Rheem / Ruud R98V Furnace Codes
The manual covers the (-)98V series; the first letter of the model number is the brand (R98V Rheem, U98V Ruud). Both the R98VA and R98VB design series use this list. Rheem's downflow/horizontal R97V uses the same codes.
| Code | Meaning | What to check |
|---|---|---|
| d1 | No model data. | The furnace won't run in any mode. Usually the model data card is missing or came off the control. Put the original card back in connector P6 on the control and cycle power. A replacement card for the exact furnace model can be ordered from ProStock. |
| d4 | No valid model data on model data card. | The card is blank, corrupt or missing, but the control still has a valid copy, so the furnace keeps running. Replace it with the original or the correct card. Never use a card from another furnace: wrong blower operation can damage the heat exchanger. |
| d6 | Horsepower conflict on model data card. | The motor's horsepower doesn't match the card, usually after a wrong replacement motor, card or control. The furnace keeps running. Install the correct motor and/or card. |
| 10 | One-hour lockout. | No gas heat; cooling still works. Shown alternating with the fault that caused it (11, 13, 14, 59, 61 or 93). Fix that fault. After four 61 lockouts in one heat call it becomes a hard lockout that needs a power reset. How to fix → |
| 11 | Failed ignition. | After four failed tries in a row the control goes to one-hour lockout (11 and 10 alternate). Check: flame sensor dirty or poorly connected; gas valve off; igniter connection or position; control. Check manifold pressure during ignition (about 3.5 in. w.c. natural gas, 10 in. w.c. LP). If the first burner lights but the flame doesn't carry over, the burner may need replacing. How to fix → |
| 12 | Low flame sense. | The furnace keeps running, but this can lead to 13 or 11. Clean or replace the flame sensor, check its wiring to the control, and make sure the sensor and furnace are properly grounded. How to fix → |
| 13 | Flame lost after established. | After five losses in a row the control goes to one-hour lockout. Check the flame sensor (clean, wiring, grounding) and for an unstable flame: burner parts installed correctly, seals between burner and blower compartments, combustion door gasket in place and the door sealed. How to fix → |
| 14 | Flame present with gas valve off. | The furnace won't operate. Inducer runs high and blower at maximum heat speed until it clears, then one-hour lockout. Causes: 24 VAC miswired to the gas valve main solenoid, gas valve stuck open, or a faulty control. |
| 22 | Main limit open. | No gas heat; cooling and fan still work. Blower runs at maximum heat speed and inducer on high until the limit closes. Causes: no or low airflow (filters, ductwork, static pressure), faulty limit, wiring, dead blower (see 61), or input too high (check orifices and manifold pressure at high fire). Check temperature rise at high and low fire using test-mode dip switches SW3-13 and SW3-14 and compare with the nameplate. If the limit stays open more than 150 seconds, the control declares a dead blower and shows 10 and 61. How to fix → |
| 23 | HALC open. | No continuity between pins 3 and 5 of connector P1 on the control. As configured, this furnace has a jumper there, not a HALC control, so repair the jumper. |
| 26 | Line and neutral reversed or poor ground. | No heating or cooling. Check line and neutral with a meter (at the furnace and at the disconnect or breaker), and check the ground wire to the cabinet and at the breaker box. |
| 30 | Open fuse. | Nothing runs. A short from 24 VAC to ground or common blew the fuse. Repair the short and replace the fuse. How to fix → |
| 33 | Over-temperature switch (roll-out) open. | Manual reset. Causes: insufficient venting, wiring, or unstable flame. Check the pressure switches aren't welded or bypassed, inducer speed, vent length and obstructions, inducer gaskets, burner seals and door, and the heat exchanger for damage. How to fix → |
| 44 | Low pressure switch closed, inducer off. | Shown during a heat call before pre-purge. Causes: faulty switch, switch bypassed, wiring, or high negative vent pressure without the inducer running. How to fix → |
| 45 | Low pressure switch open, inducer on high speed. | Causes: blocked or wrongly terminated vents, too much vent length or too many elbows, inducer or its relay on the control, wiring, disconnected or damaged hoses, wind gusts, or the switch. Check whether a high-altitude kit is needed. How to fix → |
| 46 | Low pressure switch open, inducer on low speed. | Only after the furnace switches to low fire. Same causes as 45, plus a missing high-altitude kit at high elevation. How to fix → |
| 55 | High pressure switch closed, inducer off. | Causes: faulty switch, switch bypassed, wiring, or high negative vent pressure without the inducer running. How to fix → |
