Home / Charts / Carrier furnace codes

Carrier 59TN6C two-stage condensing Furnace Codes

Applies to: Carrier 59TN6C two-stage condensing (variable-speed, 35 in. tall: 59TN6C040C14, 59TN6C060C17, 59TN6C080C17, 59TN6C080C21, 59TN6C100C21, 59TN6C120C24). Three-digit display on the control (major.minor, e.g. 14.1), plus the Status Code LED seen through the sight glass on the door.

CodeMeaningWhat to check
10.1L1 polarity fault (LED flashes rapidly).Check line voltage polarity and ground; the furnace won't run with reversed polarity.
10.2Dissipation system active; blower runs.The control runs the blower while the refrigerant dissipation system is active.
otAFirmware install in process.Wait for the install to finish.
btLFailed to load; retry the firmware install.Retry the firmware install.
12.1W on at power-up.Normal: the blower runs 90 seconds if the unit is powered up during a heat call (R-W closed) or when R-W opens during the blower on-delay.
13.1Limit lockout: the limit or flame rollout open longer than 3 minutes.Auto-resets after 3 hours. See 33.1: dirty filter or restricted ducts, loose blower wheel, defective switch or connections, defective blower motor, wrong gas input. How to fix →
14.1Ignition lockout after 4 consecutive ignition tries.Auto-resets after 3 hours. See 34.1. How to fix →
14.2Flame lost 3 times after 70 seconds of heating.See 34.x for flame checks. How to fix →
14.3Lockout: 7 loss-of-flame events during a heat call.See 34.x for flame checks. How to fix →
15.1Blower lockout: no blower RPM detected.Check for loose blower wire connections and a failed blower motor. How to fix →
15.2Lockout: blower failed to reach 500 RPM at start-up.Check for loose blower wire connections and a failed blower motor. How to fix →
17.1Lost Bluetooth module (BTM) communication.Carrier gives no further steps.
21.124 VAC sensed on the gas valve when it shouldn't be; power reset only.Turn off power and wait 5 minutes to retry. Check for a stuck-closed gas valve relay on the control and a miswire or short at the gas valve wire.
22.1False flame: flame proved while the gas valve is off.The inducer runs until the fault clears. Check for a stuck-open or leaky gas valve. How to fix →
23.4Low pressure switch (LPS) stuck closed.Check for an obstructed pressure tube and a pressure switch stuck closed. How to fix →
23.5High pressure switch (HPS) stuck closed.Check for an obstructed pressure tube and a pressure switch stuck closed. How to fix →
24.1Fuse fault.Look for a short in the 24 V wiring, including thermostat leads. Disconnect the thermostat leads to isolate it. How to fix →
25.1No program in the control; no heating.If the program in the control is missing, not recognized or corrupted, reprogram the control with the program number on the rating plate (service app or super plug). Replace the control if the problem remains.
25.2Corrupted program file; no heating.Reprogram the control with the service app or a super plug. If the program in the control is missing, not recognized or corrupted, reprogram the control with the program number on the rating plate (service app or super plug). Replace the control if the problem remains.
25.4Main program invalid; running on the backup program.The control still runs normally. Reprogram it to correct the problem.
25.5Installer settings corrupted.Reselect the installer settings or reprogram the control. It runs on default installer settings meanwhile.
25.6Wrong program for this control; no heating.Reprogram the control so the program matches the control used.
27.1Program in the super plug missing, not recognized or corrupted.Remove the super plug and retry. If you still get a 27 code, try a different super plug. If that fails, replace the control.
27.2Program in the super plug missing, not recognized or corrupted.Remove the super plug and retry. If you still get a 27 code, try a different super plug. If that fails, replace the control.
27.3Program in the super plug missing, not recognized or corrupted.Remove the super plug and retry. If you still get a 27 code, try a different super plug. If that fails, replace the control.
31.6Open high pressure switch: HPS failed to close in 75 seconds when high heat is required.Check for a secondary pressure switch that failed to close after three trials, excessive wind, a restricted vent, a defective inducer motor, low inlet gas pressure (if a low gas pressure switch is used), inadequate combustion air, proper vent sizing, disconnected or obstructed pressure tubing, and restricted or blocked condensate drainage. If it opens during the blower on-delay, the blower comes on for the selected off-delay. (Carrier's troubleshooting guide words 31.6 as the HPS not closing for one minute after the gas valve opened, or reopening.) How to fix →
