Carrier 58TP0B / 58TP1B InteliSense Furnace Codes
The older 58TP0A / 58TP1A use two-digit codes and have their own chart.
| Code | Meaning | What to check |
|---|---|---|
| 10.1 | L1 polarity fault (rapid flash LED): incoming 115 V polarity reversed. | Line voltage polarity at each junction; on twinned units, the 24 V transformer phasing. |
| 12.1 | W on at power up (normal). | Blower runs 90 seconds if power comes on during a call for heat, or when R-W opens during the blower on-delay. |
| 13.1 | Limit lockout: limit, draft safeguard, flame rollout or blocked vent switch open longer than 3 minutes. | Auto-resets after 3 hours. See 33.1. How to fix → |
| 14.1 | Ignition lockout after 4 consecutive ignition tries. | Auto-resets after 3 hours. Manifold pressure and firing rate, inlet pressure swings; see 34.1. How to fix → |
| 14.2 | Flame lost 3 times after 70 seconds of heating. | Auto-resets after 3 hours. Manifold pressure and firing rate, inlet pressure swings; see 34.6-34.8. How to fix → |
| 14.3 | Lockout: 7 loss-of-flame events during one heat request. | Manifold pressure and firing rate, inlet pressure swings; see 34.6-34.8. How to fix → |
| 14.4 | Lockout: low-heat pressure switch (LPS) opened 7 times during one heat request. | See 32.2 and 34.1. How to fix → |
| 15.1 | Lockout: no blower RPM detected. | Loose blower wire connections, failed blower motor. |
| 19.1 | InteliSense communication loss with the thermostat. | Not shown until InteliSense communication has been established once. Check the R and Y connections at the control and thermostat; see the thermostat's advanced installation instructions (Carrier.hvacpartners.com/InteliSense). |
| 21.1 | 24 VAC sensed on the gas valve when it shouldn't be. | Turn off power and wait 5 minutes to retry. Stuck-closed gas valve relay on the control, or a miswire or short on the gas valve wire. |
| 22.1 | False flame: flame proved while the gas valve is off; inducer runs until it clears. | Stuck-open or leaky gas valve. |
| 23.4 | LPS (low-heat pressure switch) stuck closed. | Obstructed pressure tube, or the switch stuck closed (the guide calls this stuck main pressure switch, 23.1). How to fix → |
| 23.5 | HPS (high-heat pressure switch) stuck closed. | Obstructed pressure tube, or the switch stuck closed. How to fix → |
| 24.1 | Fuse fault. | Short in the 24 V wiring, including thermostat leads; disconnect the thermostat leads to isolate it. How to fix → |
| 25.1 | No program. | Reprogram the control with the correct program number from the rating plate (service app or super plug); replace the control if the issue remains. |
| 25.2 | Corrupted program file. | Reprogram the control (service app or super plug). |
| 25.3 | Twinned units not identical (program numbers don't match). | Twinned furnaces must have the same program number; the main unit won't operate. |
| 25.4 | Main program invalid; running on the backup program. | Reprogram the control. It still operates normally. |
| 25.5 | Installer settings corrupted. | Reselect the installer settings or reprogram; runs on default settings meanwhile. |
| 25.6 | Wrong program; reprogram the control. | Reprogram the control with the correct program number from the rating plate (service app or super plug); replace the control if the issue remains. |
| 27.1 | Super plug program missing, not recognized or corrupted. | Remove the super plug and retry; try a different super plug; if it still fails, replace the control. |
| 27.2 | Super plug program missing, not recognized or corrupted. | Remove the super plug and retry; try a different super plug; if it still fails, replace the control. |
| 27.3 | Super plug program missing, not recognized or corrupted. | Remove the super plug and retry; try a different super plug; if it still fails, replace the control. |
| 31.6 | Open HPS: high-heat pressure switch or relay didn't close or reopened. | Control relay may be defective, gas valve miswired; see 32.2. How to fix → |
| 31.7 | High heat only for the next cycle: HPS failed to close within 75 seconds when going from low to high heat. | Control relay may be defective, gas valve miswired; see 32.2. How to fix → |
| 32.2 | Open LPS: low-heat pressure switch didn't close or reopened. | Open longer than 5 minutes: the inducer shuts off 15 minutes before retrying. If the LPS opens within 5 minutes after the gas valve opens, the next cycle is forced to high heat. Vent sizing, low inducer voltage (115 V), low inlet gas pressure (if LGPS used), combustion air, pressure tubing, defective inducer or pressure switch, excessive wind, restricted vent. How to fix → |
