Trane / American Standard A801X060AM3S Furnace Codes

Applies to: Trane / American Standard A801X060AM3S (80% single-stage, 2024 installation manual). Digital LED display on the integrated control module.

This chart is for the A801X060AM3S, whose 2024 manual uses two-character codes (E1, FE, Pr...). Other A801X models with the integrated furnace control use E2.1-style codes; check the code list on the unit's wiring diagram.

CodeMeaningWhat to check
FEGas valve relay stuck closed.Verify the gas valve is operating and shutting down properly; the burner flame should go out promptly at the end of the cycle. Check orifices and gas pressure. How to fix →
E1Shorted pressure switch.Pressure switch stuck closed. Check switch function and verify the inducer is turning off. How to fix →
E2Open pressure switch.Check pressure switch function and tubing. Verify the inducer is turning on and pulling enough vacuum to close the switch. How to fix →
E4Open pressure switch, locked.If the pressure switch cycles 15 times (open, closed) during one call for heat, the control locks out. Check the switch for fluttering, inconsistent closure or poor vacuum. How to fix →
E5Open thermal limit or rollout switch.Verify continuity through the rollout switch, primary limit and reverse flow limit circuit. How to fix →
E6Open thermal limit or rollout switch, after 5 times.Verify continuity through the rollout switch, primary limit and reverse flow limit circuit. Find out why it keeps opening before resetting. How to fix →
E7Ignition failure, locked.Failure to sense flame is often caused by carbon deposits on the flame sensor, a disconnected or shorted sensor lead, or a poorly grounded furnace. Verify the sensor isn't touching the burner and sits where it can sense flame. How to fix →
E8Flame loss, locked.Check the same items as for E7, and verify the gas valve isn't dropping out so the flame is established and then lost. How to fix →
FLFlame low.Low flame sense current, often from carbon on the sensor, a poorly grounded furnace or a misaligned sensor. Clean the sensor with emery cloth and check furnace and control grounding. How to fix →
PrPower reversed.Verify the control and furnace are properly grounded. Check line-voltage polarity and correct it if reversed.
FoFuse open.Low-voltage circuit overcurrent. Find and repair the shorted wiring or component, then replace the fuse. How to fix →
bEBoard error.Replace the electronic control board.
nLSignal error.Check the control signal wiring against the user manual.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Trane Installation Manual, A801X060AM3S*** upflow/horizontal and downflow gas furnaces, 88-A801X004-1B-EN (11/2024), Table 13-1 Troubleshooting Chart. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.