Carrier 58SU0B Furnace Codes

Applies to: Carrier 58SU0B (80% single-stage, ECM blower, Ultra Low NOx, 3-digit display). 3-digit LCD display on the furnace control, plus the status LED seen through the door.

The 58SU0B service label lists the same codes and descriptions as the ICP N80MSU label (ICP builds furnaces for Carrier), so the checks here are from the N80MSU manual. The older 58SU0A uses two-digit codes and has its own chart.

CodeMeaningWhat to check
10.1L1 polarity fault (LED flashes rapidly).Line voltage polarity reversed at the furnace.
12.1W on at power-up or within 5 minutes.Thermostat and W wiring.
13.1Limit lockout: a switch opened in the limit circuit. How to fix →
14.1Ignition lockout after 4 consecutive ignition tries. How to fix →
14.2Flame lost 3 times after 70 seconds of heating. How to fix →
14.37 loss-of-flame events during a heat request, or three 34.4 faults during a heat request. How to fix →
14.4Lockout: 7 loss-of-pressure events during a heat request. How to fix →
21.124 VAC sensed on the gas valve when it shouldn't be.
22.1False flame.
23.3Pressure detected over 0.15 in. w.c. (about 0.65 V DC signal to ground; 0 in. = about 0.500 V DC).The transducer reads pressure when it shouldn't. Check the pressure tubing and the transducer. How to fix →
24.1Fuse fault.Find the short in the 24 V wiring before replacing the fuse. How to fix →
25.1No program information in the micro. No heating operation.Reprogram the control with the correct program number from the rating plate; replace the control if the problem remains.
25.2Corrupted program file. No heating operation.Reprogram the control using the service app or a super plug (supplied separately).
25.3Twinned units are not identical (program numbers don't match). The main unit will not heat.Twinned furnaces must be identical, with the same program number.
25.4Main program invalid; using the backup program. The control still operates normally.Reprogram the control to correct it.
25.5Installer settings corrupted. The control runs on default installer settings.Reselect the installer settings or reprogram the control.
25.6Wrong program for the control. No heating operation.Reprogram the control so the program matches the control used.
26.1Lockout: BTS (burner thermal switch) open. Power reset only.Find out why the burner area overheated before resetting power. How to fix →
27.1–27.3Program in the super plug missing, not recognized or corrupted.Remove the super plug and retry. If code 27 remains, try a different super plug. If it still fails, replace the control.
31.4Loss of pressure before the blower comes on. How to fix →
31.5Loss of pressure after the blower comes on. How to fix →
34.1Ignition fault during four consecutive ignition trials. How to fix →
34.2Flame lost after successful ignition (flame proven), before the heating blower on-delay. How to fix →
34.3Flame lost after successful ignition (flame proven), after the heating blower on-delay. How to fix →
34.4Flame lost while operating at reduced inducer pressure after a previous 34.3 fault. How to fix →
42.1No inducer RPM feedback at start-up or before ignition is proved. How to fix →
42.2No inducer RPM feedback after ignition is proved. How to fix →
42.3Exceeding the inducer RPM limit (model specific). How to fix →
45.1Control failure: flame circuit fault, memory mismatch or sequence error.Cycle power. If code 45 repeats, replace the control.
45.2Control failure: gas valve relay will not close.Cycle power. If code 45 repeats, replace the control.
45.3Control failure: EEPROM memory issue.Cycle power. If code 45 repeats, replace the control.
46.1Momentary loss of power.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Carrier 58SU0B Installation, Start-up, Operating and Service and Maintenance Instructions 58SU0B-03SI, Fig. 35 Service Label p. 24 (read at 400 dpi); checks from ICP N80MSU-03SI Table 11 p. 22. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.