| 33.1 | Main limit circuit open (limit, draft safeguard, flame rollout or blocked vent shutoff switch). | Blower runs 4 minutes or until the switch remakes; over 3 minutes it becomes 13.1. Rollout switch and BVSS need a manual reset. Dirty filter or restricted ducts, loose blower wheel, defective switch or connections, defective blower motor or capacitor, combustion air (rollout open), restricted vent, vent sizing, excessive wind. How to fix → |
| 33.2 | Lockout: high heat only for the current cycle. | Same checks as 33.1. How to fix → |
| 34.1 | Ignition fault: four consecutive ignition trials without proving flame. | Low inlet gas pressure, control ground continuity, manual shut-off valve, green/yellow wire connected from the furnace to the burner box screw, flame sensor not grounded or touching the casing. In component test, the igniter should glow orange/white by the end of the 15-second warm-up. How to fix → |
| 34.5 | Low heat flame lost before the blower on-delay. | Low inlet gas pressure, control ground continuity, manual shut-off valve, green/yellow wire connected from the furnace to the burner box screw, flame sensor not grounded or touching the casing. In component test, the igniter should glow orange/white by the end of the 15-second warm-up. How to fix → |
| 34.6 | Low heat flame lost after the blower on-delay. | Low inlet gas pressure, control ground continuity, manual shut-off valve, green/yellow wire connected from the furnace to the burner box screw, flame sensor not grounded or touching the casing. In component test, the igniter should glow orange/white by the end of the 15-second warm-up. How to fix → |
| 34.7 | High heat flame lost before the blower on-delay. | Low inlet gas pressure, control ground continuity, manual shut-off valve, green/yellow wire connected from the furnace to the burner box screw, flame sensor not grounded or touching the casing. In component test, the igniter should glow orange/white by the end of the 15-second warm-up. How to fix → |
| 34.8 | High heat flame lost after the blower on-delay. | Low inlet gas pressure, control ground continuity, manual shut-off valve, green/yellow wire connected from the furnace to the burner box screw, flame sensor not grounded or touching the casing. In component test, the igniter should glow orange/white by the end of the 15-second warm-up. How to fix → |
| 41.1 | No blower RPM at start-up. | Loose blower wire connections, failed blower motor. |
| 41.2 | No RPM while the blower motor is running. | Loose blower wire connections, failed blower motor. |
| 43.1 | HPS closed before LPS (low-heat switch open while high-heat switch is closed). | LPS stuck open, disconnected or obstructed pressure tube, low inlet gas pressure (if LGPS used). How to fix → |
| 45.1 | Control failure: internal control error (flame circuit fault, memory mismatch or sequence error). | Cycle power; if 45 repeats, replace the control. |
| 45.2 | Control failure: gas valve relay not closing. | Cycle power; if 45 repeats, replace the control. |
| 45.3 | Control failure: micro EEPROM error. | Cycle power; if 45 repeats, replace the control. |
| 45.4 | Control failure: micro loss of communication. | Cycle power; if 45 repeats, replace the control. |
| 46.1 | Momentary loss of power. | Heating stops and restarts once the power fluctuation is resolved. |
| 52.1 | SAT open: supply air temperature sensor connection open. | Loose connection at the control board screw terminals, cut or shorted SAT wires, damaged SAT sensor. |
| 52.2 | SAT short: supply air temperature sensor wires shorted. | Loose connection at the control board screw terminals, cut or shorted SAT wires, damaged SAT sensor. |
| 53.1 | RAT open: return air temperature sensor connection open. | RAT firmly plugged into the control board; damaged RAT sensor. (The guide labels the RAT box 52.1/52.2; the service label numbers it 53.) |
| 53.2 | RAT short: return air temperature sensor shorted. | RAT firmly plugged into the control board; damaged RAT sensor. |
How to read the codes
- The display shows the major code in the first two digits and the minor code in the third (for example 34.6). Only the major code is seen through the sight glass: the LED flashes it as short flashes for the first digit and long flashes for the second.
