Lennox Merit ML296UHVK / ML296DFVK / ML297UHVK Furnace Codes

Applies to: Lennox Merit ML296UHVK / ML296DFVK / ML297UHVK (two-stage, variable-speed; upflow/horizontal ML296UH045XV36BK, ML296UH070XV36BK, ML296UH090XV48CK, ML296UH110XV60CK; downflow ML296DF045XV36BK, ML296DF070XV48BK, ML296DF090XV60CK; ML297UH045XV36BK, ML297UH070XV36BK, ML297UH090XV36CK, ML297UH090XV60CK, ML297UH110XV60CK, ML297UH135XV60DK). Seven-segment diagnostic LED and push button on the integrated control.

The downflow ML296DFVK instructions (508521-01, pp. 41-44) and the 2026 ML297UHVK instructions (508907-01, pp. 45-48, same Table 27 flame values) print the same diagnostic code list as the upflow ML296UHVK, so all three are covered here.

CodeMeaningWhat to check
E000No error in memory.None.
E110Low line voltage (below the nameplate rating).Check and correct line voltage. Clears 5 seconds after recovery.
E111Listed as low line voltage; Lennox's action is to reverse the line power wiring (polarity).Reverse the line power voltage wiring. Resumes 5 seconds after recovery.
E112Ground not detected; system shuts down.Provide a proper earth ground. Resumes 5 seconds after recovery.
E113High line voltage (above the nameplate rating).Provide voltage within range. Resumes 5 seconds after recovery.
E117Poor ground detected (warning only).Check for proper earth ground. Clears 30 seconds after recovery.
E125Control failed self-check or hardware (flame sense circuit faults, pin shorts, etc.); control not communicating.Cycle power. Replace the control if the problem persists and prevents service. Critical alert; clears 300 seconds after recovery.
E150A2L refrigerant leak alarm.May mean a leak at or in the indoor coil that must be repaired, and the charge verified. Can't be cleared while the sensor still reports a leak.
E151Refrigerant leak detector sensor #1 fault.The sensor reports a problem that stops it working; it may need replacing. Clears when the sensor no longer reports a fault.
E152Refrigerant leak detector #2 fault.Same action as E151 for sensor #2 (Lennox's text repeats sensor #1).
E154Refrigerant leak detector #1 communication lost, or invalid sensor DIP switch setting (disable/enable).Check the wiring harness and connector between the sensor and the furnace control for damage or poor connection, and the sensor for damage or an obstructed harness plug. Clears when communication returns, but the blower latches on for at least 5 minutes. Retest with the LOW GWP test button on the control. May also mean the LOW GWP DIP switches are set wrong.
E155Refrigerant leak detector #2 communication lost.Check the wiring harness and connector between the sensor and the furnace control for damage or poor connection, and the sensor for damage or an obstructed harness plug. Clears when communication returns, but the blower latches on for at least 5 minutes. Retest with the LOW GWP test button on the control.
E160Refrigerant leak detector sensor #1 is the wrong type.Replace it with a Lennox-approved sensor. Clears when a suitable sensor is detected; the blower latches on for at least 5 minutes. Retest with the LOW GWP test button.
E161Refrigerant leak detector sensor #2 is the wrong type.Replace it with a Lennox-approved sensor. Clears when a suitable sensor is detected; the blower latches on for at least 5 minutes.
E163Furnace control board failure (stops proper operation).May need a new control board. Clears when the control operates normally.
E164Low GWP test.Test mode started with the LOW GWP test button. Normal operation resumes and codes clear after 1 minute.
E200Hard lockout: rollout circuit open or previously open.Correct the cause of the rollout trip, or replace the rollout switch. Test operation. Clears after recovery. How to fix →
E204Gas valve miswired.Check gas valve operation and wiring. Clears when repaired.
E205Gas valve control relay contact shorted.Check the wiring on the control and gas valve; if it's correct, replace the control.
E207Hot surface igniter sensed open.Measure igniter resistance; replace if open or outside the range in the instructions. How to fix →
E223Low pressure switch failed open.Check pressure (inches w.c.) of the switch closing on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. How to fix →
E224Low pressure switch failed closed.Check whether the switch is stuck closed on the heat call for longer than 150 seconds. Measure operating pressure; inspect the vent and inducer. How to fix →
E225High pressure switch failed open.Check pressure (inches w.c.) of the switch closing on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. How to fix →
E226High pressure switch failed closed.Check the high pressure switch closing on the heat call, measure operating pressure, inspect the vent and inducer. How to fix →
E227Low pressure switch open during trial for ignition or run mode.Check pressure (inches w.c.) of the switch closing on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. How to fix →
E229Ignition on high fire.The control switched to high-fire ignition because the low-fire pressure switch didn't close in time. No action needed.
E240Low flame current, run mode.Check flame current with the control diagnostics; clean or replace the sensor; measure neutral to ground for a good unit ground. Clears after the heat call completes. How to fix →
E241Flame sensed out of sequence; flame still present.Shut off the gas. Check the gas valve for a leak and replace it if needed. Clears when the fault recovers.
E250Limit switch circuit open.Proper firing rate, no blockage in the heater, proper airflow. If the limit doesn't close within 3 minutes, the unit goes into a 1-hour soft lockout. How to fix →
E270Soft lockout: too many retries, no flame current sensed.Proper gas flow, igniter lighting the burner, flame sensor current. How to fix →
E271Soft lockout: too many retries; last retry failed when the pressure switch opened.Check pressure (inches w.c.) of the switch closing on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. How to fix →
E272Soft lockout: too many recycles; last recycle due to the pressure switch opening.Check whether the low pressure switch is stuck closed, check the high pressure switch closing, measure operating pressure, inspect the vent and inducer. How to fix →
E273Soft lockout: too many recycles; last recycle due to flame failure.Check flame current, clean or replace the sensor, measure neutral to ground for a good unit ground. How to fix →
E274Soft lockout: too many recycles; last recycle failed on the limit circuit, or the limit stayed open over 3 minutes.1-hour soft lockout. Check firing rate and airflow; check for blockage. How to fix →
E275Soft lockout: flame sensed out of sequence; flame signal now gone.Shut off the gas and check the gas valve for a leak. 1-hour soft lockout; clears when flame is proven stable.
E292Indoor blower motor can't start (obstructed wheel, seized bearings).Replace the motor or wheel if the assembly doesn't run or meet performance. 1-hour soft lockout clears after the blower starts.
E311Heat rate reduced to match indoor blower airflow (warning only).The blower is in cutback for restricted airflow and the firing rate drops every 60 seconds to match; 2-stage controls drop to first stage. Check the filter and duct system. How to fix →
E390Low GWP relay stuck.A problem with the low GWP relay on the control; may need a new control board. Clears when the relay works normally.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Lennox ML296UHVK Merit Series Gas Furnace Installation Instructions 508520-01 (06/2026), Ignition Control Diagnostic Codes pp. 44-47, Table 27 flame signal p. 61. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.