York White-Rodgers Board Furnace Codes

Applies to: York White-Rodgers Board (the generation before the 2009 UTEC boards; 265901, S1-33109167000 / 265902, S1-33109168000 / 265903, S1-33109169000 / 265904). LED on the White-Rodgers furnace control board that flashes red, green or amber.

Johnson Controls also sells furnaces under the Coleman and Luxaire names. Codes match only when the control board is the same, so check the board's part number and the label inside the blower door.

CodeMeaningWhat to check
Steady offNo power to the board. Fault codes are possible with a blown on-board fuse. How to fix →
Green heartbeatNormal operation, no call for heat.
1 amberNormal operation with call for heat (first stage on two-stage boards).
2 amberTwo-stage boards: normal operation with call for second-stage heat.
3 amberTwo-stage boards: W2 present with no W1. How to fix →
4 amberY present with no G call. How to fix →
Rapid amber flashLow flame sense current. How to fix →
Solid redInternal gas valve error, micro and frequency check.
Rapid red flashTwinning error, incorrect 24 V phasing.
1 redFlame sensed when no flame should be present. Stored. How to fix →
2 redPressure switch stuck closed, or inducer error. Stored. How to fix →
3 redFirst-stage pressure switch stuck open, or inducer error. Stored. How to fix →
3 double redTwo-stage boards: second-stage pressure switch stuck open, or inducer error. Stored. How to fix →
4 redOpen limit switch. Stored. How to fix →
5 redOpen rollout or open fuse detected. Stored; hard lockout. How to fix →
6 redPressure switch cycle lockout. Stored; one-hour soft lockout. How to fix →
7 redExternal lockout (retries). Stored; one-hour soft lockout. How to fix →
8 redExternal lockout (recycles). Stored; one-hour soft lockout. How to fix →
9 redGrounding or reversed polarity, or transformer leads reversed.
10 redGas flow with no call for heat. Stored.
11 redLimit switch open more than 5 minutes (blower failure). Stored; hard lockout. How to fix →
12 redIgniter failure. How to fix →

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: York Service Tips ST-045-09 (September 2, 2009), Last Generation W/R Emerson IFC Boards fault code sheet, p. 6, and p. 1. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.