Bryant 820SA / 821SA Furnace Codes

Applies to: Bryant 820SA / 821SA (80% single-stage, 4-way multipoise). LED on the furnace control, two-digit status codes.

CodeMeaningWhat to check
11No previous code.Stored codes are erased automatically after 72 hours or when cleared (see above). After the component test, 11 means no errors were detected; check the inducer motor, hot surface igniter and blower motor visually.
12Blower on after power up (115 VAC or 24 VAC).The blower runs 90 seconds if the unit is powered up during a call for heat (R-W closed) or R-W opens during the blower on-delay.
13Limit circuit lockout: the limit, draft safeguard, flame rollout or blocked vent switch (if used) open longer than 3 minutes.Auto-resets after three hours. See 33. How to fix →
14Ignition lockout.Auto-resets after three hours. See 34. How to fix →
21Gas heating lockout (does NOT auto reset).Mis-wired gas valve, or a defective control (valve relay).
22Abnormal flame-proving signal: flame is proved while the gas valve is de-energized.The inducer runs until the fault clears. Check for a leaky or stuck-open gas valve.
23Pressure switch did not open.Obstructed pressure tubing, or a pressure switch stuck closed. How to fix →
24Secondary voltage fuse is open.Short circuit in the 24 VAC wiring. How to fix →
25Invalid model selection or setup error: model plug missing or wrong, or setup switch SW1-1 or SW1-6 set wrong.If the code flashes 4 times at power-up, the control is using the model selection stored in memory. Check for a thermostat call with SW1-1, SW1-6 or both ON.
31Pressure switch did not close or reopened.If it is open longer than five minutes, the inducer shuts off for 15 minutes before retrying; if it opens during the blower on-delay, the blower runs for the selected off-delay. Check for excessive wind, vent sizing, a defective inducer motor or low inducer voltage (115 VAC), a defective pressure switch, inadequate combustion air, disconnected or obstructed pressure tubing, low inlet gas pressure (if an LGPS is used) and a restricted vent. How to fix →
33Limit circuit fault: a limit, draft safeguard, flame rollout or blocked vent switch (if used) is open.The blower runs 4 minutes or until the switch closes, whichever is longer. Open more than 3 minutes changes to lockout 13; open less than 3 minutes, 33 keeps flashing until the blower shuts off. The flame rollout switch and BVSS need a manual reset. Check for a restricted vent, vent sizing, a loose blower wheel, excessive wind, a dirty filter or restricted ducts, a defective blower motor or capacitor, the switch or its connections, and inadequate combustion air (flame rollout switch open). How to fix →
34Ignition proving failure: the control tries four ignition trials before lockout 14.If the flame signal is lost during the blower on-delay, the blower runs for the selected off-delay. Check for oxide on the flame sensor (clean with fine steel wool), flame current (0.5 microamps DC minimum, 4.0-6.0 nominal), the manual shut-off valve, low inlet gas pressure, control ground continuity, a defective or turned-off gas valve, a grounded flame sensor, and poor flame carryover or rough ignition. How to fix →
45Control circuitry lockout: gas valve relay stuck open, flame sense circuit failure or software check error.Auto-resets after one hour. Reset power to clear the lockout; replace the control if the code repeats.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Bryant 820SA/821SA Installation, Start-Up, Operating and Service and Maintenance Instructions II820SA-02, Fig. 43 Service Label (344738-201 Rev. A) p. 26 (read at 500 dpi). The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.