Rheem / Ruud R98V Furnace Codes

Applies to: Rheem / Ruud R98V (98% modulating communicating, upflow). Dual seven-segment display on the integrated furnace control (IFC).

The manual covers the (-)98V series; the first letter of the model number is the brand (R98V Rheem, U98V Ruud). Both the R98VA and R98VB design series use this list. Rheem's downflow/horizontal R97V uses the same codes.

CodeMeaningWhat to check
d1No model data.The furnace won't run in any mode. Usually the model data card is missing or came off the control. Put the original card back in connector P6 on the control and cycle power. A replacement card for the exact furnace model can be ordered from ProStock.
d4No valid model data on model data card.The card is blank, corrupt or missing, but the control still has a valid copy, so the furnace keeps running. Replace it with the original or the correct card. Never use a card from another furnace: wrong blower operation can damage the heat exchanger.
d6Horsepower conflict on model data card.The motor's horsepower doesn't match the card, usually after a wrong replacement motor, card or control. The furnace keeps running. Install the correct motor and/or card.
10One-hour lockout.No gas heat; cooling still works. Shown alternating with the fault that caused it (11, 13, 14, 59, 61 or 93). Fix that fault. After four 61 lockouts in one heat call it becomes a hard lockout that needs a power reset. How to fix →
11Failed ignition.After four failed tries in a row the control goes to one-hour lockout (11 and 10 alternate). Check: flame sensor dirty or poorly connected; gas valve off; igniter connection or position; control. Check manifold pressure during ignition (about 3.5 in. w.c. natural gas, 10 in. w.c. LP). If the first burner lights but the flame doesn't carry over, the burner may need replacing. How to fix →
12Low flame sense.The furnace keeps running, but this can lead to 13 or 11. Clean or replace the flame sensor, check its wiring to the control, and make sure the sensor and furnace are properly grounded. How to fix →
13Flame lost after established.After five losses in a row the control goes to one-hour lockout. Check the flame sensor (clean, wiring, grounding) and for an unstable flame: burner parts installed correctly, seals between burner and blower compartments, combustion door gasket in place and the door sealed. How to fix →
14Flame present with gas valve off.The furnace won't operate. Inducer runs high and blower at maximum heat speed until it clears, then one-hour lockout. Causes: 24 VAC miswired to the gas valve main solenoid, gas valve stuck open, or a faulty control.
22Main limit open.No gas heat; cooling and fan still work. Blower runs at maximum heat speed and inducer on high until the limit closes. Causes: no or low airflow (filters, ductwork, static pressure), faulty limit, wiring, dead blower (see 61), or input too high (check orifices and manifold pressure at high fire). Check temperature rise at high and low fire using test-mode dip switches SW3-13 and SW3-14 and compare with the nameplate. If the limit stays open more than 150 seconds, the control declares a dead blower and shows 10 and 61. How to fix →
23HALC open.No continuity between pins 3 and 5 of connector P1 on the control. As configured, this furnace has a jumper there, not a HALC control, so repair the jumper.
26Line and neutral reversed or poor ground.No heating or cooling. Check line and neutral with a meter (at the furnace and at the disconnect or breaker), and check the ground wire to the cabinet and at the breaker box.
30Open fuse.Nothing runs. A short from 24 VAC to ground or common blew the fuse. Repair the short and replace the fuse. How to fix →
33Over-temperature switch (roll-out) open.Manual reset. Causes: insufficient venting, wiring, or unstable flame. Check the pressure switches aren't welded or bypassed, inducer speed, vent length and obstructions, inducer gaskets, burner seals and door, and the heat exchanger for damage. How to fix →
44Low pressure switch closed, inducer off.Shown during a heat call before pre-purge. Causes: faulty switch, switch bypassed, wiring, or high negative vent pressure without the inducer running. How to fix →
45Low pressure switch open, inducer on high speed.Causes: blocked or wrongly terminated vents, too much vent length or too many elbows, inducer or its relay on the control, wiring, disconnected or damaged hoses, wind gusts, or the switch. Check whether a high-altitude kit is needed. How to fix →
46Low pressure switch open, inducer on low speed.Only after the furnace switches to low fire. Same causes as 45, plus a missing high-altitude kit at high elevation. How to fix →
55High pressure switch closed, inducer off.Causes: faulty switch, switch bypassed, wiring, or high negative vent pressure without the inducer running. How to fix →
57High pressure switch open, inducer on high speed.Once heat is established, the furnace drops to low fire and keeps running if the low pressure switch stays closed. Same causes as 46. How to fix →
58Water circuit open.No continuity between pins 1 and 2 of connector P4 (the two water sensors). Repair damaged wiring or connections, or replace a missing sensor.
59Water sensed.Water in the collector box for at least ten seconds. Clear a blocked condensate drain or trap, repair sensor wiring touching the sheet metal, and put a sensor that was pulled out back in the collector box.
60Blower fault, blower can still run.The blower hit its speed or torque limit, or is running at the temperature limit, because static pressure is too high. Fix the ductwork or filter so static pressure is within published values. How to fix →
61Blower fault, motor cannot run.Nothing runs. Causes: motor thermal trip (restriction or bearings), PFC choke, bad model data (replace the card), motor or choke wiring, blower wheel damaged or loose on the shaft, or a failed motor.
65Mid pressure switch closed, should be open.Check wiring to the mid pressure switch, the switch and the control.
66Blower cutback.An operating indicator, not a fault: the blower is at its rpm or torque limit because static pressure is too high. Not shown in the first three minutes after power-up. Fix the ductwork or filter. How to fix →
67Mid pressure switch open, should be closed.Causes: wind gusts, venting not per the manual, wiring, the switch, or the control.
68No blower communications.Nothing runs. Check motor communication wiring and connectors, line voltage to the PFC choke and motor, the model data card, or a failed motor.
71Inducer fault.Too much or too little current on the inducer circuit. Can appear after a quick power loss (within 30 seconds) during heating: reset power. Otherwise check inducer wiring, the inducer and the control.
77No gas valve feedback signal.The control can't communicate with the gas valve. Check wiring, the gas valve and the control.
93Internal control fault detected.Nothing runs. Causes: 24 VAC or similar voltage on the main gas valve solenoid circuit when it shouldn't be (check for miswiring), or a failed control.
99Remote faults reset performed.Notification that the stored fault codes were reset.

