Goodman / Amana GMES96 U Ultra-Low NOx Furnace Codes

Applies to: Goodman / Amana GMES96 U Ultra-Low NOx (single-stage 96%, U models: GMES96, Amana AMES96). Red, amber and green LED on the integrated control, with an SW1 button.

CodeMeaningWhat to check
NoneLED off; furnace doesn't run.No 120 V or 24 V to the control (disconnect off, door switch open, 24 V wires loose) or a bad control. Check for shorts in the 120 V and 24 V circuits. How to fix →
1 redLockout after too many ignition attempts (3 total retries).Failure to establish flame (no gas, bad igniter or alignment, wrong orifices, coated or oxidized sensor, bad wiring) or loss of flame (interrupted gas, lazy flames from gas pressure or flue/condensate restriction, weak inducer), an igniter or ground connection problem, or a faulty control. Check gas, the gas valve and orifice size, the flame signal (clean the sensor with steel wool), the inducer pressure sensor and its hose, flue and condensate piping, igniter resistance and the unit ground. How to fix →
2 redPressure sensor reads pressure when it should read zero.Faulty wiring to the pressure sensor, or a faulty sensor. Check the wiring; replace the sensor. How to fix →
3 redInducer not making its pressure setting; inducer runs continuously.Pressure sensor hoses blocked, pinched or misconnected, bad wiring, blocked intake or flue, or a weak inducer. Replace the inducer pressure sensor and hoses with proper parts if needed, check wiring, inspect intake and flue, or replace the inducer. How to fix →
4 redPrimary limit insert or aux limit open; circulator blower runs continuously.Not enough air over the heat exchanger (blocked filters, restrictive ductwork, wrong blower speed, failed blower), a faulty primary limit insert or aux limit, or loose wiring. Also check the heat exchanger shield position. How to fix →
5 redFlame sensed with no call for heat; inducer and circulator run continuously.Goodman lists a faulty integrated control: replace the control.
6 redBurner temperature limit switch open.Excessive flame (check gas supply pressure, gas valve and orifice size), blocked flue or air inlet pipe, failed inducer, loose wiring, or a faulty burner temperature switch. How to fix →
7 redGas valve circuit shorted; no furnace operation.Bad wiring or a faulty control. Inspect and replace wiring as needed, or replace the control.
Steady amberOEM test mode.None listed.
1 amberLow flame sense.Sensor out of position, coated or oxidized sensor, or lazy flame from wrong gas pressure or combustion air. Clean the flame rod (steel wool), check alignment, compare gas pressure with the rating plate. How to fix →
2 amberID plug failure.Improper ID plug: replace it.
3 amberControl fuse blown.Replace the 3 A control fuse. How to fix →
Steady greenNormal operation, idle / standby.None.
Rapid greenClearing error history (SW1 held over 5 seconds).Release the button while the LED is flashing green to clear the history.
1 greenCall for heating.Normal.
1 green (combustion noise)Abnormal combustion noise: high-pitched noise during burner operation.Insufficient combustion air or high input, blocked flue or air inlet pipe, or a faulty inducer or pressure sensor. Check gas supply and manifold pressures, gas valve and orifice size, flue and inlet piping, and inducer and pressure sensor performance.
2 greenCall for cooling.Normal.
3 greenContinuous fan operation.Normal.
3 rapid greenID plug installed (shown at power-up).On a control with unit-specific programming, a valid ID plug was installed at power-up and the control will use its parameters.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Goodman/Amana 96% Single Stage Ultra-Low NOx Gas Furnaces A/GMES96*U* & A/GM9S96*U* Service and Troubleshooting manual RS6612017 Rev. 5 (2026), *MES96*U* Troubleshooting pp. 26-28 (fault code recall and clear p. 28). The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.