Home / Charts / Carrier furnace codes

Carrier 59SU5B single-stage Ultra Low NOx Furnace Codes

Applies to: Carrier 59SU5B single-stage Ultra Low NOx (condensing, 35 in. tall: 59SU5B040M17, 59SU5B060M17, 59SU5B080M21, 59SU5B100M21; also PG95MSUA). Three-digit display on the control (major.minor), plus the Status Code LED seen through the sight glass on the blower door.

The older 59SU5A uses two-digit codes and has its own chart. Payne's PG95MSUA manual prints the identical service label (IM-PG95MSUA-04, Fig. 60 p. 48).

CodeMeaningWhat to check
10.1L1 polarity fault: incoming 115 V polarity reversed (LED flashes rapidly).Check line voltage (115 V) polarity at each junction. If units are twinned, check low-voltage (24 V) transformer phasing.
12.1W on, or burner thermal switch (BTS) open, at power-up or within 5 minutes.Normal: the blower runs 90 seconds if powered up during a heat call or when R-W opens during the blower on-delay. If the BTS is also open, the inducer runs too.
13.1Limit lockout: a switch opened in the limit circuit.Auto-resets after 3 hours. Check for a dirty filter or restricted ducts, a blower motor not working, and a defective switch or connections. How to fix →
14.1Ignition lockout after 4 consecutive ignition tries.Auto-resets after 3 hours. See 34.1. Check correct manifold pressure and gas firing rate, gas inlet pressure fluctuations and proper pressure transducer operation. See the 34 codes. How to fix →
14.2Flame lost 3 times after 70 seconds of heating (after the heating blower on-delay).Auto-resets after 3 hours. See 34.3. Check correct manifold pressure and gas firing rate, gas inlet pressure fluctuations and proper pressure transducer operation. See the 34 codes. How to fix →
14.3Flame lost 7 times during one heat call, or three 34.4 faults during a heat call.See 34.2 to 34.4. Check correct manifold pressure and gas firing rate, gas inlet pressure fluctuations and proper pressure transducer operation. See the 34 codes. How to fix →
14.4Lockout: 7 loss-of-pressure events during a heat call.See 31.4/31.5 for pressure checks. How to fix →
21.1Gas heating lockout: 24 VAC sensed on the gas valve when it shouldn't be.Turn off power and wait 5 minutes to retry. Check for a stuck-closed gas valve relay on the control and a miswire or short on the gas valve wire.
22.1Abnormal (false) flame: flame proved while the gas valve is off.The inducer runs until the fault clears. Check for a stuck-open or leaky gas valve. How to fix →
23.3Over pressure at start-up: transducer output above 0.65 V DC (about 0.15 in.) at the start of the heat sequence.The control delays ignition until the signal returns to range (about 0.50 V DC at 0 in. w.c.). Check vent sizing, obstructed pressure tubing, a defective transducer or its wiring, and excessive wind. How to fix →
24.1Fuse fault: secondary voltage fuse open.Look for a short in the 24 V wiring, including thermostat leads. Disconnect the thermostat leads to isolate it. How to fix →
25.1No program in the control; no heating.If the program in the control is missing, not recognized or corrupted, reprogram the control with the program number on the rating plate. Replace the control if the problem remains.
25.2Corrupted program file; no heating.Reprogram the control with the service app or a super plug (supplied separately). If the program in the control is missing, not recognized or corrupted, reprogram the control with the program number on the rating plate. Replace the control if the problem remains.
25.3Twinned units aren't identical (program numbers don't match).Make sure both furnaces are identical (same program number) when twinning. The main unit won't heat.
25.4Main program invalid; running on the backup program.The control still runs normally. Reprogram it to correct the problem.
25.5Installer settings corrupted.Reselect the installer settings or reprogram the control. It runs on default installer settings meanwhile.
25.6Wrong program for this control; no heating.Reprogram the control so the program matches the control used.
26.1Lockout: burner thermal switch (BTS) open; power reset only.If the switch is open during a heat call, a permanent lockout occurs; cycle power to reset. Check for a blocked burner inlet or burner mesh, a power loss during heating that opened the BTS, and correct manifold pressure and firing rate.
27.1Program in the super plug missing, not recognized or corrupted.Remove the super plug and retry. If code 27 remains, try a different super plug. If that fails, replace the control.
27.2Program in the super plug missing, not recognized or corrupted.Remove the super plug and retry. If code 27 remains, try a different super plug. If that fails, replace the control.