- Normal displays: IdL idle/standby, HE2/HE1 high/low heating, CL2/CL1 high/low cooling, HPd heat pump defrost, CFn continuous fan. Menu FLt shows the last 7 faults.
- Component test: in IdL with no thermostat call, select Ct from the menu; the inducer runs on high, then the igniter for 15 seconds, the blower for 10 seconds, then the inducer on low for 10 seconds.
- Code meanings are from the service label (Fig. 46); checks are from the troubleshooting guide (Fig. 52). Where the guide numbers a code differently, the label number is used.
Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.
Source: Carrier 58TP0B/58TP1B Installation, Start-up, Operating and Service and Maintenance Instructions 58TP0B-01SI, Fig. 46 Service Label p. 32, Fig. 52 Troubleshooting Guide pp. 49-50. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.
Related
- How to read furnace LED flash codes
- Furnace pressure switch troubleshooting
- Flame sensor microamps and cleaning
Other brands
- Lennox Merit ML180UH (80% single-stage)
- Carrier 58CVA / 58CVX (80% variable-speed two-stage)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) R96MSN / N96MSN (single-stage 35-in. condensing, 4-way multipoise)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) R95MSU (single-stage Ultra Low NOx condensing, upflow/horizontal, 35 in. tall)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N95ESN / R92ESN (single-stage 35-in. condensing, 4-way multipoise; also PG95ESA)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N92ESN (single-stage 35-in. condensing, 4-way multipoise)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N9MSE (90% single-stage condensing, PSC blower)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N8MSN / N8MSL (80% single-stage, PSC blower)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N80ESU / R80ESU (80% single-stage, ECM blower, Ultra Low NOx, minor series 2 and 3)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N80MSU (80% single-stage, ECM blower, Ultra Low NOx, 3-digit display, minor series 3)
- Rheem / Ruud R96P / 96MDP (96% two-stage condensing, PSC blower; model numbers (-)96P and (-)(-)96MDP, e.g. R96PA0702317MSA)
- Rheem / Ruud R96V / 96MDV (96% two-stage communicating)
- Rheem / Ruud R97V (97% modulating communicating, downflow/horizontal)
- Rheem / Ruud R98V (98% modulating communicating, upflow)
- Goodman / Amana GR9S80 / GD9S80 (80% single-stage)
- Trane / American Standard S9X1 / S9X2 / S9B1 (96% condensing)