31.7High heat only for the rest of the current cycle (HPS failed to close in 75 seconds going from low to high heat).Check for a secondary pressure switch that failed to close after three trials, excessive wind, a restricted vent, a defective inducer motor, low inlet gas pressure (if a low gas pressure switch is used), inadequate combustion air, proper vent sizing, disconnected or obstructed pressure tubing, and restricted or blocked condensate drainage. If it opens during the blower on-delay, the blower comes on for the selected off-delay. How to fix →
32.2Open low pressure switch (main pressure switch).If the LPS is open longer than 5 minutes or has reopened, the inducer shuts off for 15 minutes before retrying. If the low-heat switch opens within 5 minutes after the gas valve turns on, the next cycle is forced to high heat (32.2 stays shown during it). Troubleshoot as 31.6 and 31.7. How to fix →
33.1Main limit circuit open (limit or flame rollout).The blower runs 4 minutes or until the switch recloses, whichever is longer. Open longer than 3 minutes changes to lockout 13. The flame rollout switch needs a manual reset. Check for a dirty filter or restricted ducts, loose blower wheel, defective switch or connections, defective blower motor, wrong gas input. How to fix →
34.1Ignition fault: four consecutive ignition trials failed.First check the gas valve and manual shutoff are on, the green/yellow wire is connected to the furnace sheet metal, and the flame sensor isn't grounded. Then remove R and run the component test: the igniter should glow orange/white by the end of the 15-second warm-up. If not, unplug the igniter harness and rerun: no 115 V between pin 1 and NEUTRAL-L2 means replace the control; 115 V present means check the harness and igniter. How to fix →
34.5After successful ignition: low heat flame lost before the blower on-delay.Check flame current during trial for ignition: nominal 4.0-6.0 µA. Below 0.5, clean the sensor with fine steel wool and recheck; if still low, replace the electrode. If current is near normal and the burners still won't stay on, replace the control. How to fix →
34.6Low heat flame lost after the blower on-delay.Same flame checks as 34.5. How to fix →
34.7High heat flame lost before the blower on-delay.Same flame checks as 34.5. How to fix →
34.8High heat flame lost after the blower on-delay.Same flame checks as 34.5. (Carrier's troubleshooting guide words 34.5-34.8 differently from the service label; this chart follows the label.) How to fix →
41.1No blower RPM at start-up.Check for loose blower wire connections and a failed blower motor. How to fix →
41.2No RPM while the blower motor is running.Check for loose blower wire connections and a failed blower motor. How to fix →
41.3Blower failed to reach 500 RPM at start-up.Check for loose blower wire connections and a failed blower motor. How to fix →
43.1HPS closed before LPS.Check the pressure switches and tubing. How to fix →
45.1Control failure: flame circuit fault, memory mismatch or sequence error (1 hour).Cycle power. If code 45 repeats, replace the control.
45.2Control failure: gas valve relay won't close.Cycle power. If code 45 repeats, replace the control.
45.3Control failure: EEPROM memory error (1 hour).Cycle power. If code 45 repeats, replace the control.
45.4Control failure: micro loss of communication.Cycle power. If code 45 repeats, replace the control.
51.1Outdoor air temperature sensor open.Check for a loose connection at the control board screw terminals, cut or shorted sensor wires, and a damaged sensor.
51.2Outdoor air temperature sensor shorted.Check for a loose connection at the control board screw terminals, cut or shorted sensor wires, and a damaged sensor.
52.1Supply air temperature sensor open.Check for a loose connection at the control board screw terminals, cut or shorted sensor wires, and a damaged sensor.
52.2Supply air temperature sensor shorted.Check for a loose connection at the control board screw terminals, cut or shorted sensor wires, and a damaged sensor.
53.1Return air temperature sensor open.Make sure the RAT sensor is firmly plugged into the control board; check for a damaged sensor.
53.2Return air temperature sensor shorted.Make sure the RAT sensor is firmly plugged into the control board; check for a damaged sensor.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Carrier 59TN6C Installation, Start-up, Operating, Service and Maintenance Instructions 59TN6C-04SI (7/26), service label Fig. 61 p. 57 (read at 400 dpi), troubleshooting guide pp. 76-77. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.

Related

Other brands