Carrier 58TP0B / 58TP1B InteliSense Furnace Codes

Applies to: Carrier 58TP0B / 58TP1B InteliSense (80% two-stage, variable 25-speed ECM, 4-way multipoise). Three-digit display on the furnace control (major.minor code); the LED seen through the door sight glass flashes the major code.

The older 58TP0A / 58TP1A use two-digit codes and have their own chart.

CodeMeaningWhat to check
10.1L1 polarity fault (rapid flash LED): incoming 115 V polarity reversed.Line voltage polarity at each junction; on twinned units, the 24 V transformer phasing.
12.1W on at power up (normal).Blower runs 90 seconds if power comes on during a call for heat, or when R-W opens during the blower on-delay.
13.1Limit lockout: limit, draft safeguard, flame rollout or blocked vent switch open longer than 3 minutes.Auto-resets after 3 hours. See 33.1. How to fix →
14.1Ignition lockout after 4 consecutive ignition tries.Auto-resets after 3 hours. Manifold pressure and firing rate, inlet pressure swings; see 34.1. How to fix →
14.2Flame lost 3 times after 70 seconds of heating.Auto-resets after 3 hours. Manifold pressure and firing rate, inlet pressure swings; see 34.6-34.8. How to fix →
14.3Lockout: 7 loss-of-flame events during one heat request.Manifold pressure and firing rate, inlet pressure swings; see 34.6-34.8. How to fix →
14.4Lockout: low-heat pressure switch (LPS) opened 7 times during one heat request.See 32.2 and 34.1. How to fix →
15.1Lockout: no blower RPM detected.Loose blower wire connections, failed blower motor.
19.1InteliSense communication loss with the thermostat.Not shown until InteliSense communication has been established once. Check the R and Y connections at the control and thermostat; see the thermostat's advanced installation instructions (Carrier.hvacpartners.com/InteliSense).
21.124 VAC sensed on the gas valve when it shouldn't be.Turn off power and wait 5 minutes to retry. Stuck-closed gas valve relay on the control, or a miswire or short on the gas valve wire.
22.1False flame: flame proved while the gas valve is off; inducer runs until it clears.Stuck-open or leaky gas valve.
23.4LPS (low-heat pressure switch) stuck closed.Obstructed pressure tube, or the switch stuck closed (the guide calls this stuck main pressure switch, 23.1). How to fix →
23.5HPS (high-heat pressure switch) stuck closed.Obstructed pressure tube, or the switch stuck closed. How to fix →
24.1Fuse fault.Short in the 24 V wiring, including thermostat leads; disconnect the thermostat leads to isolate it. How to fix →
25.1No program.Reprogram the control with the correct program number from the rating plate (service app or super plug); replace the control if the issue remains.
25.2Corrupted program file.Reprogram the control (service app or super plug).
25.3Twinned units not identical (program numbers don't match).Twinned furnaces must have the same program number; the main unit won't operate.
25.4Main program invalid; running on the backup program.Reprogram the control. It still operates normally.
25.5Installer settings corrupted.Reselect the installer settings or reprogram; runs on default settings meanwhile.
25.6Wrong program; reprogram the control.Reprogram the control with the correct program number from the rating plate (service app or super plug); replace the control if the issue remains.
27.1Super plug program missing, not recognized or corrupted.Remove the super plug and retry; try a different super plug; if it still fails, replace the control.
27.2Super plug program missing, not recognized or corrupted.Remove the super plug and retry; try a different super plug; if it still fails, replace the control.
27.3Super plug program missing, not recognized or corrupted.Remove the super plug and retry; try a different super plug; if it still fails, replace the control.
31.6Open HPS: high-heat pressure switch or relay didn't close or reopened.Control relay may be defective, gas valve miswired; see 32.2. How to fix →
31.7High heat only for the next cycle: HPS failed to close within 75 seconds when going from low to high heat.Control relay may be defective, gas valve miswired; see 32.2. How to fix →