- Lennox EL296UHV / SL280UHV control 107045 (Elite EL296UHV(X), EL296DFV(X) and SL280UHV/SL280UHNV/SL280DFV, two-stage, variable-speed, communicating; EL296UH045V36B, EL296UH045XV36B, EL296UH070V36B, EL296UH070XV36B, EL296UH090V36C, EL296UH090XV36C, EL296UH090XV48C, EL296UH090V60C, EL296UH090XV60C, EL296UH110V48C, EL296UH110XV48C, EL296UH110V60C, EL296UH110XV60C, EL296UH135V60D, EL296UH135XV60D, EL296DF045XV36B, EL296DF070V48B, EL296DF070XV48B, EL296DF090V60C, EL296DF090XV60C, EL296DF110V60C, EL296DF110XV60C, SL280UH070V36A, SL280UH070XV36A, SL280UH090V36B, SL280UH090V48B, SL280UH090XV48B, SL280UH090V60C, SL280UH090XV60C, SL280UH110V60C, SL280UH110XV60C, SL280UH135V60D, SL280DF070V36A, SL280DF090V48B, SL280DF090V60C, SL280DF110V60C)
- Lennox EL296UHV / SL280UHV control 103130 (Elite EL296UHV(X), EL296DFV(X) and SL280UHV/SL280UHNV/SL280DFV, earlier units: EL296UH045V36B, EL296UH045XV36B, EL296UH070V36B, EL296UH070XV36B, EL296UH090V36C, EL296UH090XV36C, EL296UH090XV48C, EL296UH090V60C, EL296UH090XV60C, EL296UH110V48C, EL296UH110XV48C, EL296UH110V60C, EL296UH110XV60C, EL296UH135V60D, EL296UH135XV60D, EL296DF045XV36B, EL296DF070V48B, EL296DF070XV48B, EL296DF090V60C, EL296DF090XV60C, EL296DF110V60C, EL296DF110XV60C, SL280UH070V36A, SL280UH070XV36A, SL280UH090V36B, SL280UH090V48B, SL280UH090XV48B, SL280UH090V60C, SL280UH090XV60C, SL280UH110V60C, SL280UH110XV60C, SL280UH135V60D, SL280DF070V36A, SL280DF090V48B, SL280DF090V60C, SL280DF110V60C, SL280UH060NV36A, SL280UH080NV48B, SL280UH080NV60C, SL280UH100NV60C)
- Lennox Elite EL297UHVK(X) / EL297DFVK (two-stage, variable-speed, communicating; upflow/horizontal EL297UH045XV36BK, EL297UH070XV36BK, EL297UH090XV36CK, EL297UH090XV48CK, EL297UH090XV60CK, EL297UH110XV48CK, EL297UH110XV60CK, EL297UH135XV60DK; downflow EL297DF045XV36BK, EL297DF070XV48BK, EL297DF090XV60CK, EL297DF110XV60CK; also Merit SL280UHVK and SL280UHNVK: SL280UH070XV36AK, SL280UH090XV48BK, SL280UH090XV60CK, SL280UH110XV60CK, SL280UH070V36AK, SL280UH090V36BK, SL280UH090V48BK, SL280UH090V60CK, SL280UH110V60CK, SL280UH135V60DK, SL280UH060NV36AK, SL280UH080NV48BK, SL280UH080NV60CK, SL280UH100NV60CK)
- Lennox Signature SLP99UHVK (Dave Lennox Signature, variable capacity, variable speed, communicating: SLP99UH070V36BK, SLP99UH070XV36BK, SLP99UH090V36CK, SLP99UH090XV36CK, SLP99UH090V48CK, SLP99UH090XV48CK, SLP99UH090V60CK, SLP99UH090XV60CK, SLP99UH110V60CK, SLP99UH110XV60CK, SLP99UH135V60DK, SLP99UH135XV60DK)
- Lennox Signature SLP99DFV (Dave Lennox Signature downflow, variable capacity, variable speed, communicating: SLP99DF070XV36B, SLP99DF090XV36C, SLP99DF090XV48C, SLP99DF090XV60C, SLP99DF110XV60C)
- Lennox Elite EL296UHE (96% two-stage, constant torque: EL296UH045XE36B, EL296UH070XE36B, EL296UH090XE48C, EL296UH110XE60C, EL296UH135XE60D; also Elite EL280DFE downflow: EL280DF070E36A, EL280DF090E48B)
- Lennox Elite EL297UHEK (two-stage, constant torque, non-communicating: EL297UH045XE36BK, EL297UH070XE36BK, EL297UH090XE48CK, EL297UH110XE60CK, EL297UH135XE60DK; same control and codes: Elite EL280UHEK and EL280DFEK (80%): EL280UH045E36AK, EL280UH070E36AK, EL280UH070XE36AK, EL280UH090E36BK, EL280UH090E48BK, EL280UH090XE48BK, EL280UH110E48CK, EL280UH110E60CK, EL280UH110XE60CK, EL280DF070E36AK, EL280DF090E48BK)