27.3Program in the super plug missing, not recognized or corrupted.Remove the super plug and retry. If code 27 remains, try a different super plug. If that fails, replace the control.
31.4Loss of pressure before the blower comes on.The pressure transducer doesn't sense target pressure, or pressure is out of range for the operating stage. Check vent sizing, low inducer voltage (115 V), inadequate combustion air, disconnected or obstructed pressure tubing, a defective inducer motor, a defective pressure transducer, excessive wind and a restricted vent. How to fix →
31.5Loss of pressure after the blower comes on.The pressure transducer doesn't sense target pressure, or pressure is out of range for the operating stage. Check vent sizing, low inducer voltage (115 V), inadequate combustion air, disconnected or obstructed pressure tubing, a defective inducer motor, a defective pressure transducer, excessive wind and a restricted vent. How to fix →
34.1Ignition proving failure: no adequate flame sense during trial for ignition, four tries.Check for oxide on the flame sensor (clean with fine steel wool), flame current (0.5 µA DC minimum, 4.0-6.0 nominal), a defective or turned-off gas valve, low inlet gas pressure, control ground continuity, the manual shutoff valve, the green/yellow wire connected to the back of the burner box, a grounded flame sensor or one touching the casing, and poor flame carryover or rough ignition. To narrow it down, remove R and run the component test: the inducer starts and after 10 seconds the igniter output is on for 15 seconds. With the igniter unplugged at PL8, no 115 V between PL8-1 and NEUTRAL-L2 means replace the control; then check the igniter harness and igniter for 40-70 ohms. How to fix →
34.2Flame lost after successful ignition, before the heating blower on-delay.Check for oxide on the flame sensor (clean with fine steel wool), flame current (0.5 µA DC minimum, 4.0-6.0 nominal), a defective or turned-off gas valve, low inlet gas pressure, control ground continuity, the manual shutoff valve, the green/yellow wire connected to the back of the burner box, a grounded flame sensor or one touching the casing, and poor flame carryover or rough ignition. How to fix →
34.3Flame lost after successful ignition, after the heating blower on-delay.Check for oxide on the flame sensor (clean with fine steel wool), flame current (0.5 µA DC minimum, 4.0-6.0 nominal), a defective or turned-off gas valve, low inlet gas pressure, control ground continuity, the manual shutoff valve, the green/yellow wire connected to the back of the burner box, a grounded flame sensor or one touching the casing, and poor flame carryover or rough ignition. How to fix →
34.4Flame lost while running at reduced inducer pressure after a previous 34.3 fault.Check for oxide on the flame sensor (clean with fine steel wool), flame current (0.5 µA DC minimum, 4.0-6.0 nominal), a defective or turned-off gas valve, low inlet gas pressure, control ground continuity, the manual shutoff valve, the green/yellow wire connected to the back of the burner box, a grounded flame sensor or one touching the casing, and poor flame carryover or rough ignition. How to fix →
42.1No inducer RPM feedback at start-up or before ignition proved.Check vent sizing, restricted combustion air, a failed inducer motor, loose or bad motor wiring, and a frozen or blocked drain. How to fix →
42.2No inducer RPM feedback after ignition proved (signal lost for 5 seconds).Check vent sizing, restricted combustion air, a failed inducer motor, loose or bad motor wiring, and a frozen or blocked drain. How to fix →
42.3Inducer RPM limit exceeded (limit is model specific).Check vent sizing, restricted combustion air, a failed inducer motor, loose or bad motor wiring, and a frozen or blocked drain. How to fix →
45.1Control failure: flame circuit fault, memory mismatch or sequence error.Cycle power. If code 45 repeats, replace the control.
45.2Control failure: gas valve relay won't close.Cycle power. If code 45 repeats, replace the control.
45.3Control failure: EEPROM memory issue.Cycle power. If code 45 repeats, replace the control.
46.1Momentary loss of power.Heating stops and restarts once the power fluctuation clears.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Carrier 59SU5B Installation, Start-up, Operating and Service Maintenance Instructions 59SU5B-03SI (7/26), service label Fig. 60 p. 48 (read at 400 dpi), troubleshooting guide Fig. 69 pp. 62-64. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.

Related

Other brands