Carrier 59SU5A Furnace Codes

Applies to: Carrier 59SU5A (single-stage Ultra Low NOx condensing, upflow/horizontal, 35 in. tall). LED on the furnace control, two-digit status codes.

The newer 59SU5B uses three-digit codes and has its own chart.

CodeMeaningWhat to check
11No previous code.Stored codes are erased automatically after 72 hours. After the component test, 11 means the blower motor tested OK; check the inducer motor and hot surface igniter visually.
12Blower on after power up (115 VAC or 24 VAC).The blower runs 90 seconds if the unit is powered up during a call for heat (R-W closed) or R-W opens during the blower on-delay. If the BTS is also open, the inducer runs too.
13Limit circuit lockout: a limit is open.Auto-resets after three hours. Check for a loose blower wheel, a restricted vent, vent sizing, a dirty filter or restricted ducts, and the switch or its connections. How to fix →
14Ignition lockout.Auto-resets after three hours. See 34. How to fix →
21Gas heating lockout (does NOT auto-reset): 24 VAC sensed at the gas valve when it shouldn't be.Mis-wired gas valve, or a defective control (valve relay).
22Abnormal flame-proving signal: flame is proved while the gas valve is de-energized.The inducer runs until the fault clears. Check for a leaky or stuck-open gas valve.
23Pressure above 0.15 in. w.c. at start-up.Check for an obstruction in the pressure tubing or the transducer vent holes, a defective transducer, and the transducer wiring. How to fix →
24Secondary voltage fuse is open.Short circuit in the 24 VAC wiring. How to fix →
25Invalid model selection or setup error: model plug missing or wrong.If the code flashes 4 times at power-up, the control is using the model selection stored in memory.
26Burner thermal switch (BTS) open.If the switch is open during a call for heat (W), a permanent lockout occurs; cycle power to reset it. Check for a blocked burner inlet or burner mesh, poor inducer flow and excess wind.
31Pressure transducer doesn't sense target pressure, or pressure is out of range.Check for excessive wind, vent sizing, a restricted vent, a defective inducer motor or low inducer voltage (115 VAC), inadequate combustion air, a defective pressure transducer, low inlet gas pressure (if an LGPS is used), a frozen or blocked drain, and disconnected or obstructed pressure tubing. How to fix →
34Ignition proving failure: the control tries ignition four times before lockout 14.If the flame signal is lost during the blower on-delay, the blower runs for the selected off-delay. Check for oxide on the flame sensor (clean with fine steel wool), flame current (0.5 microamps DC minimum, 4.0-6.0 nominal), the manual shut-off valve, low inlet gas pressure, control ground continuity, a defective or turned-off gas valve, a flame sensor that is grounded or touching the casing, and poor flame carryover or rough ignition. The green/yellow wire must be connected to the furnace sheet metal. How to fix →
42Inducer motor fault: no RPM pulses within 20 seconds of a heat request, inducer outside its valid range, RPM signal lost for 5 seconds, or inducer above its model-specific RPM limit.Check vent sizing, a restricted combustion air supply, a failed inducer motor, loose or bad motor wiring, and a frozen or blocked drain. After the component test, also check the inducer, wiring, furnace control and tubing for poor connections.
45Control circuitry lockout: gas valve relay stuck open, flame sense circuit failure or software check error.Auto-resets after one hour. Reset power to clear the lockout; replace the control if the code repeats.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Carrier 59SU5A Installation, Start-up, Operating and Service Maintenance Instructions 59SU5A-05SI, Fig. 61 Service Label Information p. 51 (read at 450 dpi). The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.