Bryant 926SA Furnace Codes

Applies to: Bryant 926SA (single-stage condensing, multi-speed ECM, multipoise). LED on the furnace control, two-digit status codes.

CodeMeaningWhat to check
11No previous code.Stored codes are erased automatically after 72 hours or when cleared (see above). After the component test, 11 means no errors were detected; check the hot surface igniter, inducer and blower motor visually.
12Blower on after power up (115 VAC or 24 VAC).The blower runs 90 seconds if the unit is powered up during a call for heat (R-W closed) or R-W opens during the blower on-delay.
13Limit circuit lockout: a limit or flame rollout switch open longer than 3 minutes.Auto-resets after 3 hours. See 33. How to fix →
14Ignition lockout.Auto-resets after 3 hours. See 34. How to fix →
21Gas heating lockout (does NOT auto reset).Mis-wired gas valve, or a defective control (valve relay).
22Abnormal flame-proving signal: flame is proved while the gas valve is de-energized.The inducer runs until the fault clears. Check for a leaky or stuck-open gas valve.
23Pressure switch did not open.Obstructed pressure tubing, or a pressure switch stuck closed. How to fix →
24Secondary voltage fuse is open.Short circuit in the 24 VAC wiring. How to fix →
25Model selection or setup error: model plug (PL4) missing or wrong, or setup switch SW1-1 or SW1-6 set wrong.If the code flashes only 4 times at power-up, the control is using the model selection stored in memory. Check for a thermostat call with SW1-1 ON or with SW1-6 ON, SW1-1 and SW1-6 both ON, or two different furnace models twinned. If it flashes continuously, check the rating plate for the model plug number and resistance values.
31HPS pressure switch did not close or reopened.If the HPS stays open one minute after the gas valve closes (after three successive trials), the control locks out for 3 hours before retrying. If it opens during the blower on-delay, the blower runs for the selected off-delay. Check for excessive wind, a restricted vent, a defective inducer motor or low inducer voltage (115 VAC), low inlet gas pressure (if an LGPS is used), a defective pressure switch, inadequate combustion air, vent sizing, disconnected or obstructed pressure tubing, and restricted or blocked condensate drainage. How to fix →
32LPS pressure switch did not close or reopened.If the LPS is open longer than five minutes, the inducer shuts off for 15 minutes before retrying. Troubleshoot as code 31. How to fix →
33Limit circuit fault: a limit or flame rollout switch is open.The blower runs 4 minutes or until the switch closes, whichever is longer. Open more than 3 minutes changes to lockout 13; open less than 3 minutes, 33 keeps flashing until the blower shuts off. The flame rollout switch needs a manual reset. Check for a dirty filter or restricted ducts, vent sizing, a restricted vent, a loose blower wheel, excessive wind, a defective blower motor, the switch or its connections, and inadequate combustion air (flame rollout switch open). How to fix →
34Ignition proving fault: the control tries three more times before lockout 14.If the flame signal is lost during the blower on-delay, the blower runs for the selected off-delay. Check for oxide on the flame sensor (clean with fine steel wool), the manual shut-off valve, control ground continuity, flame current (0.5 microamps DC minimum, 4.0-6.0 nominal), a defective or turned-off gas valve, low inlet gas pressure, poor flame carryover or rough ignition, a defective hot surface igniter, and a grounded flame sensor. The green/yellow wire must be connected to the furnace sheet metal. How to fix →
45Control circuitry lockout: gas valve relay contact stuck open, flame sense circuit failure or software check error.Auto-resets after 1 hour. Reset power to clear the lockout; replace the control if the code repeats.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Bryant 926SA Installation, Start-up, Operating, Service and Maintenance Instructions II926SA-01, Fig. 66 Service Label Information p. 59 (read at 450 dpi). The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.