Home / Charts / Lennox furnace codes

Lennox SL280UHV Furnace Codes

Applies to: Lennox SL280UHV (80% two-stage variable speed). Seven-segment diagnostic display on the integrated control.

Other Lennox furnaces with the same style of integrated control use E-codes too, but check the installation instructions for your model.

CodeMeaningWhat to check
E000No error in memory.
E105Communication problem: no other devices on the RS-BUS.Communicating thermostat wiring (i, R, C).
E110Line voltage low.Supply voltage under load.
E111Line voltage low, likely reversed line power wiring.Check hot and neutral at the furnace. How to fix →
E112No ground detected; system shuts down.Verify the ground to the furnace. How to fix →
E113Line voltage high.Supply voltage.
E114Line frequency out of range (not 60 Hz).Generator or supply problem.
E11524 V power low.Transformer and 24 V wiring, shorts loading the circuit. How to fix →
E11624 V power high.Transformer and supply voltage.
E117Poor ground detected (warning).Ground connection. How to fix →
E120Unresponsive device (communicating systems).Communicating wiring and devices.
E124Communicating thermostat signal missing for more than 3 minutes.Thermostat wiring and power.
E125Control failed self-check or internal hardware fault.Replace the integrated control.
E131Corrupted control parameters.Reprogram or replace the control.
E150A2L refrigerant leak alarm.Find the leak; the furnace runs the blower to dilute refrigerant.
E151A2L refrigerant sensor fault.Sensor and its wiring.
E180Outdoor air temperature sensor failure.Sensor and wiring (communicating systems).
E200Hard lockout: rollout circuit open or previously open.Find the cause of the rollout trip before resetting. How to fix →
E201Indoor blower communication failure.Blower motor wiring and motor.
E202Indoor blower motor does not match unit capacity.Wrong replacement motor or setup.
E203Appliance capacity/size not programmed.Program the unit size per the installation instructions.
E204Gas valve mis-wired.Gas valve wiring. How to fix →
E205Gas valve control relay contact shorted.Replace the integrated control.
E206Gas valve second-stage relay failure.Furnace runs on first stage; replace the control.
E207Hot surface igniter sensed open.Igniter and its wiring. How to fix →
E223Low pressure switch failed open.Vent, intake, hoses, condensate, inducer. How to fix →
E224Low pressure switch failed closed.Stuck switch or wiring short. How to fix →
E225High pressure switch failed open.Vent, intake, hoses, inducer. How to fix →
E226High pressure switch failed closed.Stuck switch or wiring short. How to fix →
E227Low pressure switch open during trial for ignition or run.Vent, condensate trap, hoses. How to fix →
E228Combustion air inducer calibration failure.Vent system and pressure switch wiring. How to fix →
E229Ignition moved to high fire because the low pressure switch closed late (no action needed).
E240Low flame current in run mode.Clean the flame sensor; check ground and gas pressure. How to fix →
E241Flame sensed out of sequence, flame still present.Gas valve leaking through. How to fix →
E250Limit switch circuit open.Airflow: filter, blower, ducts, coil. How to fix →
E252Discharge air temperature too high (gas heat).Airflow and temperature rise. How to fix →
E270Soft lockout: maximum retries exceeded, no flame current sensed.Gas supply, igniter, flame sensor. How to fix →
E271Soft lockout: maximum retries exceeded, last retry failed on pressure switch opening.Venting and pressure switch. How to fix →
E272Soft lockout: maximum recycles exceeded, last recycle from pressure switch opening.Venting, condensate, pressure switch. How to fix →
E273Soft lockout: maximum recycles exceeded, last recycle from flame failure.Flame sensor, gas pressure, ground. How to fix →
E274Soft lockout: maximum recycles exceeded, limit opened or stayed open over 3 minutes.Airflow. How to fix →
E275Soft lockout: flame sensed out of sequence, flame signal now gone.Gas valve, flame sense wiring. How to fix →
E290Igniter circuit fault.Igniter and wiring. How to fix →
E292Indoor blower motor can't start (obstructed wheel or seized bearings).Blower wheel and motor.
E295Indoor blower motor temperature too high.Airflow restriction, motor. How to fix →
E310Discharge temperature sensor failure.Sensor and wiring.
E311Heat rate reduced to match indoor blower airflow (warning).Restricted ducts or filter. How to fix →
E312Restricted airflow in cooling or continuous fan (warning).Ducts, filter, coil. How to fix →
E313Indoor/outdoor unit capacity mismatch (communicating, warning).
E334Y1 relay stuck on the integrated control.Replace the control.
E347No 24 V on Y1 with a non-communicating outdoor unit; stage 1 relay failed.Control relay, Y1 wiring.
E348No 24 V on Y2 with a non-communicating outdoor unit; stage 2 relay failed.Control relay, Y2 wiring.
E370Interlock (door) switch open for 2 minutes.Blower door and door switch.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Lennox SL280UHV Installation Instructions 508245-01 (04/2024), Integrated Control Diagnostic Codes. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.