- Lennox Merit ML196UHEK / Elite EL196UHEK (80% single-stage, constant torque: ML196UH030XE36BK, ML196UH045XE36BK, ML196UH070XE36BK, ML196UH070XE48BK, ML196UH090XE36CK, ML196UH090XE48CK, ML196UH090XE60CK, ML196UH110XE60CK, ML196UH135XE60DK, EL196UH030XE36BK, EL196UH045XE36BK, EL196UH070XE36BK, EL196UH090XE48CK, EL196UH110XE60CK; same control and codes: Elite EL180UHNEK, Merit ML180UHEK, ML193DFEK, Elite EL195UHNEK: EL180UH040NE36AK, EL180UH060NE36AK, EL180UH080NE48BK, EL180UH100NE60CK, ML180UH045E36AK, ML180UH045XE36AK, ML180UH070E36AK, ML180UH070E36BK, ML180UH070XE36BK, ML180UH090E48BK, ML180UH090XE48BK, ML180UH090E60CK, ML180UH110E60CK, ML180UH110XE60CK, ML180UH135E60DK, ML193DF045XE36BK, ML193DF070XE36BK, ML193DF090XE48CK, EL195UH040NE36BK, EL195UH060NE36BK, EL195UH080NE48CK, EL195UH100NE60CK; variable-speed Merit ML180UHVK: ML180UH030V36AK, ML180UH045V36AK, ML180UH070V36AK, ML180UH070V36BK, ML180UH070V48BK, ML180UH090V48BK, ML180UH110V60CK, ML180UH135V60DK)
- Lennox Merit ML196UHE / ML196DFE / ML193UHE (single-stage, red LED controls 103217-03 and 107163-01: ML196UH030XE36B, ML196UH045XE36B, ML196UH070XE36B, ML196UH070XE48B, ML196UH090XE36C, ML196UH090XE48C, ML196UH090XE60C, ML196UH110XE60C, ML196UH135XE60D, ML196DF045XE36B, ML196DF070XE48B, ML196DF090XE48C, ML196DF110XE60C, ML193UH030XE36B, ML193UH045XE36B, ML193UH070XE36B, ML193UH090XE36C, ML193UH090XE48C, ML193UH110XE48C, ML193UH110XE60C; also ML180UHE and ML180DFE: ML180UH045E36A, ML180UH045XE36A, ML180UH070E36A, ML180UH070XE36A, ML180UH070E36B, ML180UH070XE36B, ML180UH090E48B, ML180UH090XE48B, ML180UH090E60C, ML180UH110E60C, ML180UH110XE60C, ML180UH135E60D, ML180DF045E36A, ML180DF070E36A, ML180DF070E36B, ML180DF090E48B, ML180DF110E60C; ML180UHV: ML180UH030V36A, ML180UH045V36A, ML180UH070V36A, ML180UH070V36B, ML180UH070V48B, ML180UH090V48B, ML180UH110V60C; Elite EL195UH (2011): EL195UH045P24B, EL195UH045P36B, EL195UH070P36B, EL195UH070P48B, EL195UH090P36C, EL195UH090P48C, EL195UH090P60C, EL195UH110P48C, EL195UH110P60C, EL195UH135P60D)
- Lennox Merit ML296UHVK / ML296DFVK / ML297UHVK (two-stage, variable-speed; upflow/horizontal ML296UH045XV36BK, ML296UH070XV36BK, ML296UH090XV48CK, ML296UH110XV60CK; downflow ML296DF045XV36BK, ML296DF070XV48BK, ML296DF090XV60CK; ML297UH045XV36BK, ML297UH070XV36BK, ML297UH090XV36CK, ML297UH090XV60CK, ML297UH110XV60CK, ML297UH135XV60DK)
- Lennox SL280UHV (80% two-stage variable speed)
