Lennox Merit ML196UHE / ML196DFE / ML193UHE Furnace Codes

Applies to: Lennox Merit ML196UHE / ML196DFE / ML193UHE (single-stage, red LED controls 103217-03 and 107163-01: ML196UH030XE36B, ML196UH045XE36B, ML196UH070XE36B, ML196UH070XE48B, ML196UH090XE36C, ML196UH090XE48C, ML196UH090XE60C, ML196UH110XE60C, ML196UH135XE60D, ML196DF045XE36B, ML196DF070XE48B, ML196DF090XE48C, ML196DF110XE60C, ML193UH030XE36B, ML193UH045XE36B, ML193UH070XE36B, ML193UH090XE36C, ML193UH090XE48C, ML193UH110XE48C, ML193UH110XE60C; also ML180UHE and ML180DFE: ML180UH045E36A, ML180UH045XE36A, ML180UH070E36A, ML180UH070XE36A, ML180UH070E36B, ML180UH070XE36B, ML180UH090E48B, ML180UH090XE48B, ML180UH090E60C, ML180UH110E60C, ML180UH110XE60C, ML180UH135E60D, ML180DF045E36A, ML180DF070E36A, ML180DF070E36B, ML180DF090E48B, ML180DF110E60C; ML180UHV: ML180UH030V36A, ML180UH045V36A, ML180UH070V36A, ML180UH070V36B, ML180UH070V48B, ML180UH090V48B, ML180UH110V60C; Elite EL195UH (2011): EL195UH045P24B, EL195UH045P36B, EL195UH070P36B, EL195UH070P48B, EL195UH090P36C, EL195UH090P48C, EL195UH090P60C, EL195UH110P48C, EL195UH110P60C, EL195UH135P60D). Red LED and recall button on the ignition control (103217-03 or 107163-01).

Lennox's service literature for the ML196UHE (1911), ML196DFE (1910), ML193UHE (1905), ML180UHE (1120) and ML180DFE (1121) lists the same two ignition controls and flash codes, with the same igniter, flame and timing figures. The ML180UHV service literature (1909, Table 4 p. 14) prints the same flash codes without naming the control; on it, error flashes are 1/3 second on, 1/3 second off, and only the last 5 codes are stored. The 2011 EL195UH installation instructions (506596-01, p. 49) print the same 1-13 list, with 6 flashes as igniter circuit failure, not available on that control. The newer A2L-ready ML196UHEK (model numbers ending in K) uses a seven-segment display and E-codes instead; see that chart.

CodeMeaningWhat to check
OffNo power to the control, or board fault detected.Confirm 120 V and 24 V at the control. The furnace needs 120 V +/-10% (108-132 V) and 60 Hz +/-5%.
OnBoard fault detected (107163-01 control).Lennox lists this only as a board fault detected. Check power to the control first.
Slow heartbeatNormal operation: idle, continuous fan or cooling.None.
Fast heartbeatCall for heat / burner operation (shown as a continuous rapid flash on the 103217-03).None.
1 flashReverse line voltage polarity (107163-01: or phasing of the 120 V power).These furnaces are polarity sensitive. Make sure hot and neutral are wired correctly and the furnace is properly grounded. How to fix →
2 flashesImproper earth ground.The control needs both correct polarity and a proper ground. Check the ground at the furnace and the panel. How to fix →
3 flashesBurner failed to light, or lost flame during a heat call.Check gas supply, that the igniter glows (Lennox: 39 to 70 ohms is a good igniter; it should get 102-132 VAC), and the flame sensor. How to fix →
4 flashesLow flame signal: check the flame sensor.Clean the sensor (Lennox: steel wool only) and measure flame current: 1.5 µA or more is normal, 0.5-1.4 low, 0.4 or less drops out. Check polarity and ground too. How to fix →
5 flashesWatchguard: burner failed to light; maximum retries or recycles exceeded (1-hour lockout).After five ignition trials the control waits 60 minutes, then tries again. Lennox says this lockout is usually due to low gas line pressure; check supply and manifold pressure, the igniter and the flame sensor. How to fix →
6 flashesNot used.Lennox lists 6 flashes as not used on these controls. Recount the flashes.
7 flashesPrimary or secondary limit open, or Watchguard: limit open longer than 3 minutes.The limit opens on excess heat; the control runs the blower and shuts the gas valve, and the limit resets itself when the temperature drops. Check the filter, ductwork and blower, and that temperature rise is within the nameplate range. How to fix →
8 flashesRollout switch open.The rollout switches are manual reset. A trip points to a blockage in the combustion passages; an obstructed vent pipe or termination can cause it. Find the cause before resetting. How to fix →
9 flashesPressure switch failed to close, or opened during a heat call (inducer on).If the switch isn't proven within 2-1/2 minutes, the control goes into a 5-minute Watchguard reset period. Check exhaust and intake connections for tightness and blockage, and the termination. How to fix →
10 flashesWatchguard: pressure switch opened 5 times during one heat call.Check exhaust and intake connections for tightness and blockage, and the termination. How to fix →
11 flashesPressure switch stuck closed before the inducer started.The control won't start a heat cycle with the switch already closed (bypassed). Check for a jumpered or stuck switch. How to fix →
12 flashesFlame sensed without the gas valve energized.Shut off the gas and check the gas valve for a leak. (Lennox's newer controls give this action for the same fault, E241.)
13 flashesLow line voltage.The furnace needs 120 V +/-10% (108-132 V). Check supply voltage under load.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Lennox ML196UHE Unit Information, Service Literature 1911 (revised 04/2024), ignition control 103217-03 and 107163-01 flash code tables pp. 10-12, ignition sequence p. 11, flame signal and igniter pp. 14-15; same controls in ML196DFE (1910) and ML193UHE (1905); Watchguard and generator voltage notes from ML196UHE installation instructions 507966-04. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.