Home / Charts / York furnace codes

York TM9T Furnace Codes

Applies to: York TM9T (96% AFUE two-stage PSC, multi-position). LED on the furnace control board that flashes red, green or amber.

Johnson Controls also sells furnaces under the Coleman and Luxaire names. Codes match only when the control board is the same, so check the label inside the blower door.

CodeMeaningWhat to check
Slow greenNormal operation, no thermostat calls.
Slow amberNormal operation with call for heat.
LED offLED does not flash at all.Check power to the board and for a blown fuse on the board (3-amp ATO automotive fuse). If power and fuse are good, the control board may need to be replaced. How to fix →
Steady on, any colorControl failure.Turn power off and back on. If the code returns, replace the control board; it is not field-repairable.
Continuous red flashTwinning error: incorrect 24 V phasing or no power to the twinned unit.Check the twinning wiring. Confirm both twinned units have power. How to fix →
Continuous amber flashFlame sense current is below 1.5 microamps.Clean the flame sensor and check gas flow. Current should be above 1.5 microamps at the flame current test pad. How to fix →
1 redFlame sensed when there was not a call for heat.The control runs the inducer and supply blower. Leaking or slow-closing gas valve. How to fix →
2 redPressure switch closed when it should be open.The control checks the switch contacts are open at the start of each heat cycle and won't start ignition until they are. Faulty pressure switch or miswiring. How to fix →
3 redPressure switch contacts open when they should be closed.Faulty inducer, blocked vent pipe, broken pressure switch hose, disconnected switch or inducer wires, faulty pressure switch. How to fix →
4 redMain limit switch open.The control runs the supply blower and inducer. Dirty filter, undersized ducts, wrong blower speed setting, incorrect firing rate, loose limit wiring or faulty blower motor. Five limit trips in one call for heat also gives 4 red and a one-hour soft lockout. Open more than five minutes becomes 11 red; more than fifteen minutes becomes 5 red. How to fix →
5 redLimit circuit open more than fifteen minutes, usually a manual-reset rollout switch.Check combustion air, inducer operation, and for primary heat exchanger failure or a burner problem. Hard lockout: cycle power after the problem is corrected. How to fix →
6 redPressure switch opened four times during the call for heat.Faulty inducer, blocked vent pipe or faulty pressure switch. Locks out for one hour, then restarts. How to fix →
7 redFlame not established during three trials for ignition.Gas valve switch ON, low or no gas pressure, faulty gas valve, dirty or faulty flame sensor, faulty hot surface ignitor, loose wires or a burner problem. Locks out for one hour, then restarts. How to fix →
8 redFlame lost five times (four recycles) during the heating cycle.Low gas pressure, dirty or faulty flame sensor or faulty gas valve. Locks out for one hour, then restarts. How to fix →
9 redReversed line voltage polarity, grounding problem or reversed low voltage transformer wires.Heating and cooling are both affected. Check polarity at the furnace and branch, furnace grounding, and that the flame probe isn't shorted to the chassis. The furnace won't start ignition until it's corrected.
10 redGas valve energized with no call for heat.Main blower and inducer run and no ignition sequence starts while this lasts. Check the gas valve and its wiring.
11 redLimit circuit open more than five minutes and less than fifteen.Usually a failed blower motor or blower wheel. Hard lockout: cycle power after the problem is corrected. How to fix →
13 redVent, intake or termination problem (listed on the wiring diagram's fault code table only).The manual's diagnostics text doesn't describe this code. Check the vent, intake and termination, and the second-stage pressure switch (PS2) and its wiring. How to fix →
4 amberY signal from the thermostat without a G signal.The furnace still heats and cools normally; the code flags a wiring problem. Make sure the G wire from the thermostat is connected. How to fix →

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: York TM9T Installation Manual, 1083286-UIM-A-0114, Furnace Control Diagnostics p. 37, Fault Code Storage and Retrieval p. 38, wiring diagram fault code table p. 39. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.

Related

Other brands