Rheem replacement part numbers

Part060070085100115Codes
Integrated furnace control (IFC) board62-105563-04 (gas code KE) or 62-105563-05 (gas code KL)14, 77, 93
Memory module (model data card) for the IFC47-104778-1847-104778-1947-104778-2047-104778-2147-104778-22d1, d4, d6, 61, 68
Flame sensor62-23543-0811, 12, 13
Spark ignitor62-24141-0511
Gas valve, natural gas60-102787-0414, 77
Pressure switch, high fire42-106242-0442-106242-0642-106242-0442-106242-0442-106242-0455, 57
Pressure switch, mid fire42-106243-0142-106243-0342-106243-0142-106243-0142-106243-0165, 67
Pressure switch, low fire42-106242-0244, 45, 46
Main limit (heat exchanger panel)47-104465-0147-104465-0147-104465-0147-104465-0147-104465-0222
Manual reset limit, burner compartment (3 per furnace)47-104888-0133
Induced draft blower (with gasket)70-104157-0645, 46, 57, 71
Induced draft blower gasket68-104152-01
Water sensor (2 per furnace)47-104184-0158, 59
Transformer46-102856-0230
Blower motor51-102602-0151-102602-0151-102603-0151-102603-0151-102603-0160, 61, 68
Power factor choke (PFC)NoneNone46-24256-0546-24256-0546-24256-0561, 68
Blower wheelPD703027PD703027PD703028PD703028PD70302961
Door switch42-22692-09
High altitude kitRXGY-F43RXGY-F44RXGY-F45RXGY-F46RXGY-F4746, 57
Outdoor sensor kitRXGY-J02

Parts source: Rheem Parts List 92-42800-R98V-USA (13-November-2019), Electric, Blower, Heat Exchanger and Gas Controls groups, pp. 6-8.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Rheem (-)98V Installation Instructions, 92-24161-159-03, Table 19 Fault Codes, pp. 92-101 (normal operation codes, Table 18, p. 91). The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.