| 57 | High pressure switch open, inducer on high speed. | Once heat is established, the furnace drops to low fire and keeps running if the low pressure switch stays closed. Same causes as 46. How to fix → |
| 58 | Water circuit open. | No continuity between pins 1 and 2 of connector P4 (the two water sensors). Repair damaged wiring or connections, or replace a missing sensor. |
| 59 | Water sensed. | Water in the collector box for at least ten seconds. Clear a blocked condensate drain or trap, repair sensor wiring touching the sheet metal, and put a sensor that was pulled out back in the collector box. |
| 60 | Blower fault, blower can still run. | The blower hit its speed or torque limit, or is running at the temperature limit, because static pressure is too high. Fix the ductwork or filter so static pressure is within published values. How to fix → |
| 61 | Blower fault, motor cannot run. | Nothing runs. Causes: motor thermal trip (restriction or bearings), PFC choke, bad model data (replace the card), motor or choke wiring, blower wheel damaged or loose on the shaft, or a failed motor. |
| 65 | Mid pressure switch closed, should be open. | Check wiring to the mid pressure switch, the switch and the control. |
| 66 | Blower cutback. | An operating indicator, not a fault: the blower is at its rpm or torque limit because static pressure is too high. Not shown in the first three minutes after power-up. Fix the ductwork or filter. How to fix → |
| 67 | Mid pressure switch open, should be closed. | Causes: wind gusts, venting not per the manual, wiring, the switch, or the control. |
| 68 | No blower communications. | Nothing runs. Check motor communication wiring and connectors, line voltage to the PFC choke and motor, the model data card, or a failed motor. |
| 71 | Inducer fault. | Too much or too little current on the inducer circuit. Can appear after a quick power loss (within 30 seconds) during heating: reset power. Otherwise check inducer wiring, the inducer and the control. |
| 77 | No gas valve feedback signal. | The control can't communicate with the gas valve. Check wiring, the gas valve and the control. |
| 93 | Internal control fault detected. | Nothing runs. Causes: 24 VAC or similar voltage on the main gas valve solenoid circuit when it shouldn't be (check for miswiring), or a failed control. |
| 99 | Remote faults reset performed. | Notification that the stored fault codes were reset. |
Rheem replacement part numbers
| Part | 060 | 070 | 085 | 100 | 115 | Codes |
|---|---|---|---|---|---|---|
| Integrated furnace control (IFC) board | 62-105563-04 (gas code KE) or 62-105563-05 (gas code KL) | 14, 77, 93 | ||||
| Memory module (model data card) for the IFC | 47-104778-18 | 47-104778-19 | 47-104778-20 | 47-104778-21 | 47-104778-22 | d1, d4, d6, 61, 68 |
| Flame sensor | 62-23543-08 | 11, 12, 13 | ||||
| Spark ignitor | 62-24141-05 | 11 | ||||
| Gas valve, natural gas | 60-102787-04 | 14, 77 | ||||
| Pressure switch, high fire | 42-106242-04 | 42-106242-06 | 42-106242-04 | 42-106242-04 | 42-106242-04 | 55, 57 |
| Pressure switch, mid fire | 42-106243-01 | 42-106243-03 | 42-106243-01 | 42-106243-01 | 42-106243-01 | 65, 67 |
| Pressure switch, low fire | 42-106242-02 | 44, 45, 46 | ||||
| Main limit (heat exchanger panel) | 47-104465-01 | 47-104465-01 | 47-104465-01 | 47-104465-01 | 47-104465-02 | 22 |
| Manual reset limit, burner compartment (3 per furnace) | 47-104888-01 | 33 | ||||
| Induced draft blower (with gasket) | 70-104157-06 | 45, 46, 57, 71 | ||||
| Induced draft blower gasket | 68-104152-01 | |||||
| Water sensor (2 per furnace) | 47-104184-01 | 58, 59 | ||||
| Transformer | 46-102856-02 | 30 | ||||
| Blower motor | 51-102602-01 | 51-102602-01 | 51-102603-01 | 51-102603-01 | 51-102603-01 | 60, 61, 68 |
| Power factor choke (PFC) | None | None | 46-24256-05 | 46-24256-05 | 46-24256-05 | 61, 68 |
| Blower wheel | PD703027 | PD703027 | PD703028 | PD703028 | PD703029 | 61 |
| Door switch | 42-22692-09 | |||||
| High altitude kit | RXGY-F43 | RXGY-F44 | RXGY-F45 | RXGY-F46 | RXGY-F47 | 46, 57 |
| Outdoor sensor kit | RXGY-J02 | |||||
- Sizes are the input in the model number (R98VA060…, R98VB115…). The gas code (KE or KL) is on the rating plate.
- The memory module carries the model data for one furnace size. Never use one from a different furnace; Rheem warns wrong blower operation can damage the heat exchanger.
- Part numbers are from Rheem's parts list dated 13-November-2019. Rheem supersedes numbers over time, so confirm with your distributor using the full model and serial number.
Parts source: Rheem Parts List 92-42800-R98V-USA (13-November-2019), Electric, Blower, Heat Exchanger and Gas Controls groups, pp. 6-8.
How to read the codes
- Check that you're reading the display the right way up. If a code isn't on this list, the display may be upside-down.
- Normal operation, not faults: 0 standby; h low gas heat, H high gas heat; c low cooling, C high cooling; hP low heat pump heat, HP high heat pump heat; F continuous fan; dF defrost (dual-fuel); cd or Cd cooling with dehumidification.
