Home / Charts / York furnace codes

York TI Board Furnace Codes

Applies to: York TI Board (older furnaces; 031-01972-000 TI 6DT-1, 031-01973-000 TI 6DT-2, 031-09117-000 TI 6MD-1, 031-09118-000 TI 6MI-1). LED on the TI furnace control board that flashes red, green or amber.

Johnson Controls also sells furnaces under the Coleman and Luxaire names. Codes match only when the control board is the same, so check the board's part number and the label inside the blower door.

CodeMeaningWhat to check
Steady offNo power to the board.24 VAC, fuse. How to fix →
Green heartbeatNormal function, no flame detected (2 seconds on, 2 off).
Amber heartbeatNormal function, flame detected (first-stage heat on two-stage boards). 2 seconds on, 2 off.
Long amber heartbeatTwo-stage boards: normal function, flame detected, second-stage heat (3.5 seconds on, 0.5 off).
Rapid amber flashDirty flame probe: may soon prevent ignition and cause a retry lockout. The heartbeat (2 or 3.5 seconds) flashes rapidly, then 2 seconds off.Clean the flame probe and verify more than 3.0 VDC on the test pads with a meter. How to fix →
3 amberTwo-stage boards: W2 present without W1. Stored once per power cycle.Thermostat, control wiring. How to fix →
4 amberY present with no G. Stored once per power cycle.Thermostat, control wiring. How to fix →
Steady on redControl failure, or board not properly tested.Reset power. If it faults again, replace the control.
Rapid red flashSingle-stage boards: incorrect 24 V phasing or twinning error.24 VAC R and C connections; twinned furnaces must be on the same line phase.
1 redFlame present with gas off. Stored.Gas valve, wiring. How to fix →
2 redPressure switch stuck closed (first-stage pressure switch on two-stage boards). Stored.Pressure switch (first stage), wiring. How to fix →
3 redPressure switch stuck open (first-stage pressure switch on two-stage boards). Stored once per call on W.Pressure switch (first stage), ventor motor. How to fix →
3 double redTwo-stage boards: second-stage pressure switch stuck open. Stored.Pressure switch (second stage), ventor motor. How to fix →
4 redLimit switch opened 5 times in 1 call for heat. Stored.Main limit, blower, filter. How to fix →
5 redRollout switch open. Stored; hard lockout.Rollout switch, overfired. How to fix →
6 redPressure switch cycle lockout. Stored; one-hour soft lockout.Same as code 3. How to fix →
7 redIgnition lockout due to retries. Stored; one-hour soft lockout.Gas flow, pressure, valve; flame sensor. How to fix →
8 redIgnition lockout due to recycles. Stored; one-hour soft lockout.Same as code 7. How to fix →
9 redGrounding or line polarity fault.L1 and neutral, connections, transformer ground, flame probe.
10 redMV/MV1 failure: gas valve energized with W off. Stored.First-stage gas valve, wiring.
10 double redTwo-stage boards: MV2 failure. Stored.Second-stage gas valve, wiring.
11 redMain blower failure. Stored; hard lockout.Main blower, limit switch. How to fix →
2 greenNo active error codes stored (LAST ERROR pressed between 1/5 and 5 seconds).
3 greenStored error codes cleared (LAST ERROR pressed more than 5 seconds).

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: York Service Tips ST-045-09 (September 2, 2009), Generation Before - TI Boards fault code sheet, p. 7. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.