32.2Open LPS: low-heat pressure switch didn't close or reopened.Open longer than 5 minutes: the inducer shuts off 15 minutes before retrying. If the LPS opens within 5 minutes after the gas valve opens, the next cycle is forced to high heat. Vent sizing, low inducer voltage (115 V), low inlet gas pressure (if LGPS used), combustion air, pressure tubing, defective inducer or pressure switch, excessive wind, restricted vent. How to fix →
33.1Main limit circuit open (limit, draft safeguard, flame rollout or blocked vent shutoff switch).Blower runs 4 minutes or until the switch remakes; over 3 minutes it becomes 13.1. Rollout switch and BVSS need a manual reset. Dirty filter or restricted ducts, loose blower wheel, defective switch or connections, defective blower motor or capacitor, combustion air (rollout open), restricted vent, vent sizing, excessive wind. How to fix →
33.2Lockout: high heat only for the current cycle.Same checks as 33.1. How to fix →
34.1Ignition fault: four consecutive ignition trials without proving flame.Low inlet gas pressure, control ground continuity, manual shut-off valve, green/yellow wire connected from the furnace to the burner box screw, flame sensor not grounded or touching the casing. In component test, the igniter should glow orange/white by the end of the 15-second warm-up. How to fix →
34.5Low heat flame lost before the blower on-delay.Low inlet gas pressure, control ground continuity, manual shut-off valve, green/yellow wire connected from the furnace to the burner box screw, flame sensor not grounded or touching the casing. In component test, the igniter should glow orange/white by the end of the 15-second warm-up. How to fix →
34.6Low heat flame lost after the blower on-delay.Low inlet gas pressure, control ground continuity, manual shut-off valve, green/yellow wire connected from the furnace to the burner box screw, flame sensor not grounded or touching the casing. In component test, the igniter should glow orange/white by the end of the 15-second warm-up. How to fix →
34.7High heat flame lost before the blower on-delay.Low inlet gas pressure, control ground continuity, manual shut-off valve, green/yellow wire connected from the furnace to the burner box screw, flame sensor not grounded or touching the casing. In component test, the igniter should glow orange/white by the end of the 15-second warm-up. How to fix →
34.8High heat flame lost after the blower on-delay.Low inlet gas pressure, control ground continuity, manual shut-off valve, green/yellow wire connected from the furnace to the burner box screw, flame sensor not grounded or touching the casing. In component test, the igniter should glow orange/white by the end of the 15-second warm-up. How to fix →
41.1No blower RPM at start-up.Loose blower wire connections, failed blower motor.
41.2No RPM while the blower motor is running.Loose blower wire connections, failed blower motor.
43.1HPS closed before LPS (low-heat switch open while high-heat switch is closed).LPS stuck open, disconnected or obstructed pressure tube, low inlet gas pressure (if LGPS used). How to fix →
45.1Control failure: internal control error (flame circuit fault, memory mismatch or sequence error).Cycle power; if 45 repeats, replace the control.
45.2Control failure: gas valve relay not closing.Cycle power; if 45 repeats, replace the control.
45.3Control failure: micro EEPROM error.Cycle power; if 45 repeats, replace the control.
45.4Control failure: micro loss of communication.Cycle power; if 45 repeats, replace the control.
46.1Momentary loss of power.Heating stops and restarts once the power fluctuation is resolved.
52.1SAT open: supply air temperature sensor connection open.Loose connection at the control board screw terminals, cut or shorted SAT wires, damaged SAT sensor.
52.2SAT short: supply air temperature sensor wires shorted.Loose connection at the control board screw terminals, cut or shorted SAT wires, damaged SAT sensor.
53.1RAT open: return air temperature sensor connection open.RAT firmly plugged into the control board; damaged RAT sensor. (The guide labels the RAT box 52.1/52.2; the service label numbers it 53.)
53.2RAT short: return air temperature sensor shorted.RAT firmly plugged into the control board; damaged RAT sensor.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Carrier 58TP0B/58TP1B Installation, Start-up, Operating and Service and Maintenance Instructions 58TP0B-01SI, Fig. 46 Service Label p. 32, Fig. 52 Troubleshooting Guide pp. 49-50. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.