York UTEC Board Furnace Codes

Applies to: York UTEC Board (single- and two-stage furnaces from August 2009; SAP 539617, 542760, 542767, 542766; Source 1 S1-33102956000, S1-03102951001, S1-33102954000, S1-33102955000). LED on the UTEC furnace control board that flashes red, green or amber.

Johnson Controls also sells furnaces under the Coleman and Luxaire names. Codes match only when the control board is the same, so check the board's SAP number and the label inside the blower door.

CodeMeaningWhat to check
Steady offNo power to the board, or control failure. How to fix →
Green heartbeatNormal operation, no call for heat, no active errors.
Amber heartbeatNormal operation with call for heat (first stage on two-stage boards).
2 amberTwo-stage boards: normal operation with call for second-stage heat.
3 amberTwo-stage boards: W2 present with no W1. How to fix →
4 amberY present with no G call. How to fix →
Rapid amber flashLow flame sense current. How to fix →
Solid LED, any colorControl fault detected.
Rapid red flashIncorrect 24 VAC phasing or twinning error.York's chart adds: don't twin X13 ECM motors (single-stage boards) or variable speed ECM motors (two-stage ECM board).
1 redFlame sensed with the gas valve off. Stored. How to fix →
2 redPressure switch stuck closed. Stored. How to fix →
3 redPressure switch open (first-stage pressure switch open on two-stage boards). Stored. How to fix →
3 double redTwo-stage boards: second-stage pressure switch stuck open. Stored. How to fix →
4 redOpen high limit switch. Stored. How to fix →
5 redOpen rollout. Stored; hard lockout. How to fix →
6 redPressure switch cycle lockout. Stored; one-hour soft lockout. How to fix →
7 redOne-hour lockout (retries). Stored; one-hour soft lockout. How to fix →
8 redLockout (recycles), flame dropouts. Stored; one-hour soft lockout. How to fix →
9 redGrounding or reversed polarity, or transformer leads reversed.
10 redGas valve energized with no call for heat. Stored.
11 redLimit switch open more than 5 minutes (blower failure). Stored; hard lockout. How to fix →
12 redOpen hot surface igniter (HSI). How to fix →

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: York Service Tips ST-045-09, UTEC Integrated Furnace Control (IFC) Boards on All Single and Two Stage Gas Furnaces (September 2, 2009), p. 1 and New UTEC IFC Boards fault code sheet, p. 5. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.