the correct program number from the rating plate (service app or super plug); replace the control if the issue remains.
27.1Super plug program missing, not recognized or corrupted.Remove the super plug and retry; try a different super plug; if it still fails, replace the control.
27.2Super plug program missing, not recognized or corrupted.Remove the super plug and retry; try a different super plug; if it still fails, replace the control.
27.3Super plug program missing, not recognized or corrupted.Remove the super plug and retry; try a different super plug; if it still fails, replace the control.
31.6Open high pressure switch: HPS failed to close in 75 seconds when high heat is required, or reopened.Excessive wind, restricted vent or wrong vent sizing, defective inducer, low inlet gas pressure (if LGPS used), inadequate combustion air, disconnected or obstructed pressure tubing. If it opens during the blower on-delay, the blower runs for the selected off-delay. How to fix →
31.7High heat only for the remainder of the current cycle.Same checks as 31.6. How to fix →
32.2Open low pressure switch (LPS).Open longer than 5 minutes: the inducer shuts off 15 minutes before retrying. If it opens within 5 minutes after the gas valve opens, the next cycle is forced to high heat. See 31.6 and 31.7. How to fix →
33.1Main limit circuit open (limit or flame rollout).Blower runs 4 minutes or until the switch remakes; over 3 minutes it becomes 13.1. Rollout switch and BVSS need a manual reset. Dirty filter or restricted ducts, loose blower wheel, defective switch or connections, defective blower motor, improper gas input. How to fix →
34.1Ignition fault: four consecutive ignition trials.Gas valve turned off, manual shut-off valve, green/yellow wire connected to furnace sheet metal, flame sensor not grounded. In component test, the igniter should glow orange/white by the end of the 15-second warm-up. How to fix →
34.5Low heat flame lost before the blower on-delay.Gas valve turned off, manual shut-off valve, green/yellow wire connected to furnace sheet metal, flame sensor not grounded. In component test, the igniter should glow orange/white by the end of the 15-second warm-up. How to fix →
34.6Low heat flame lost after the blower on-delay.Gas valve turned off, manual shut-off valve, green/yellow wire connected to furnace sheet metal, flame sensor not grounded. In component test, the igniter should glow orange/white by the end of the 15-second warm-up. How to fix →
34.7High heat flame lost before the blower on-delay.Gas valve turned off, manual shut-off valve, green/yellow wire connected to furnace sheet metal, flame sensor not grounded. In component test, the igniter should glow orange/white by the end of the 15-second warm-up. How to fix →
34.8High heat flame lost after the blower on-delay.Gas valve turned off, manual shut-off valve, green/yellow wire connected to furnace sheet metal, flame sensor not grounded. In component test, the igniter should glow orange/white by the end of the 15-second warm-up. How to fix →
41.1No blower RPM at start-up.Loose blower wire connections, failed blower motor.
41.2No RPM while the blower motor is running.Loose blower wire connections, failed blower motor.
41.3Failed to reach 500 RPM at start-up.Loose blower wire connections, failed blower motor.
43.1HPS closed before LPS.No checks listed in the guide; look at both pressure switches and their tubing. How to fix →
45.1Internal control error (1 hr): flame circuit fault, memory mismatch or sequence error.Cycle power; if 45 repeats, replace the control.
45.2Gas valve relay not closing.Cycle power; if 45 repeats, replace the control.
45.3Micro EEPROM error (1 hr).Cycle power; if 45 repeats, replace the control.
45.4Micro loss of communication.Cycle power; if 45 repeats, replace the control.
51.1OAT open: outdoor air temperature sensor connection open.Loose connection at the control board screw terminals, cut or shorted OAT wires, damaged OAT sensor.
51.2OAT short: outdoor air temperature sensor wires shorted.Loose connection at the control board screw terminals, cut or shorted OAT wires, damaged OAT sensor.
52.1SAT open: supply air temperature sensor connection open.Loose connection at the control board screw terminals, cut or shorted SAT wires, damaged SAT sensor.
52.2SAT short: supply air temperature sensor wires shorted.Loose connection at the control board screw terminals, cut or shorted SAT wires, damaged SAT sensor.
53.1RAT open: return air temperature sensor connection open.RAT firmly plugged into the control board; damaged RAT sensor.
53.2RAT short: return air temperature sensor shorted.RAT firmly plugged into the control board; damaged RAT sensor.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Carrier 58TN0B/58TN1B Installation, Start-Up, Operating and Service and Maintenance Instructions 58TN0B-03SI, Fig. 46 Service Label p. 33, Fig. 53 Troubleshooting Guide pp. 50-51. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.