Carrier 58CTA / 58CTX Furnace Codes

Applies to: Carrier 58CTA / 58CTX (80% two-stage, 4-way multipoise, Series 140/E). Status code LED on the furnace control, seen through the sight glass in the blower door; two-digit codes.

Similar two-digit status codes are used on many Carrier, Bryant and Payne two-stage furnaces, but titles and causes vary by model. Check the service label on the blower door.

CodeMeaningWhat to check
11No previous code.Stored codes are erased automatically after 72 hours. On red LED boards they are also erased when 115 VAC or 24 VAC to the control is interrupted.
12Blower on after power up.The blower runs for the selected off-delay if the unit is powered up during a call for heat (R-W/W1 closed) or R-W/W1 opens during the blower on-delay.
13Limit circuit lockout.A limit, draft safeguard, flame rollout or blocked vent switch (if used) was open longer than 3 minutes. Auto-resets after three hours. See code 33. How to fix →
14Ignition lockout.Auto-resets after three hours. See code 34. How to fix →
21Gas heating lockout. The control will not auto reset.Mis-wired gas valve, or a defective control (valve relay).
22Abnormal flame-proving signal.Flame is proved while the gas valve is de-energized; the inducer runs until the fault clears. Leaky or stuck-open gas valve. How to fix →
23Pressure switch did not open.Obstructed pressure tubing, or pressure switch stuck closed. How to fix →
24Secondary voltage fuse is open.Short circuit in the 24 VAC wiring. Replace with a 3-amp fuse only. How to fix →
31High-heat pressure switch or relay did not close or reopened.The control relay may be defective. See code 32. How to fix →
32Low-heat pressure switch did not close or reopened.Open longer than five minutes: the inducer shuts off for 15 minutes before retrying. Excessive wind, restricted vent, vent sizing, defective inducer or pressure switch, low inducer voltage (115 VAC), combustion air supply, low inlet gas pressure (if LGPS used), disconnected or obstructed pressure tubing. How to fix →
33Limit circuit fault.A limit, draft safeguard, flame rollout or blocked vent switch is open; after 3 minutes it becomes code 13. Flame rollout switch and BVSS are manual reset. Dirty filter or restricted ducts, blower motor or capacitor, loose blower wheel, vent sizing or restriction, wind, combustion air. How to fix →
34Ignition proving failure.The control tries three more times before code 14. Clean oxide off the flame sensor (fine steel wool); flame current 0.5 microamps DC minimum, 4.0 to 6.0 nominal. Manual valve, gas valve, inlet gas pressure, control ground (green/yellow wire to sheet metal), flame carryover, hot surface igniter. How to fix →
43Low-heat pressure switch open while high-heat pressure switch is closed.Disconnected or obstructed pressure tubing, mis-wired pressure switches, low-heat switch stuck open, low inlet gas pressure (if LGPS used). How to fix →
45Control circuitry lockout.Gas valve relay stuck open, flame sense circuit failure, or software check error. Auto-resets after one hour. Reset power; replace the control if the code repeats.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Carrier 58CTA/CTX Series 140/E Installation, Start-up, Operating and Service and Maintenance Instructions, Form 58CT-12SI, Fig. 51 Service Label (327598-101 Rev. C), p. 45, and code recall, p. 44. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.