- Goodman / Amana / Daikin GM9S96 / GC9S96 / GM9S92 (96% and 92% condensing, single-stage; also Daikin DM96SN, DM92SN, DC96SN: DM96SN0403AN, DM96SN0603BN, DM96SN0803BN, DM96SN0804CN, DM96SN0805CN, DM96SN1005CN, DM96SN1205DN, DM92SN0403AN, DM92SN0603BN, DM92SN0803BN, DM92SN0804CN, DM92SN0805CN, DM92SN1004CN, DM92SN1005CN, DM92SN1205DN, DC96SN0403BN, DC96SN0603BN, DC96SN0804CN, DC96SN1005CN, DC96SN1205DN)
- Payne PG96VTAB (two-stage condensing, variable-speed, non-communicating, 4-way multipoise)
- Payne PG9YAA / PG9YAB (95% single-stage condensing, direct or non-direct vent)
- Carrier 59TP6C (two-stage condensing with InteliSense, Performance series; also 926TC)
- Lennox G60DF / G60DFV (older two-stage SureLight boards 18M3401, 46M9901, 18M9901, 49M5901)
- Lennox G60UH / G60UHV (SureLight boards 100869 and 100870)
- Rheem / Ruud R801T Ultra Low NOx (14 ng/J) single-stage upflow/horizontal, constant-torque blower
- Rheem / Ruud 802V / 80MDV (80% two-stage communicating, ECM blower; model numbers (-)802V and (-)(-)80MDV)
- Trane / American Standard S8B1 / S8X1 / S8X2 (80% single-stage and two-stage)
- Trane / American Standard A801X060AM3S (80% single-stage, 2024 installation manual)
- Trane / American Standard A801X (80% single-stage: A801X040AM3SD, A801X040BM2SD, A801X060BM4SD, A801X080BM4SD, A801X080CM5SD, A801X100CM5SD, A801X120DM5SD)
- Goodman / Amana GMEC96 / GCEC96 (two-stage, multi-speed ECM: GMEC96, GCEC96, Amana AMEC96, ACEC96)
- Goodman / Amana / Daikin GMSS92 / GMSS96 / GCSS9 (single-stage, 92% and 96%: GMSS92, GMSS96, GCSS92, GCSS96, Amana AMSS92, AMSS96, ACSS92, ACSS96, Daikin VMSS9, VCSS9)
- Goodman / Amana / Daikin GMES92 / GMES96 / GCES96 (single-stage, 92% and 96%: GMES92, GMES96, GCES96, Amana AMES92, AMES96, ACES96, Daikin VMES96, VCES96)
- Goodman / Amana GM9C96 / GC9C96 (two-stage, nine-speed ECM: GM9C96, GC9C96, Amana AM9C96, AC9C96)
- Goodman / Amana GMH8 / GDH8 / GME95 (modified two-stage: 80% GMH8, GDH8, Amana AMH8, ADSH8; 95% GME95, Amana AMEH96)
- Goodman / Amana / Daikin GMS8 / GDS8 (80% single-stage: GMS8, GDS8, Amana AMS8, ADSS8, Daikin VMS8, VDS8)
- Goodman / Amana GMES96 U Ultra-Low NOx (single-stage 96%, U models: GMES96, Amana AMES96)
- Goodman / Amana GM9S96 U Ultra-Low NOx (single-stage 96%, U models: GM9S96, Amana AM9S96; Daikin DM96SN U: DM96SN0403BU, DM96SN0603BU, DM96SN0805CU)
- Goodman / Amana GMVS80 U Ultra-Low NOx (80% single-stage, variable-speed communicating: GMVS80, Amana AMVS80)
- Goodman / Amana GKS9 / AKSS92 (92% single-stage upflow: GKS9, Amana AKSS92)
- Goodman / Amana GMVM97 / GCVM97 ComfortBridge (97% modulating, BA revision and later: GMVM97, GCVM97, Amana AMVM97, ACVM97)
- Goodman / Amana GMVC96 / GCVC96 (96% two-stage variable-speed, *MVC96*BA and *CVC96*BA)
- Goodman / Amana GMVC96 / GCVC96 BB ComfortBridge (96%, BB revision: GMVC96, GCVC96, Amana AMVC96, ACVC96)
