Carrier 59TP6B / 59TP6A / 59TN6A two-stage Furnace Codes

Applies to: Carrier 59TP6B / 59TP6A / 59TN6A two-stage (condensing, two-digit codes; also 926TA, 926TB, 986TB, PG96VAT, PG96VTAA). Status code LED on the furnace control, seen through the sight glass in the blower door; two-digit codes.

The 59TP6B (59TP6B-01SI, 04/19, p. 72), 59TP6A (59TP6A-10SI, 11/18, p. 73) and 59TN6A (59TN6A-13SI, 08/18, p. 72) service labels print the same code list. The 59TN6B adds blower codes 15 and 41, and the 59TP6C uses three-digit codes; see those charts. Bryant's manuals print the identical service label: Bryant 926TA (II926TA-10, p. 73), 926TB (II926TB-04, p. 67) and 986TB (II986TB-10, p. 72). So do Payne's PG96VAT (IM-PG96VAT-13, Fig. 65 p. 70) and PG96VTA series A (IM-PG96VTAA-04, Fig. 70 p. 66) manuals; the series B PG96VTAB has a three-digit label and its own chart.

CodeMeaningWhat to check
11No previous code.Stored codes are erased automatically after 72 hours or as described under code recall.
12Blower on after power up (115 VAC or 24 VAC).The blower runs 90 seconds if the unit is powered up during a call for heat (R-W/W1 closed) or R-W/W1 opens during the blower on-delay.
13Limit circuit lockout.A limit or flame rollout switch was open longer than 3 minutes, or 10 successive limit trips occurred during high heat. Auto-resets after 3 hours. See code 33. How to fix →
14Ignition lockout.Auto-resets after 3 hours. See code 34. How to fix →
21Gas heating lockout.Does NOT auto-reset. Check for a miswired gas valve and a defective control (valve relay).
22Abnormal flame-proving signal: flame proved while the gas valve is off.The inducer runs until the fault clears. Check for a leaky or stuck-open gas valve. How to fix →
23Pressure switch did not open.Check for obstructed pressure tubing and a pressure switch stuck closed. How to fix →
24Secondary voltage fuse is open.Look for a short circuit in the 24 VAC wiring. How to fix →
25Model selection or setup error.The model plug (PL4) is missing or wrong, or setup switch SW1-1 or SW1-6 is set wrong. If it flashes only 4 times at power-up, the control is defaulting to the model selection stored in memory. Check for a thermostat call with SW1-1 ON or with SW1-6 ON, SW1-1 and SW1-6 both ON, or two different furnace models twinned. If it flashes continuously, see the wiring diagram for the model plug number and resistance values.
31High-heat pressure switch or HPSR relay did not close or reopened.The high-heat pressure switch input failed to close on a call for high heat, or opened during high heat. The HPSR relay may be defective. See code 32. How to fix →
32Low-heat pressure switch did not close or reopened.The low-heat pressure switch failed to close on a call for low heat or opened during low heat. If it opens within 5 minutes after ignition, the next heating cycle is restricted to high heat. Check for proper vent sizing, a plugged condensate drain, excessive wind, low inlet gas pressure (if a low gas pressure switch is used), improper pressure switch wiring, restricted combustion air, disconnected or obstructed pressure tubing, water in the vent piping (possibly sagging pipe), and failed or out-of-calibration pressure switches. How to fix →
33Limit circuit fault.A limit or flame rollout is open, or the furnace is in high-heat-only mode after 2 successive low-heat limit trips. The blower runs 4 minutes or until the switch recloses, whichever is longer. Open longer than 3 minutes changes to lockout 13. The flame rollout switch needs a manual reset. Check for an improper limit switch or missing limit gasket, defective switch or connections, wrong low or high-heat gas input, loose blower wheel, and a stuck high-heat solenoid in the gas valve. How to fix →
34Ignition proving fault.The control tries three more times before lockout 14. If flame is lost during the blower on-delay, the blower comes on for the off-delay. Check for oxide on the flame sensor (clean with fine steel wool), the manual shutoff valve, control ground continuity, flame current (0.5 µA DC min., 4.0-6.0 nominal), a defective or turned-off gas valve, low inlet gas pressure, poor flame carryover or rough ignition, a defective hot surface igniter, a grounded flame sensor, and the green/yellow wire connected to the furnace sheet metal. How to fix →
43Low-heat pressure switch open while the high-heat pressure switch is closed.Check for a plugged condensate drain, low inlet gas pressure (if a low gas pressure switch is used), improper pressure switch wiring, water in the vent piping (possibly sagging pipe), a stuck-open low-heat pressure switch, and disconnected or obstructed pressure tubing. How to fix →
45Control circuitry lockout.Auto-resets after a 1-hour lockout, caused by a gas valve relay contact stuck open, flame sense circuit failure or software check error. Reset power to clear it; replace the control if the code repeats.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Carrier 59TP6B Installation, Start-up, Operating and Service and Maintenance Instructions 59TP6B-01SI (04/19), service label Fig. 64 p. 72 (read at 450 dpi); same list on 59TP6A-10SI p. 73 and 59TN6A-13SI p. 72. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.