Carrier 58CTA / 58CTX Furnace Codes
Similar two-digit status codes are used on many Carrier, Bryant and Payne two-stage furnaces, but titles and causes vary by model. Check the service label on the blower door.
| Code | Meaning | What to check |
|---|---|---|
| 11 | No previous code. | Stored codes are erased automatically after 72 hours. On red LED boards they are also erased when 115 VAC or 24 VAC to the control is interrupted. |
| 12 | Blower on after power up. | The blower runs for the selected off-delay if the unit is powered up during a call for heat (R-W/W1 closed) or R-W/W1 opens during the blower on-delay. |
| 13 | Limit circuit lockout. | A limit, draft safeguard, flame rollout or blocked vent switch (if used) was open longer than 3 minutes. Auto-resets after three hours. See code 33. How to fix → |
| 14 | Ignition lockout. | Auto-resets after three hours. See code 34. How to fix → |
| 21 | Gas heating lockout. The control will not auto reset. | Mis-wired gas valve, or a defective control (valve relay). |
| 22 | Abnormal flame-proving signal. | Flame is proved while the gas valve is de-energized; the inducer runs until the fault clears. Leaky or stuck-open gas valve. How to fix → |
| 23 | Pressure switch did not open. | Obstructed pressure tubing, or pressure switch stuck closed. How to fix → |
| 24 | Secondary voltage fuse is open. | Short circuit in the 24 VAC wiring. Replace with a 3-amp fuse only. How to fix → |
| 31 | High-heat pressure switch or relay did not close or reopened. | The control relay may be defective. See code 32. How to fix → |
| 32 | Low-heat pressure switch did not close or reopened. | Open longer than five minutes: the inducer shuts off for 15 minutes before retrying. Excessive wind, restricted vent, vent sizing, defective inducer or pressure switch, low inducer voltage (115 VAC), combustion air supply, low inlet gas pressure (if LGPS used), disconnected or obstructed pressure tubing. How to fix → |
| 33 | Limit circuit fault. | A limit, draft safeguard, flame rollout or blocked vent switch is open; after 3 minutes it becomes code 13. Flame rollout switch and BVSS are manual reset. Dirty filter or restricted ducts, blower motor or capacitor, loose blower wheel, vent sizing or restriction, wind, combustion air. How to fix → |
| 34 | Ignition proving failure. | The control tries three more times before code 14. Clean oxide off the flame sensor (fine steel wool); flame current 0.5 microamps DC minimum, 4.0 to 6.0 nominal. Manual valve, gas valve, inlet gas pressure, control ground (green/yellow wire to sheet metal), flame carryover, hot surface igniter. How to fix → |
| 43 | Low-heat pressure switch open while high-heat pressure switch is closed. | Disconnected or obstructed pressure tubing, mis-wired pressure switches, low-heat switch stuck open, low inlet gas pressure (if LGPS used). How to fix → |
| 45 | Control circuitry lockout. | Gas valve relay stuck open, flame sense circuit failure, or software check error. Auto-resets after one hour. Reset power; replace the control if the code repeats. |
How to read the codes
- Two-digit codes: the first digit is the number of short flashes and the second the number of long flashes.
- Continuous off: check for 115 VAC at L1 and L2 and 24 VAC at SEC-1 and SEC-2. Continuous on: the control has 24 VAC power. Rapid flashing: line voltage (115 VAC) polarity reversed; if twinned, see the twinning kit instructions.
- Code recall (amber LED controls): with no thermostat call and blower off-delays finished, leave 115 V on, remove the outer door, then briefly remove the insulated wire from the draft safeguard switch (DSS) until the LED goes out and reconnect it. The LED shows each stored code four times; repeat for older codes until code 11. Up to five codes are stored, and they are not erased by a power interruption.
- On red LED boards, the service label says to briefly remove and reconnect one main limit wire instead, without removing power or the blower door first.
Source: Carrier 58CTA/CTX Series 140/E Installation, Start-up, Operating and Service and Maintenance Instructions, Form 58CT-12SI, Fig. 51 Service Label (327598-101 Rev. C), p. 45, and code recall, p. 44. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.
