Goodman / Amana GM9C96 / GC9C96 Furnace Codes

Applies to: Goodman / Amana GM9C96 / GC9C96 (two-stage, nine-speed ECM: GM9C96, GC9C96, Amana AM9C96, AC9C96). Three-character seven-segment display on the integrated control.

CodeMeaningWhat to check
IdLNormal operation.None.
NoneNo display: no 115 V to the furnace or no 24 V to the control, blown fuse or tripped breaker, or a dead control.Restore power, correct whatever opened the fuse and replace it, or replace the control. How to fix →
EE0Lockout after too many ignition retries (3 total): failure to establish flame or loss of flame after it was established.Gas interruption, igniter (replace or realign), flame sense signal (clean a coated or oxidized sensor), flue piping blockage, length, elbows and termination, induced draft blower performance. How to fix →
EE1Low stage pressure switch closed at the start of the heating cycle.Low stage pressure switch contacts sticking, or a short in the switch wiring. Replace the switch or repair the short. How to fix →
EE2Low stage pressure switch not closed; inducer runs continuously, no furnace operation.Pressure switch hose blocked, pinched or misconnected; blocked flue or inlet pipe, blocked drain system or weak inducer; wrong setpoint or bad switch contacts; loose wiring. How to fix →
EE3Primary limit open; circulator blower runs continuously, no furnace operation.Not enough air over the heat exchanger: blocked filters, restrictive ductwork, wrong blower speed or failed blower motor; loose wiring in the high limit circuit. How to fix →
EE4Flame sensed with no call for heat; inducer and blower run continuously.Short to ground in the flame sense circuit, or a lingering burner flame from a slow-closing gas valve.
EE5Open fuse; no furnace operation.Find and fix the short in the low voltage wiring, then replace the fuse. How to fix →
EE6Low flame sense microamp signal (furnace still runs).Coated or oxidized sensor, sensor out of position in the flame, or lazy flame from wrong gas pressure or combustion air. Clean the sensor, check alignment, compare gas pressure with the rating plate. How to fix →
EELIgniter circuit problem.Improperly connected or shorted igniter, poor unit ground, or the igniter relay on the control. Check the wiring and ground; check igniter output from the control and replace the control if needed. How to fix →
EE8High stage pressure switch closed at the start of the heating cycle; runs normally on low stage only.High stage pressure switch contacts sticking, or a short in the switch wiring. How to fix →
EE9High stage pressure switch not closed; runs normally on low stage only, inducer running.Pressure switch hose, flue and inlet piping (blockage, length, elbows, termination), inducer performance, loose wiring. How to fix →
EEA115 V polarity reversed, or poor unit ground.Correct the polarity and verify the ground.
EEbGas valve not energized when it should be (external gas valve error).Wiring in the gas valve circuit; replace the control if the wiring is good.
EECGas valve energized when it should not be (internal gas valve error).Wiring in the gas valve circuit; replace the control if the wiring is good.
E10Grounding fault or poor neutral connection.Neutral connection to the furnace and continuity to the ground source.
E11Open rollout switch.Gas pressure, burner alignment and burner restriction. How to fix →
EEnIgniter open.Igniter wiring; replace a damaged igniter. How to fix →
EEJInducer relay error.Replace the control.
EEHTwin error: twinning not working.Twin wiring; replace the control if the wiring is good.
EEEInternal fault or IRQ loss in the control.Replace the control.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Goodman GM9C96/GC9C96 & Amana AM9C96/AC9C96 Service and Troubleshooting manual RS6612020 Rev. 2 (2026), 2 Stage Troubleshooting Codes pp. 28-29. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.