- Code 10 (one-hour lockout) alternates with the code that caused it: 11 four failed ignitions, 13 flame lost five times, 14 unexpected flame, 59 water sensed, 61 dead blower after the main limit, 93 internal fault.
- A communicating thermostat shows the same fault code and message.
- Codes 65 and 67 are the mid pressure switch. The furnace keeps heating, but any firing rate between 50% and 65% runs at 70% instead.
Source: Rheem (-)98V Installation Instructions, 92-24161-159-03, Table 19 Fault Codes, pp. 92-101 (normal operation codes, Table 18, p. 91). The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.
Related
- How to read furnace LED flash codes
- Furnace pressure switch troubleshooting
- Flame sensor microamps and cleaning
Other brands
- Lennox Merit ML180UH (80% single-stage)
- Carrier 58CVA / 58CVX (80% variable-speed two-stage)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N9MSE (90% single-stage condensing, PSC blower)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N8MSN / N8MSL (80% single-stage, PSC blower)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N80ESU / R80ESU (80% single-stage, ECM blower, Ultra Low NOx, minor series 2 and 3)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N80MSU (80% single-stage, ECM blower, Ultra Low NOx, 3-digit display, minor series 3)
- Rheem / Ruud R96V / 96MDV (96% two-stage communicating)
- Rheem / Ruud R97V (97% modulating communicating, downflow/horizontal)
- Goodman / Amana GR9S80 / GD9S80 (80% single-stage)
- Trane / American Standard S9X1 / S9X2 / S9B1 (96% condensing)
- Lennox SL280UHV (80% two-stage variable speed)
- Goodman / Amana / Daikin GM9S96 / GC9S96 / GM9S92 (96% and 92% condensing, single-stage)
- Carrier 59TP6C two-stage condensing with InteliSense (Performance series)
- Lennox G60DF / G60DFV (older two-stage SureLight boards 18M3401, 46M9901, 18M9901, 49M5901)
- Lennox G60UH / G60UHV (SureLight boards 100869 and 100870)
- Rheem / Ruud R801T Ultra Low NOx (14 ng/J) single-stage upflow/horizontal, constant-torque blower
- Rheem / Ruud 802V / 80MDV (80% two-stage communicating, ECM blower; model numbers (-)802V and (-)(-)80MDV)
- Trane / American Standard S8B1 / S8X1 / S8X2 (80% single-stage and two-stage)
- Trane / American Standard A801X060AM3S (80% single-stage, 2024 installation manual)
- Trane / American Standard A801X (80% single-stage: A801X040AM3SD, A801X040BM2SD, A801X060BM4SD, A801X080BM4SD, A801X080CM5SD, A801X100CM5SD, A801X120DM5SD)
- Goodman / Amana GMVC96 / GCVC96 (96% two-stage variable-speed, *MVC96*BA and *CVC96*BA)
- Goodman / Amana GMVS96 / AMVS96 U-revision (96% variable-speed with analog pressure sensor, model numbers GMVS96*U and AMVS96*U)
- Goodman / Amana GMVM96 / GCVM96 / AMVM96 / ACVM96 (96% modulating, model numbers *MVM96 and *CVM96)
- Rheem / Ruud R801T / 80MSX (80% single-stage, constant-torque blower; model numbers (-)801T and (-)(-)80MSX)
- Rheem / Ruud 802P / 80MDP (80% two-stage, model numbers (-)802P and (-)(-)80MDP)
- Rheem / Ruud 802T / 80MDT (80% two-stage with constant-torque blower, model numbers (-)802T and (-)(-)80MDT)
- Rheem / Ruud 801S / 801P / 80MSS / 80MSP (80% single-stage, model numbers (-)801S, (-)801P, (-)(-)80MSS and (-)(-)80MSP)
- Rheem / Ruud W801T (Rheem Select 80% downflow single-stage)
- Rheem / Ruud R951T (95% single-stage condensing, constant-torque blower; model numbers (-)951T)
- Rheem / Ruud 801V Ultra Low NOx (80% communicating, constant CFM blower, upflow/horizontal)
- Carrier 58STA / 58STX (80% single-stage, 4-way multipoise)
- Carrier 58CTA / 58CTX (80% two-stage, 4-way multipoise, Series 140/E)
- York TG9S (95.5% AFUE single-stage PSC, multi-position)
- York TM9V (96% AFUE two-stage variable-speed ECM, multi-position)
- York UTEC Board (single- and two-stage furnaces from August 2009; SAP 539617, 542760, 542767, 542766; Source 1 S1-33102956000, S1-03102951001, S1-33102954000, S1-33102955000)
- York White-Rodgers Board (the generation before the 2009 UTEC boards; 265901, S1-33109167000 / 265902, S1-33109168000 / 265903, S1-33109169000 / 265904)
- York TI Board (older furnaces; 031-01972-000 TI 6DT-1, 031-01973-000 TI 6DT-2, 031-09117-000 TI 6MD-1, 031-09118-000 TI 6MI-1)
- Carrier 58SB0A / 58SB1A (single-stage, non-condensing)