Related
- How to read furnace LED flash codes
- Furnace pressure switch troubleshooting
- Flame sensor microamps and cleaning
Other brands
- Lennox Merit ML180UH (80% single-stage)
- Carrier 58CVA / 58CVX (80% variable-speed two-stage)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N9MSE (90% single-stage condensing, PSC blower)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N8MSN / N8MSL (80% single-stage, PSC blower)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N80ESU / R80ESU (80% single-stage, ECM blower, Ultra Low NOx, minor series 2 and 3)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N80MSU (80% single-stage, ECM blower, Ultra Low NOx, 3-digit display, minor series 3)
- Rheem / Ruud R96V / 96MDV (96% two-stage communicating)
- Rheem / Ruud R97V (97% modulating communicating, downflow/horizontal)
- Rheem / Ruud R98V (98% modulating communicating, upflow)
- Goodman / Amana GR9S80 / GD9S80 (80% single-stage)
- Trane / American Standard S9X1 / S9X2 / S9B1 (96% condensing)
- Lennox SL280UHV (80% two-stage variable speed)
- Goodman / Amana / Daikin GM9S96 / GC9S96 / GM9S92 (96% and 92% condensing, single-stage)
- Carrier 59TP6C two-stage condensing with InteliSense (Performance series)
- Lennox G60DF / G60DFV (older two-stage SureLight boards 18M3401, 46M9901, 18M9901, 49M5901)
- Lennox G60UH / G60UHV (SureLight boards 100869 and 100870)
- Rheem / Ruud R801T Ultra Low NOx (14 ng/J) single-stage upflow/horizontal, constant-torque blower
- Rheem / Ruud 802V / 80MDV (80% two-stage communicating, ECM blower; model numbers (-)802V and (-)(-)80MDV)
- Trane / American Standard S8B1 / S8X1 / S8X2 (80% single-stage and two-stage)
- Trane / American Standard A801X060AM3S (80% single-stage, 2024 installation manual)
- Trane / American Standard A801X (80% single-stage: A801X040AM3SD, A801X040BM2SD, A801X060BM4SD, A801X080BM4SD, A801X080CM5SD, A801X100CM5SD, A801X120DM5SD)
- Goodman / Amana GMVC96 / GCVC96 (96% two-stage variable-speed, *MVC96*BA and *CVC96*BA)
- Goodman / Amana GMVS96 / AMVS96 U-revision (96% variable-speed with analog pressure sensor, model numbers GMVS96*U and AMVS96*U)
- Goodman / Amana GMVM96 / GCVM96 / AMVM96 / ACVM96 (96% modulating, model numbers *MVM96 and *CVM96)
- Rheem / Ruud R801T / 80MSX (80% single-stage, constant-torque blower; model numbers (-)801T and (-)(-)80MSX)
- Rheem / Ruud 802P / 80MDP (80% two-stage, model numbers (-)802P and (-)(-)80MDP)
- Rheem / Ruud 802T / 80MDT (80% two-stage with constant-torque blower, model numbers (-)802T and (-)(-)80MDT)
- Rheem / Ruud 801S / 801P / 80MSS / 80MSP (80% single-stage, model numbers (-)801S, (-)801P, (-)(-)80MSS and (-)(-)80MSP)
- Rheem / Ruud W801T (Rheem Select 80% downflow single-stage)
- Rheem / Ruud R951T (95% single-stage condensing, constant-torque blower; model numbers (-)951T)
- Rheem / Ruud 801V Ultra Low NOx (80% communicating, constant CFM blower, upflow/horizontal)
- Carrier 58STA / 58STX (80% single-stage, 4-way multipoise)
- York TG9S (95.5% AFUE single-stage PSC, multi-position)
- York TM9V (96% AFUE two-stage variable-speed ECM, multi-position)
- York UTEC Board (single- and two-stage furnaces from August 2009; SAP 539617, 542760, 542767, 542766; Source 1 S1-33102956000, S1-03102951001, S1-33102954000, S1-33102955000)
- York White-Rodgers Board (the generation before the 2009 UTEC boards; 265901, S1-33109167000 / 265902, S1-33109168000 / 265903, S1-33109169000 / 265904)
- York TI Board (older furnaces; 031-01972-000 TI 6DT-1, 031-01973-000 TI 6DT-2, 031-09117-000 TI 6MD-1, 031-09118-000 TI 6MI-1)
- Carrier 58SB0A / 58SB1A (single-stage, non-condensing)