Goodman / Amana GM9S96 U Ultra-Low NOx Furnace Codes

Applies to: Goodman / Amana GM9S96 U Ultra-Low NOx (single-stage 96%, U models: GM9S96, Amana AM9S96; Daikin DM96SN U: DM96SN0403BU, DM96SN0603BU, DM96SN0805CU). Three-character seven-segment display on the integrated control.

Daikin's DM96SE*U/DM96SN*U service instructions (RSD6612016r3, pp. 18-19) print the same troubleshooting chart for the DM96SN*U (PCBBF241 control board).

CodeMeaningWhat to check
IdLStand-by mode, normal operation.None.
EEEInternal control fault.Replace the control board.
EE0Lockout after too many ignition retries (3 total): failure to establish flame or loss of flame after it was established.Gas interruption, igniter (replace or realign), flame sense signal (clean a coated or oxidized sensor), flue piping blockage, length, elbows and termination, inducer performance. How to fix →
EE1Draft inducer pressure switch circuit closed at the start of the heating cycle.Switch contacts sticking or a short in the switch wiring. Replace the switch or repair the short. How to fix →
EE2Draft inducer pressure switch circuit not closed; inducer runs continuously.Pressure switch hose blocked, pinched or misconnected; blocked flue or inlet or a weak inducer; wrong setpoint or bad contacts; loose wiring. How to fix →
EE3Primary limit open; circulator runs continuously.Blocked filters, restrictive ductwork, wrong blower speed or failed blower motor; loose wiring in the high limit circuit. How to fix →
EE4Flame sensed with no call for heat; inducer and circulator run continuously.Short to ground in the flame sense circuit, or a lingering flame from a slow-closing gas valve.
EE5Open fuse.Find the short in the low voltage wiring, then replace the fuse. How to fix →
EE6Weak flame signal (furnace still runs).Coated or oxidized sensor, sensor out of position, inlet air blockage, or lazy flame from gas pressure or combustion air. Clean the sensor, check alignment and gas pressure against the rating plate. How to fix →
EE7Igniter circuit problem.Improperly connected or shorted igniter, poor unit ground, or the control's igniter relay. Check wiring and ground; check igniter output from the control. How to fix →
EEA115 V polarity reversed, or poor unit ground.Correct the polarity and verify the ground.
EEbGas valve energized when it should not be (internal gas valve error).Wiring in the gas valve circuit; replace the control if the wiring is good.
EECGas valve not energized when it should be (external gas valve error).Wiring in the gas valve circuit; replace the control if the wiring is good.
EEdAuxiliary limit (blower compartment) open.Power turned off during a heat cycle, blower not running during heat, or a faulty aux limit or wiring. How to fix →
E10Grounding error.Check grounding.
E11Burner limit switch circuit open.Gas supply pressure, flue and air inlet (blockage, length, elbows, termination), limit circuit wiring, burner temperature switch. How to fix →
E12Redundant relay open alarm.Replace the control board.
E13Redundant relay stuck closed alarm.Replace the control board.
EbFInducer communication alarm.Red, black and white harness and connections between the inducer and the control board.
E1bAPS (pressure sensor) reference error.Red, black and green harness and connections to the pressure sensor and board; replace the pressure sensor. How to fix →
E1CAPS null error.Red, black and green harness and connections; pressure hoses to the pressure sensor and pressure switch. How to fix →
E1dAPS span error.Red, black and green harness and connections; pressure hoses to the pressure sensor and pressure switch. How to fix →
E1EAPS pressure error.Red, black and green harness and connections; replace the pressure sensor. How to fix →
E1FAPS input error.Red, black and green harness and connections; replace the pressure sensor. How to fix →
EEHTwinning error.None listed in Goodman's table.
EbLLow circulator current.Make sure the motor's 120 V line wire runs through the current transformer loop to its terminal; check the wire connections to the motor and board.
EbUCirculator current unexpected.Make sure the motor's 120 V line wire runs through the current transformer loop to its terminal.
Ed0No shared data.Populate the shared data set using the memory card.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Goodman/Amana 96% Single Stage Ultra-Low NOx Gas Furnaces A/GMES96*U* & A/GM9S96*U* Service and Troubleshooting manual RS6612017 Rev. 5 (2026), *M9S96*U* Troubleshooting pp. 29-30. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.