Lennox Elite EL296UHE Furnace Codes

Applies to: Lennox Elite EL296UHE (96% two-stage, constant torque: EL296UH045XE36B, EL296UH070XE36B, EL296UH090XE48C, EL296UH110XE60C, EL296UH135XE60D; also Elite EL280DFE downflow: EL280DF070E36A, EL280DF090E48B). Seven-segment diagnostic LED and push button on the integrated control.

Lennox's EL280DFE service literature (1902, pp. 10-12, Table 9) prints the same table and flame values. The newer EL297UHEK uses the same style of control with a few more codes (E000, E131, E228 and the A2L refrigerant detection codes); see that chart.

CodeMeaningWhat to check
E110Low line voltage (below the nameplate rating).Check and correct line voltage. Clears 5 seconds after recovery.
E111Line voltage polarity reversed.Reverse the line power wiring. Resumes 5 seconds after recovery.
E112Ground not detected; system shuts down.Provide a proper earth ground. Resumes 5 seconds after recovery.
E113High line voltage (above the nameplate rating).Provide voltage within range. Resumes 5 seconds after recovery.
E114Line voltage frequency out of range.No 60 Hz power: check voltage and line frequency. Resumes 5 seconds after recovery.
E115Low 24 V (the control restarts if it recovers).24 V range is 18 to 30 V. Check and correct; look for power-robbing equipment on the system; a larger VA transformer may be needed. Clears after recovery.
E117Poor ground detected (warning only).Provide proper grounding for the unit. Clears 30 seconds after recovery.
E125Control failed self-check or hardware (flame sense circuit faults, pin shorts, etc.); control not communicating.Cycle power. Replace the control if the problem persists and prevents service. Critical alert; clears 300 seconds after recovery.
E200Hard lockout: rollout circuit open or previously open.Correct the cause of the rollout trip, or replace the rollout switch. Test operation. Clears after recovery. How to fix →
E204Gas valve miswired.Check gas valve operation and wiring. Clears when repaired.
E205Gas valve control relay contact shorted.Check wiring on the control and gas valve. If the wiring is correct, replace the control.
E206Gas valve second-stage relay failure.The furnace runs on first stage for the rest of the heat call. If it still can't run second stage, replace the control.
E207Hot surface igniter sensed open.Measure igniter resistance; replace if open or outside the range in the installation instructions. How to fix →
E223Low pressure switch failed open.Check pressure (inches w.c.) of the switch closing on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. Resumes after the fault clears. How to fix →
E224Low pressure switch failed closed.Lennox prints the same action as E223: check the low pressure switch closing on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. How to fix →
E225High pressure switch failed open.Check pressure (inches w.c.) of the switch closing on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. Resumes after the fault clears. How to fix →
E226High pressure switch failed closed.Check the high pressure switch closing on the heat call, measure operating pressure, inspect the vent and inducer. How to fix →
E227Low pressure switch open during trial for ignition or run mode.Check pressure (inches w.c.) of the switch closing on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. Resumes after the fault clears. How to fix →
E229Ignition on high fire (information only).Shown when 1) the low pressure switch fails to close, so the furnace switches to high inducer speed to close both switches and lights on high fire, or 2) continuous fan is on, so it lights on high fire for 60 seconds to warm the heat exchanger. No action needed.
E240Low flame current, run mode.Check flame microamps with the control diagnostics (see Table 9 above); clean or replace the sensor; measure neutral to ground for a good unit ground. Clears after the heat call completes. How to fix →
E241Flame sensed out of sequence; flame still present.Shut off the gas. Check the gas valve for a leak and replace it if needed. Clears when the fault recovers.
E250Limit switch circuit open.Check firing rate, blockage in the heater and airflow. If the limit doesn't close within 3 minutes, the unit goes into a 1-hour soft lockout. How to fix →
E270Soft lockout: too many retries, no flame current sensed.Check gas flow, that the igniter lights the burner, and flame sensor current. Clears when a heat call finishes successfully. How to fix →
E271Soft lockout: too many retries; last retry failed when the pressure switch opened.Check pressure (inches w.c.) of the switch closing on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. Resumes after the fault clears. How to fix →
E272Soft lockout: too many recycles; last recycle due to the pressure switch opening.Check whether the low pressure switch is stuck closed, check the high pressure switch closing, measure operating pressure, inspect the vent and inducer. How to fix →
E273Soft lockout: too many recycles; last recycle due to flame failure.Check flame microamps, clean or replace the sensor, measure neutral to ground for a good unit ground. How to fix →
E274Soft lockout: too many recycles; last recycle failed on the limit circuit, or the limit stayed open over 3 minutes.1-hour soft lockout. Check firing rate and airflow; check for blockage. How to fix →
E275Soft lockout: flame sensed out of sequence; flame signal now gone.Shut off the gas and check the gas valve for a leak. 1-hour soft lockout; clears when flame is proven stable.
E290Igniter circuit fault: failed igniter or triggering circuitry.Measure hot surface igniter resistance; replace if open or out of spec. 1-hour soft lockout. How to fix →

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Lennox EL296UHE Unit Information, Service Literature 1246k (revised 08/2023), Integrated Control Diagnostic Modes and Codes (Tables 3-4) pp. 12-14, Table 9 flame signal p. 19. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.