Trane / American Standard S9X1 / S9X2 / S9B1 Furnace Codes

Applies to: Trane / American Standard S9X1 / S9X2 / S9B1 (96% condensing). Seven-segment display on the integrated furnace control (IFC).

Covers the single-stage S9X1 and S9B1 and the two-stage S9X2. American Standard sells matching models; check the label on the unit.

CodeMeaningWhat to check
E01Loss of IRQ or other internal failure (internal IFC error).Replace the integrated furnace control.
E2.1Retries exceeded: flame never sensed. One-hour lockout after 3 tries.Gas supply, igniter, gas valve, flame sensor. How to fix →
E2.2Recycles exceeded: flame sensed then lost. One-hour lockout after 10 times.Flame sensor, ground, gas pressure, pressure switch dropping out. How to fix →
E2.31st-stage gas valve not energized when it should be, 10 times.Gas valve wiring and the circuit through the limits and pressure switch. How to fix →
E3.11st-stage pressure switch closed when it should be open (shorted).Stuck switch or wiring short. How to fix →
E3.21st-stage pressure switch open when it should be closed.Vent or intake blockage, condensate, hoses, inducer. How to fix →
E3.32nd-stage pressure switch closed when it should be open (S9X2 only). How to fix →
E3.42nd-stage pressure switch open when it should be closed (S9X2 only). How to fix →
E04Open limit: main thermal limit, rollout switch or reverse airflow switch.Airflow first; rollout needs a vent and heat exchanger check. How to fix →
E05Flame detected when it should not be present.Gas valve leaking through or flame sense circuit short. How to fix →
E6.1Line voltage polarity reversed.Swap hot and neutral at the furnace. How to fix →
E6.2Bad grounding: incoming or chassis ground not sensed.Verify the ground to the furnace and control. How to fix →
E6.3Igniter relay fault or igniter open.Igniter and its wiring; replace the control if the relay is stuck. How to fix →
E7.11st-stage gas valve energized when it should be off (24 V present when it shouldn't be).Gas valve wiring; external 24 V fed into the valve circuit.
E08Flame current low but still strong enough to operate.Below about 0.5 microamps DC: clean the flame sensor, check ground. How to fix →
E09Open inducer limit switch or condensate pressure switch.Condensate not draining freely: trap, drain line, hoses.
E11Gas valve circuit fault: valve not energized when it should be, or internal gas valve relay failure.Gas valve wiring; replace the control if the wiring is good.
E12Open fuse (onboard 5 A fuse open or missing).Short in the 24 VAC wiring. How to fix →

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Trane S9X1/S9X2/S9B1 Installation, Operation and Maintenance, FNR-SVX002A-EN (02/2026), Table 43 Error Codes and troubleshooting. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.