Carrier 58TN0A / 58TN1A Furnace Codes

Applies to: Carrier 58TN0A / 58TN1A (80% two-stage, variable-speed, 4-way multipoise; also 880TA, 881TA). LED on the furnace control, two-digit status codes.

The newer 58TN0B / 58TN1B use three-digit codes and have their own chart. Bryant's manuals print the identical service label: Bryant 880TA/881TA (II880TA-02, p. 35).

CodeMeaningWhat to check
11No previous code.Stored codes are erased automatically after 72 hours or when cleared (see above). After the component test, 11 means the blower motor tested OK; check the inducer motor and hot surface igniter visually.
12Blower on after power up (115 VAC or 24 VAC).The blower runs 90 seconds if the unit is powered up during a call for heat (R-W/W1 closed) or R-W/W1 opens during the blower on-delay.
13Limit circuit lockout: a limit, draft safeguard, flame rollout or blocked vent switch (if used) open longer than 3 minutes, or 10 successive limit trips during high heat.Auto-resets after three hours. See 33. How to fix →
14Ignition lockout.Auto-resets after three hours. See 34. How to fix →
15Blower motor lockout: the blower failed to reach 250 RPM or to communicate within 30 seconds of being turned on, in two successive heating cycles.Auto-resets after 3 hours. See 41.
21Gas heating lockout (does NOT auto reset).Mis-wired gas valve, or a defective control (valve relay).
22Abnormal flame-proving signal: flame is proved while the gas valve is de-energized.The inducer runs until the fault clears. Check for a leaky or stuck-open gas valve.
23Pressure switch did not open.Obstructed pressure tubing, or a pressure switch stuck closed. How to fix →
24Secondary voltage fuse is open.Short circuit in the 24 VAC wiring. How to fix →
25Invalid model selection or setup error: model plug missing or wrong, or setup switch SW1-1 or SW1-6 set wrong.If the code flashes 4 times at power-up, the control is using the model selection stored in memory. Check for a thermostat call with SW1-1, SW1-6 or both ON. Board date code 2103 or later is needed to recognize model plug 007. Check the model plug number and resistance values against the wiring diagram.
31High-heat pressure switch or relay did not close or reopened.The control relay may be defective. See 32. How to fix →
32Low-heat pressure switch did not close or reopened.If it is open longer than five minutes, the inducer shuts off for 15 minutes before retrying; if it opens during the blower on-delay, the blower runs for the selected off-delay. Check for excessive wind, a restricted vent, vent sizing, a defective inducer motor or low inducer voltage (115 VAC), a defective pressure switch, inadequate combustion air, low inlet gas pressure (if an LGPS is used), and disconnected or obstructed pressure tubing. How to fix →
33Limit circuit fault: a limit, draft safeguard, flame rollout or blocked vent switch (if used) is open, or the furnace is in high-heat-only mode after 2 successive low-heat limit trips.The blower runs 4 minutes or until the switch closes, whichever is longer; open more than 3 minutes changes to lockout 13. The flame rollout switch and BVSS need a manual reset. Check for a loose blower wheel, a restricted vent, vent sizing, excessive wind, a dirty filter or restricted ducts, the switch or its connections, and inadequate combustion air (flame rollout switch open). How to fix →
34Ignition proving failure: the control tries three more times before lockout 14.If the flame signal is lost during the blower on-delay, the blower runs for the selected off-delay. Check for oxide on the flame sensor (clean with fine steel wool), flame current (0.5 microamps DC minimum, 4.0-6.0 nominal), the manual shut-off valve, low inlet gas pressure, control ground continuity, a defective or turned-off gas valve, a grounded flame sensor, and poor flame carryover or rough ignition. The green/yellow wire must be connected to the furnace sheet metal. How to fix →
41Blower motor fault: the blower failed to reach 250 RPM or to communicate in time (30 seconds after being turned on, or 10 seconds during steady operation).After the component test: check the blower, wiring and furnace control.
43Low-heat pressure switch open while the high-heat pressure switch is closed.Check for mis-wired pressure switches, a low-heat pressure switch stuck open, low inlet gas pressure (if an LGPS is used), and disconnected or obstructed pressure tubing. How to fix →
45Control circuitry lockout: gas valve relay stuck open, flame sense circuit failure or software check error.Auto-resets after one hour. Reset power to clear the lockout; replace the control if the code repeats.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Carrier 58TN0A/58TN1A Installation, Start-Up, Operating and Service and Maintenance Instructions 58TN0A-02SI, Fig. 52 Service Label p. 35 (read at 400 dpi). The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.