Goodman / Amana GMVM97 / GCVM97 ComfortBridge Furnace Codes

Applies to: Goodman / Amana GMVM97 / GCVM97 ComfortBridge (97% modulating, BA revision and later: GMVM97, GCVM97, Amana AMVM97, ACVM97). Seven-segment display on the ComfortBridge integrated control.

This is the 34.5-inch ComfortBridge GMVM97 (BA revision and above). The older GMVM96 has its own chart.

CodeMeaningWhat to check
IdLIdle, normal operation.None.
NoneNo display: no 115 V or 24 V to the control, blown fuse or tripped breaker, or a dead control.Check 115 V to the furnace and control (disconnect, door switch, a supply shared with other devices) and look for shorts in the 115 V circuit; replace the control if it's dead. How to fix →
EEEInternal control fault.Replace the control.
EE0Lockout due to excessive retries or recycles (3 ignition retries).Gas interruption, front cover pressure switch (hose, wiring, contacts), igniter (replace or realign), flame signal (sand or clean the sensor with steel wool), flue piping, inducer performance. How to fix →
EE1Low stage pressure switch stuck closed at the start of heating.Switch contacts sticking or a short in the switch wiring. How to fix →
EE2Low stage pressure switch open; inducer runs continuously.Switch hose, flue and inlet piping, drain system, weak inducer, setpoint or contacts, wiring. How to fix →
EE3Open high limit switch; circulator runs continuously.Filters and ductwork, blower speed and performance, wiring in the high limit circuit. See the specification sheet for the allowable rise range and blower speed. How to fix →
EE4Flame detected when no flame should be present.Short to ground at the flame sensor or its wiring, a lingering flame, or a slow-closing gas valve.
EE5Open fuse.Find and correct the short in the low voltage wiring; replace the fuse with a 3 A automotive type. (The symptoms table repeats the EE4 description here; the alarm table names it open fuse.) How to fix →
EE6Low flame signal (furnace still runs).Clean the flame sensor (steel wool), check alignment, inlet air piping and gas pressure against the rating plate. How to fix →
EE7Igniter fault or improper grounding.Igniter wiring from the control, shorted igniter, unit ground, the control's igniter relay (check igniter output). How to fix →
EE8High stage pressure switch stuck closed at the start of the heating cycle; runs on low stage only.Switch contacts sticking or a short in the wiring. How to fix →
EE9High stage pressure switch open; runs on low stage only.Switch hose, flue and inlet piping, drain system, inducer performance, setpoint or contacts, wiring. How to fix →
EEAReversed line polarity, or poor unit ground (shown as EEr in the symptoms table).Correct the 115 V polarity per the wiring diagram and verify the ground.
EEbGas valve not energized when it should be (external gas valve error).Miswired or open gas valve circuit, or the control's gas valve relay stuck open. Check the wiring; replace the control.
EECGas valve energized when it should not be (internal gas valve error).Miswired or shorted gas valve wiring, or the control's gas valve relay. Check the wiring; replace the control.
EEdAuxiliary limit switch (blower compartment) open.115 V shut off during a heat cycle, or not enough air (filters, ductwork, blower speed or failed blower), or wiring. How to fix →
EEFCondensate switch open.High water in the evaporator coil: check the evaporator drain pan, trap and piping.
E10Grounding fault.Poor neutral: verify the neutral connection to the furnace and continuity to ground.
E11Rollout switch open.Gas pressure too high, misaligned burners, or a restricted heat exchanger or vent. How to fix →
E12Redundant relay open.Alarm table only.
E13Redundant relay stuck closed.Alarm table only.
Ed0Data not yet on network.Populate the shared data set using the CoolCloudHVAC app; the code clears once it's downloaded.
Ed1Invalid data on network.Make sure the shared data is right for the model and re-populate it with the CoolCloudHVAC app.
Ed4Invalid external shared data.Alarm table only.
Ed5Invalid downloaded firmware.Alarm table only.
Ed6Unrecognized data ID.Alarm table only.
Eb0Blower motor not running when it should be.Loose motor power or control leads, an open circuit or loose connection at the inductor (3/4 and 1 HP models), or a failed blower motor.
Eb1Blower communication alarm: control lost communication with the blower.Loose motor control leads, failed blower motor or failed control.
Eb2Blower motor HP / ID mismatch with the shared data.Make sure the motor horsepower matches the furnace model and the shared data is correct; re-populate with the CoolCloudHVAC app if needed.
Eb3Blower motor operating in a power, temperature or speed limit (reduced airflow).Blocked filters, restrictive or undersized ductwork, high ambient temperature; make sure all registers are open. How to fix →
Eb4Blower motor current trip or lost rotor control.Abnormal motor loading, sudden change in speed or torque, or sudden blockage of the furnace air inlet or outlet. Check filters, grilles, registers and ducts. How to fix →
Eb5Blower motor locked rotor (failed to start 10 times in a row).Obstruction in the blower housing, seized motor bearings or a failed motor; repair or replace the wheel or motor.
Eb6Blower motor over/under voltage trip or over temperature trip.Line voltage to the furnace within the rating plate range; high ambient temperature.
Eb7Incomplete parameters sent to the motor (or it failed to start 40 times in a row).Make sure the control is populated with the correct shared data; check for a locked rotor.
Eb9Inadequate airflow: lower than demanded.Blocked filters, restrictive or undersized ductwork; make sure all registers are open. How to fix →
EC1Network communication alarm.Alarm table only.
EC2E-Module network communication alarm.Alarm table only.
EC3Bluetooth module network communication alarm.Alarm table only.
ECFGas valve stepper motor communication error.Goodman's symptoms table lists no power to the gas valve: verify voltage to the gas valve.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Goodman/Amana 34.5" Chassis ACVM97*BA/AMVM97*BA/GCVM97*BA/GMVM97*BA Modulating Gas Furnaces Service and Troubleshooting manual RS6612015 Rev. 9 (2026), Alarm Code Definition Table p. 43, Symptoms of Abnormal Operation pp. 47-51. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.