- Goodman / Amana / Daikin AMVC96 / DM96VC / DM80VC ComfortNet (two-character codes: AMVC96, ACVC96, GMVC96, GCVC96 before the BA revision; DM96VC0403BN, DM96VC0603BN, DM96VC0803BN, DM96VC0804CN, DM96VC1005CN, DM96VC1005DN, DM96VC1205DN, DC96VC0403BN, DC96VC0603BN, DC96VC0803BN, DC96VC0804CN, DC96VC1005CN, DC96VC1205DN, DM80VC0603B, DM80VC0604B, DM80VC0805C, DM80VC1005C, DD80VC0603B, DD80VC0805C, DD80VC1005C)
- Goodman / Amana GMVS96 / AMVS96 U-revision (96% variable-speed with analog pressure sensor, model numbers GMVS96*U and AMVS96*U; also Daikin DM96SC U: DM96SC0603BU, DM96SC0805CU)
- Goodman / Amana GMVM96 / GCVM96 / AMVM96 / ACVM96 (96% modulating, model numbers *MVM96 and *CVM96; also Daikin DM97MC/DC97MC: DM97MC0603BNA, DM97MC0803BNA, DM97MC0804CNA, DM97MC1005CNA, DM97MC1205DNA, DC97MC0603BNA, DC97MC0803BNA, DC97MC0804CNA, DC97MC1005CNA)
- Rheem / Ruud R801T / 80MSX (80% single-stage, constant-torque blower; model numbers (-)801T and (-)(-)80MSX)
- Rheem / Ruud 802P / 80MDP (80% two-stage, model numbers (-)802P and (-)(-)80MDP)
- Rheem / Ruud 802T / 80MDT (80% two-stage with constant-torque blower, model numbers (-)802T and (-)(-)80MDT)
- Rheem / Ruud 801S / 801P / 80MSS / 80MSP (80% single-stage, model numbers (-)801S, (-)801P, (-)(-)80MSS and (-)(-)80MSP)
- Rheem / Ruud W801T (Rheem Select 80% downflow single-stage)
- Rheem / Ruud R951T / R95T / R92T (90%+ single-stage condensing, constant-torque blower; model numbers (-)951T, (-)95T, (-)(-)95MSX, (-)92T, (-)(-)92MSX, e.g. R95TC0701317MSA, R92TC0701317MSA)
- Rheem / Ruud 801V Ultra Low NOx (80% communicating, constant CFM blower, upflow/horizontal)
- Carrier 58STA / 58STX (80% single-stage, 4-way multipoise; also 313AAV, 313JAV)
- Carrier 58CTA / 58CTX (80% two-stage, 4-way multipoise, Series 140/E)
- York TG9S (95.5% AFUE single-stage PSC, multi-position)
- York TM9T (96% AFUE two-stage PSC, multi-position)
- York TM9X (95.5% AFUE single-stage ECM, multi-position: TM9X040A10MP11, TM9X060B12MP11, TM9X080B12MP11, TM9X080C16MP11, TM9X100C16MP11, TM9X100C20MP11, TM9X120D20MP11)
- York TM9M (97% AFUE modulating PSC, multi-position)
- York YP9C / TP9C / CP9C / LP9C (up to 98% AFUE modulating ECM, multi-position)
- York TM9V (96% AFUE two-stage variable-speed ECM, multi-position)
- York UTEC Board (single- and two-stage furnaces from August 2009; SAP 539617, 542760, 542767, 542766; Source 1 S1-33102956000, S1-03102951001, S1-33102954000, S1-33102955000)
- York White-Rodgers Board (the generation before the 2009 UTEC boards; 265901, S1-33109167000 / 265902, S1-33109168000 / 265903, S1-33109169000 / 265904)
- York TI Board (older furnaces; 031-01972-000 TI 6DT-1, 031-01973-000 TI 6DT-2, 031-09117-000 TI 6MD-1, 031-09118-000 TI 6MI-1)
- Carrier 58TN0A / 58TN1A (80% two-stage, variable-speed, 4-way multipoise; also 880TA, 881TA)
