Home / Charts / Goodman / Amana furnace codes

Goodman / Amana GKS9 / AKSS92 Furnace Codes

Applies to: Goodman / Amana GKS9 / AKSS92 (92% single-stage upflow: GKS9, Amana AKSS92). Single red diagnostic LED on the integrated control module.

CodeMeaningWhat to check
NoneNo signal: furnace doesn't run.No 115 V or 24 V at the control (disconnect off, door switch open, 24 V wires loose), blown fuse or breaker, or an internal control fault. Check the 3 A fuse (replace only with a 3 A automotive fuse) and look for shorts in the 115 V and 24 V circuits. How to fix →
Steady onNormal operation.None.
1 flashLockout after too many ignition retries (3 total).Failure to establish flame (no gas, front cover pressure switch stuck open, bad igniter or alignment, wrong orifices, coated or oxidized sensor) or loss of flame (interrupted gas, lazy flames from gas pressure or flue/combustion air restriction, front cover pressure switch opening, weak inducer). Goodman says to sand a coated sensor with emery cloth. How to fix →
2 flashesPressure switch circuit closed while the inducer isn't running.Inducer pressure switch contacts sticking, or a short in the pressure switch circuit. How to fix →
3 flashesPressure switch circuit not closed with the inducer running; inducer runs continuously.Pressure switch hose blocked, pinched or misconnected; blocked flue or inlet pipe, blocked drain system or weak inducer; wrong setpoint or bad contacts; loose wiring. How to fix →
4 flashesPrimary or auxiliary limit open; circulator blower runs continuously.Faulty limit; not enough air over the heat exchanger (blocked filters, restrictive ductwork, wrong blower speed, failed blower); loose wiring. How to fix →
5 flashesFlame sensed with no call for heat; inducer and circulator run continuously.Short to ground in the flame sense circuit (sensor or wiring).
6 flashesRollout limit open; circulator blower runs continuously.Flame rollout, misaligned burners, blocked flue or inlet pipe, failed inducer, loose wiring, or a faulty rollout limit. How to fix →
7 flashesLow flame sense microamp signal (furnace still runs).Coated or oxidized sensor, sensor out of position, or lazy flame from wrong gas pressure or combustion air. Sand the sensor, check alignment and inlet piping, compare gas pressure with the rating plate. How to fix →
C (continuous rapid flash)115 V or 24 V polarity reversed.115 V polarity reversed at the furnace or control, the orange and gray transformer wires reversed, or a poor unit ground.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Goodman GKS9 / Amana AKSS92 Single Stage Up-Flow Gas Furnaces Service Instructions RS6612004 Rev. 2 (2014), Troubleshooting Chart pp. 49-50. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.