Carrier 58CU0A Furnace Codes

Applies to: Carrier 58CU0A (80% communicating, Ultra Low NOx, 4-way multipoise). LED on the furnace control, two-digit status codes.

CodeMeaningWhat to check
11No previous code.Stored codes are erased automatically after 72 hours. After the component test, 11 means the blower motor tested OK; check the inducer motor and hot surface igniter visually.
12Blower on after power up (115 VAC or 24 VAC).The blower runs 90 seconds if the unit is powered up during a call for heat (R-W/W1 closed) or R-W/W1 opens during the blower on-delay.
13Limit circuit lockout: a limit, draft safeguard, burner thermal switch or blocked vent switch (if used) is open, or 10 successive limit trips occurred during heat.Auto-resets after three hours. Check for a loose blower wheel, a restricted vent, vent sizing, excess wind, a dirty filter or restricted ducts, the switch or its connections, and inadequate combustion air (burner thermal switch open). How to fix →
14Ignition lockout.Auto-resets after three hours. See 34. How to fix →
15Blower motor lockout: the blower failed to reach 250 RPM or to communicate within 30 seconds of being turned on, in two successive heating cycles.Auto-resets after 3 hours. See 41.
21Gas heating lockout (does NOT auto-reset).Mis-wired gas valve, or a defective control (valve relay).
22Abnormal flame-proving signal: flame is proved while the gas valve is de-energized.The inducer runs until the fault clears. Check for a leaky or stuck-open gas valve.
23Pressure above 0.15 in. w.c. at start-up.Check for an obstruction in the pressure tubing or the transducer vent holes, a defective transducer, and the transducer wiring. How to fix →
24Secondary voltage fuse is open.Short circuit in the 24 VAC wiring. How to fix →
25Invalid model selection or setup error: model plug missing or wrong, or setup switch SW1-1 or SW1-6 set wrong.If the code flashes 4 times at power-up, the control is using the model selection stored in memory. Check for a thermostat call with SW1-1, SW1-6 or both ON.
31Pressure transducer doesn't sense target pressure, or pressure is out of range.Check for excessive wind, vent sizing, a restricted vent, a defective inducer motor or low inducer voltage (115 VAC), inadequate combustion air, a defective pressure transducer, low inlet gas pressure (if an LGPS is used), and disconnected or obstructed pressure tubing. How to fix →
34Ignition proving failure: the control tries three more times before lockout 14.If the flame signal is lost during the blower on-delay, the blower runs for the selected off-delay. Check for oxide on the flame sensor (clean with fine steel wool), flame current (0.5 microamps DC minimum, 4.0-6.0 nominal), the manual shut-off valve, low inlet gas pressure, control ground continuity, a defective or turned-off gas valve, a flame sensor that is grounded or touching the casing, and poor flame carryover or rough ignition. The green/yellow wire must be connected to the furnace sheet metal. How to fix →
41Blower motor fault: the blower fails to reach 250 RPM or to communicate within 30 seconds of being turned on, or drops below 250 RPM for more than 10 seconds or stops communicating for more than 20 seconds during steady operation.After the component test: check the blower, wiring and furnace control.
42Inducer motor fault: no RPM pulses within 20 seconds of a heat request, inducer outside its valid range, or RPM signal lost for 5 seconds.Check vent sizing, a restricted combustion air supply, a failed inducer motor, and loose or bad motor wiring. After the component test, also check the inducer, wiring, furnace control and tubing for poor connections.
45Control circuitry lockout: gas valve relay stuck open, flame sense circuit failure or software check error.Auto-resets after one hour. Reset power to clear the lockout; replace the control if the code repeats.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Carrier 58CU0A Installation, Start-Up, Operating and Service and Maintenance Instructions 58CU0A-03SI, Fig. 39 Service Label (345374-201 Rev. A) p. 23 (read at 500 dpi). The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.