York UTEC Board Furnace Codes
Johnson Controls also sells furnaces under the Coleman and Luxaire names. Codes match only when the control board is the same, so check the board's SAP number and the label inside the blower door.
| Code | Meaning | What to check |
|---|---|---|
| Steady off | No power to the board, or control failure. | How to fix → |
| Green heartbeat | Normal operation, no call for heat, no active errors. | |
| Amber heartbeat | Normal operation with call for heat (first stage on two-stage boards). | |
| 2 amber | Two-stage boards: normal operation with call for second-stage heat. | |
| 3 amber | Two-stage boards: W2 present with no W1. | How to fix → |
| 4 amber | Y present with no G call. | How to fix → |
| Rapid amber flash | Low flame sense current. | How to fix → |
| Solid LED, any color | Control fault detected. | |
| Rapid red flash | Incorrect 24 VAC phasing or twinning error. | York's chart adds: don't twin X13 ECM motors (single-stage boards) or variable speed ECM motors (two-stage ECM board). |
| 1 red | Flame sensed with the gas valve off. Stored. | How to fix → |
| 2 red | Pressure switch stuck closed. Stored. | How to fix → |
| 3 red | Pressure switch open (first-stage pressure switch open on two-stage boards). Stored. | How to fix → |
| 3 double red | Two-stage boards: second-stage pressure switch stuck open. Stored. | How to fix → |
| 4 red | Open high limit switch. Stored. | How to fix → |
| 5 red | Open rollout. Stored; hard lockout. | How to fix → |
| 6 red | Pressure switch cycle lockout. Stored; one-hour soft lockout. | How to fix → |
| 7 red | One-hour lockout (retries). Stored; one-hour soft lockout. | How to fix → |
| 8 red | Lockout (recycles), flame dropouts. Stored; one-hour soft lockout. | How to fix → |
| 9 red | Grounding or reversed polarity, or transformer leads reversed. | |
| 10 red | Gas valve energized with no call for heat. Stored. | |
| 11 red | Limit switch open more than 5 minutes (blower failure). Stored; hard lockout. | How to fix → |
| 12 red | Open hot surface igniter (HSI). | How to fix → |
How to read the codes
- York phased these boards in during August 2009, starting with furnace serial prefix W0H9. Boards covered: single-stage heat and cool with PSC motor (SAP# 539617, Source 1 S1-33102956000); single-stage heat and cool with X13 ECM motor (SAP# 542760, Source 1 S1-03102951001); two-stage heat and cool with PSC motor (SAP# 542767, Source 1 S1-33102954000); two-stage heat and cool with variable speed ECM motor (SAP# 542766, Source 1 S1-33102955000). The SAP number is printed on the board.
- To read stored codes, push and release the LAST ERROR button for more than 1/5 second and less than 5 seconds. The LED flashes up to five stored codes, newest first, with 2 seconds between codes. Two green flashes means no codes are stored. Solid LED codes are not stored or shown.
- To clear stored codes, push and hold LAST ERROR for at least five seconds. The LED flashes three green when memory is cleared.
- In the chart, a code marked stored goes into the error code memory. Soft lockout lasts one hour; hard lockout is marked separately.
- York says these boards are basically a drop-in replacement, but they may be larger than earlier boards, so older furnaces may need new mounting holes drilled. A drilling template comes with each repair part board. Board sizes: single-stage PSC 4 1/2 x 5 7/8 in., single-stage X13 4 7/8 x 7 in., two-stage PSC 5 x 8 in., two-stage ECM 5 1/4 x 8 in.
- The single-stage PSC board has no CONT FAN SPEED selection and is designed for single-stage cooling only (no Y2). On the X13 board, blower speed #1 is high and #5 is low. The single-stage and two-stage PSC boards can be twinned; ECM motors can't be twinned.
- Refer to the furnace's own wiring diagram for circuit connections when replacing a board.
Source: York Service Tips ST-045-09, UTEC Integrated Furnace Control (IFC) Boards on All Single and Two Stage Gas Furnaces (September 2, 2009), p. 1 and New UTEC IFC Boards fault code sheet, p. 5. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.
