Home / Charts / Goodman / Amana / Daikin furnace codes

Goodman / Amana / Daikin GMES92 / GMES96 / GCES96 Furnace Codes

Applies to: Goodman / Amana / Daikin GMES92 / GMES96 / GCES96 (single-stage, 92% and 96%: GMES92, GMES96, GCES96, Amana AMES92, AMES96, ACES96, Daikin VMES96, VCES96). Single red diagnostic LED on the integrated ignition control.

CodeMeaningWhat to check
OffNo signal: control failure, no power, internal fault or IRQ loss; also a gas heating lockout (gas valve energized when it should be off, or off when it should be on).Check 115 V and 24 V to the control (disconnect, door switch, 24 V wires), the 3 A fuse and breaker, and look for shorts in the 115 V and 24 V circuits. About 13 V between C and R on the terminal board with 24 V at the transformer points to a blown fuse. How to fix →
Continuous onNormal operation.None.
1 flashSystem lockout: too many ignition retries (3 total).Failure to establish flame (no gas, front cover pressure switch stuck open, bad igniter or alignment, wrong orifices, coated or oxidized flame sensor) or loss of flame after it was established (interrupted gas, lazy flames from gas pressure or flue/combustion air restriction, front cover pressure switch opening, weak inducer). Goodman says to sand the flame sensor with emery cloth if it's coated. How to fix →
2 flashesPressure switch stuck closed (inducer not running).Inducer pressure switch contacts sticking, or a short in the pressure switch circuit. How to fix →
3 flashesPressure switch stuck open; inducer runs continuously.Pressure switch hose blocked, pinched or misconnected; blocked flue or inlet pipe, blocked drain system or weak inducer; wrong setpoint or bad contacts; loose wiring. How to fix →
4 flashesOpen high temperature (primary or auxiliary) limit; circulator blower runs continuously.Faulty limit; not enough air over the heat exchanger (blocked filters, restrictive ductwork, wrong blower speed, failed blower); loose wiring. How to fix →
5 flashesFlame sensed more than 4.25 seconds with the gas valve de-energized; inducer and circulator run continuously.Short to ground in the flame sense circuit (sensor or wiring).
6 flashesOpen flame rollout switch, or the control's fuse is blown.Flame rollout, misaligned burners, blocked flue or inlet pipe, failed inducer, loose wiring, a short in the 24 V control or safety circuits, or a faulty rollout limit. Replace the fuse only with a 3 A automotive fuse. How to fix →
7 flashesLow flame sense signal (furnace still runs; not stored).Coated or oxidized flame sensor, sensor out of position, or lazy flame from wrong gas pressure or combustion air. Clean the sensor (steel wool or emery cloth, per Goodman), check alignment and compare gas pressure with the rating plate. How to fix →
8 flashesIgniter relay fault.Improperly connected or bad igniter, poor unit or burner ground, or a faulty control. Check the igniter wiring and the ground wire; replace the control if the rest checks out. How to fix →
9 flashesTwinning fault: circulator blowers not running together (not stored).Twin terminals not connected by field wiring, or the isolating relay missing or wired wrong. Check each furnace's fan motor without the twin connection, then wire per the twinning diagram.
10 flashesOpen fuse / no 24 V to the control.A high voltage surge blew the fuse; replace it with line voltage off. How to fix →
11 flashesIgniter open.Improperly connected or bad igniter, poor unit or burner ground. Check the igniter wiring and ground; replace the igniter if open. How to fix →
12 flashesInducer relay fault or improper grounding.Improperly connected or bad inducer, blockage in the inducer or vent, poor unit ground, or a faulty control.
Rapid flash115 V or 24 V polarity reversed.115 V polarity reversed at the furnace or control, the orange and gray transformer wires reversed, or a poor unit ground.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Goodman/Amana/Daikin GMES9/GCES9/AMES9/ACES9/VMES9/VCES9 Service Instructions RS6612016 Rev. 3 (2020), LED code memory table p. 43, Troubleshooting pp. 46-48. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.