- Carrier 58TN0B / 58TN1B (80% two-stage, variable-speed, 4-way multipoise)
- Carrier 58TP0A / 58TP1A (80% two-stage, variable-speed ECM, 4-way multipoise; also PG80VTLA)
- Carrier 59SC5A (single-stage condensing, 4-way multipoise; also 912SB, 912SC, 922SA, 925SA, PG92SAS, PG92SCS, PG95SAS)
- Bryant 925TA (two-stage condensing, 4-way multipoise; also PG95XAT)
- Bryant 926SA (single-stage condensing, multi-speed ECM, multipoise)
- Bryant 926SB (single-stage condensing, 25-speed ECM, InteliSense)
- Carrier 59SC5B / 59SC2D (single-stage 35-in. condensing, 4-way multipoise; also 912SD, 915SB)
- Carrier 59MN7A / 59MN7B (modulating condensing, 4-way multipoise; also 987MA, 987MB)
- Carrier 59MN7C modulating condensing (59MN7C060C17, 59MN7C060C21, 59MN7C080C17, 59MN7C080C21, 59MN7C100C21, 59MN7C120C24; also 987MC)
- Carrier 59TP6B / 59TP6A / 59TN6A two-stage (condensing, two-digit codes; also 926TA, 926TB, 986TB, PG96VAT, PG96VTAA)
- Carrier 59TN6B two-stage condensing (variable-speed: 59TN6B060C17, 59TN6B080C17, 59TN6B080C21, 59TN6B100C21, 59TN6B120C24; also 986TC)
- Carrier 59TN6C two-stage condensing (variable-speed, 35 in. tall: 59TN6C040C14, 59TN6C060C17, 59TN6C080C17, 59TN6C080C21, 59TN6C100C21, 59TN6C120C24)
- Carrier 59TN7A two-stage condensing (variable-speed, 35 in. tall: 59TN7A060C17, 59TN7A080C17, 59TN7A080C21, 59TN7A100C21, 59TN7A120C24)
- Carrier 59SU5A (single-stage Ultra Low NOx condensing, upflow/horizontal, 35 in. tall)
- Carrier 59SU5B single-stage Ultra Low NOx (condensing, 35 in. tall: 59SU5B040M17, 59SU5B060M17, 59SU5B080M21, 59SU5B100M21; also PG95MSUA)
- Carrier 59TP7A two-stage InteliSense (condensing, variable-speed, non-communicating: 59TP7A060V17, 59TP7A080V17, 59TP7A080V21, 59TP7A100V21, 59TP7A120V24)
- Carrier 59SC2E / 59SC6A (single-stage 35-in. condensing, 4-way multipoise; also 912SE, PG96MSAA)
- Carrier 58CU0A (80% communicating, Ultra Low NOx, 4-way multipoise)
- Carrier 58SU0A (80% single-stage, ECM blower, Ultra Low NOx, 4-way multipoise; also 830SA)
- Carrier 58SU0B (80% single-stage, ECM blower, Ultra Low NOx, 3-digit display)
- Carrier 58SB0B / 58SB1B / 58SC0B / 58SC1B (80% single-stage, multi-speed ECM, 4-way multipoise; also PG80MSA, PG80MSLA)
- Bryant 820SA / 821SA (80% single-stage, 4-way multipoise)
- Carrier 58SB0A / 58SB1A / 58SC0A / 58SC1A (single-stage, non-condensing; 58SC is the multi-speed ECM version; also 800SA, 801SA, PG80ESAA, PG80ESLA)
Did you find your code?
One field tip a week
A short, practical HVAC tip in your inbox every week: diagnostics, charging, airflow and code changes. Free, unsubscribe anytime.
We'll only use your email for the newsletter. Privacy policy.
HVAC Cheat Sheet · Free PT charts, code lookups and calculators for techs at hvaccheatsheet.com