Related
- How to read furnace LED flash codes
- Furnace pressure switch troubleshooting
- Flame sensor microamps and cleaning
Other brands
- Lennox Merit ML180UH (80% single-stage)
- Carrier 58CVA / 58CVX (80% variable-speed two-stage)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N9MSE (90% single-stage condensing, PSC blower)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N8MSN / N8MSL (80% single-stage, PSC blower)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N80ESU / R80ESU (80% single-stage, ECM blower, Ultra Low NOx, minor series 2 and 3)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N80MSU (80% single-stage, ECM blower, Ultra Low NOx, 3-digit display, minor series 3)
- Rheem / Ruud R96V / 96MDV (96% two-stage communicating)
- Rheem / Ruud R97V (97% modulating communicating, downflow/horizontal)
- Rheem / Ruud R98V (98% modulating communicating, upflow)
- Goodman / Amana GR9S80 / GD9S80 (80% single-stage)
- Trane / American Standard S9X1 / S9X2 / S9B1 (96% condensing)
- Lennox SL280UHV (80% two-stage variable speed)
- Goodman / Amana / Daikin GM9S96 / GC9S96 / GM9S92 (96% and 92% condensing, single-stage)
- Carrier 59TP6C two-stage condensing with InteliSense (Performance series)
- Lennox G60DF / G60DFV (older two-stage SureLight boards 18M3401, 46M9901, 18M9901, 49M5901)
- Lennox G60UH / G60UHV (SureLight boards 100869 and 100870)
- Rheem / Ruud R801T Ultra Low NOx (14 ng/J) single-stage upflow/horizontal, constant-torque blower
- Rheem / Ruud 802V / 80MDV (80% two-stage communicating, ECM blower; model numbers (-)802V and (-)(-)80MDV)
- Trane / American Standard S8B1 / S8X1 / S8X2 (80% single-stage and two-stage)
- Trane / American Standard A801X060AM3S (80% single-stage, 2024 installation manual)
- Trane / American Standard A801X (80% single-stage: A801X040AM3SD, A801X040BM2SD, A801X060BM4SD, A801X080BM4SD, A801X080CM5SD, A801X100CM5SD, A801X120DM5SD)
- Goodman / Amana GMVC96 / GCVC96 (96% two-stage variable-speed, *MVC96*BA and *CVC96*BA)
- Goodman / Amana GMVS96 / AMVS96 U-revision (96% variable-speed with analog pressure sensor, model numbers GMVS96*U and AMVS96*U)
- Goodman / Amana GMVM96 / GCVM96 / AMVM96 / ACVM96 (96% modulating, model numbers *MVM96 and *CVM96)
- Rheem / Ruud R801T / 80MSX (80% single-stage, constant-torque blower; model numbers (-)801T and (-)(-)80MSX)
- Rheem / Ruud 802P / 80MDP (80% two-stage, model numbers (-)802P and (-)(-)80MDP)
- Rheem / Ruud 802T / 80MDT (80% two-stage with constant-torque blower, model numbers (-)802T and (-)(-)80MDT)
- Rheem / Ruud 801S / 801P / 80MSS / 80MSP (80% single-stage, model numbers (-)801S, (-)801P, (-)(-)80MSS and (-)(-)80MSP)
- Rheem / Ruud W801T (Rheem Select 80% downflow single-stage)
- Rheem / Ruud R951T (95% single-stage condensing, constant-torque blower; model numbers (-)951T)
- Rheem / Ruud 801V Ultra Low NOx (80% communicating, constant CFM blower, upflow/horizontal)
- Carrier 58STA / 58STX (80% single-stage, 4-way multipoise)
- Carrier 58CTA / 58CTX (80% two-stage, 4-way multipoise, Series 140/E)
- York TG9S (95.5% AFUE single-stage PSC, multi-position)
- York TM9V (96% AFUE two-stage variable-speed ECM, multi-position)
- York White-Rodgers Board (the generation before the 2009 UTEC boards; 265901, S1-33109167000 / 265902, S1-33109168000 / 265903, S1-33109169000 / 265904)
- York TI Board (older furnaces; 031-01972-000 TI 6DT-1, 031-01973-000 TI 6DT-2, 031-09117-000 TI 6MD-1, 031-09118-000 TI 6MI-1)
- Carrier 58SB0A / 58SB1A (single-stage, non-condensing)