Rheem / Ruud R96V / 96MDV Furnace Codes

Applies to: Rheem / Ruud R96V / 96MDV (96% two-stage communicating). Dual seven-segment display on the integrated furnace control.

Sold as Rheem R96V and Ruud U96V / 96MDV. Other Rheem and Ruud communicating furnaces use similar two-digit codes, but check the label on the unit.

CodeMeaningWhat to check
d1No model data.Memory card missing or not seated. Use the card that came with the furnace.
d4No valid model data on memory card.Wrong or damaged memory card.
d6Horsepower conflict on memory card.Blower motor horsepower doesn't match the model data, usually after a motor replacement.
10One-hour lockout.Shown alternating with the code that caused it (11, 13, 14, 59, 61). Fix that fault. How to fix →
11Failed ignition.Gas supply, igniter, gas valve, flame sensor. How to fix →
12Low flame sense.Clean the flame sensor, check wiring and burner ground. How to fix →
13Flame lost after established.Flame sensor, gas pressure, ground, unstable flame. How to fix →
14Flame present with gas valve off.Miswired gas valve, valve stuck open, or control fault. How to fix →
22Main limit open.Airflow: filter, blower, ducts, coil. Check temperature rise. How to fix →
23HALC open.No continuity between pins 3 and 5 of connector P1 on the control. Repair the jumper or wiring.
26Line and neutral reversed or poor ground.Swap hot and neutral; verify a solid ground. How to fix →
30Open fuse.Short in 24 VAC wiring to ground or common. How to fix →
33Over-temperature switch (roll-out) open.Venting, inducer, heat exchanger, flame pattern. Manual reset. How to fix →
44Low pressure switch closed, inducer off.Stuck or bypassed switch, or abnormal vent pressure. How to fix →
45Low pressure switch open, inducer on high speed.Vent or intake blockage, excess vent length, hoses, inducer. How to fix →
46Low pressure switch open, inducer on low speed.Vent or intake blockage, hoses, inducer, high-altitude kit. How to fix →
55High pressure switch closed, inducer off.Stuck or bypassed switch. How to fix →
57High pressure switch open, inducer on high speed.Vent or intake blockage, hoses, inducer. How to fix →
58Water circuit open.Blocked-drain (water) sensor wiring open or disconnected.
59Water sensed.Blocked condensate drain or trap; clear it and check the sensor.
60Blower fault – blower can still run.High static pressure or restrictive ducts. How to fix →
61Blower fault – motor cannot run.Motor wiring, choke, failed motor or seized wheel.
66Blower cutback.Blower at its torque or speed limit: high static pressure. How to fix →
68No blower communications.Communication wiring between control and motor, or failed motor.
93Internal control fault detected.Check for 24 VAC applied where it shouldn't be; otherwise replace the control.
99Remote faults reset performed.Informational: the fault history was cleared.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Rheem R96V / 96MDV Installation Instructions, 92-24161-124-08, Table 20 Fault Codes. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.