Goodman / Amana GR9T80 / GD9T80 / GR9T96 / GD9T96 Furnace Codes

Applies to: Goodman / Amana GR9T80 / GD9T80 / GR9T96 / GD9T96 (R-32 era two-stage, nine-speed ECM; also AR9T80, AD9T80, AR9T96, AD9T96, DR80TN, DD80TN, DR96TN, DD96TN). Three-character seven-segment display on the integrated control.

Covers Goodman GR9T80/GD9T80 and Amana AR9T80/AD9T80 (RS6621304 Rev. 1, pp. 34-36) and Goodman GR9T96/GD9T96 and Amana AR9T96/AD9T96 (RS6612304 Rev. 1, pp. 26-28). Daikin's DR80TN/DD80TN (RSD6621304 Rev. 1, pp. 35-37) and DR96TN/DD96TN (RSD6612304 Rev. 1, pp. 25-27) service instructions list the same codes and fault descriptions. The R-32 single-stage models have their own chart, as does the older R-410A GM9C96/GC9C96.

CodeMeaningWhat to check
IdLIdle: normal operation.
nonENo display: no 120 VAC to the furnace or no 24 V to the integrated control.Breaker, manual disconnect and door switch; 120 VAC on the transformer primary and 24 V on the secondary; 24 V wires to the 12-pin harness. Replace the control only after the wiring checks out.
EbLCirculator blower motor drawing very little current after the heat-on delay (hard lockout).Loose blower motor connections; the motor's 120 V L1 wire must be on the CIRC-H terminal of the control; blower voltage, amps and speed setting; replace the motor if needed.
EbUCirculator blower motor drawing too much current during inducer pre-purge (hard lockout).Blower motor power wiring reversed on the control; loose or miswired connections.
Ed8Invalid call: check the ODS setting.Set ODS and TON airflow to match the outdoor unit, with the system set to IdL first.
EE0Lockout after too many ignition retries (3 total): failure to establish flame, or loss of flame after it was established.Gas supply and pressure; front cover pressure switch and drainage; igniter and its alignment; restricted orifices; flame sensor (clean with steel wool); flue blockage, length and elbows; combustion air; inducer performance. How to fix →
EE1Low-stage pressure switch circuit closed at the start of the heating cycle.Sticking switch contacts or a short in the switch wiring. How to fix →
EE2Low-stage pressure switch circuit open; the inducer runs with no further operation.Pressure switch hose blocked, pinched or misconnected; blocked flue or inlet pipe; blocked drain system; weak inducer; wrong switch set point or bad contacts; loose wiring. How to fix →
EE3Primary limit circuit open; the circulator blower runs with no furnace operation.Blocked filters or restrictive ductwork; blower speed and motor; loose wiring in the limit circuit. Check the temperature rise against the specification sheet. How to fix →
EE4Flame sensed with no call for heat; inducer and circulator run continuously.Short to ground in the flame sense circuit, a lingering burner flame, or a slow-closing gas valve. How to fix →
EE5Open fuse.Replace the fuse (3-amp automotive type) and find the short in the low-voltage wiring, or the back of the control touching the mounting panel because standoffs are missing. How to fix →
EE6Low flame sense microamp signal (furnace still runs).Clean a coated or oxidized flame sensor; check its position in the flame; check the inlet air piping for blockage, length, elbows and termination; compare gas pressure with the rating plate. How to fix →
EE7Problem with the igniter circuit.Wiring from the control to the igniter; a shorted igniter; the furnace ground; the igniter output from the control (igniter relay fault). How to fix →
EE8High-stage pressure switch circuit closed at the start of the heating cycle; the furnace won't run on high stage but runs normally on low.Sticking high-stage switch contacts or a short in the switch wiring. How to fix →
EE9High-stage pressure switch circuit open; the furnace won't run on high stage but runs normally on low.Pressure switch hose blocked, pinched or misconnected; blocked flue or inlet pipe; blocked drain system; weak inducer; wrong switch set point or bad contacts; loose wiring. How to fix →
E10Grounding fault.Poor neutral connection: verify the neutral wire to the furnace and continuity to the ground source.
E11Open rollout switch.Gas pressure too high, misaligned burners, or a restricted heat exchanger or vent. How to fix →
EEA115 VAC polarity reversed.Correct the polarity per the wiring diagram and verify the furnace ground.
EEbThe control is not energizing the gas valve when it should.Check the gas valve circuit wiring; if it is good, replace the integrated control. Goodman says not to replace the gas valve for this code.
EECGas valve energized when it should be off.Cycle 120 VAC. If EEC stays, it is a wiring problem outside the control: inspect the system wiring and replace the system harness; if EEC still stays, replace the control.
EEEThe control has detected an internal fault.Power off for at least 3 minutes and back on; inspect the 120 V and 24 V wiring and the ground. Replace the control; don't replace other parts based on this code.
EEHTwinning error.Both furnaces must be on the same 120 VAC from the breaker panel. Disconnect the twinning wire and power both: a control that still shows EEH alone is the one to replace. Reconnect, check the twinning wire, then give G to the main furnace and confirm the twinned blower follows at the same speed.
EEJInducer motor relay error in the control.Replace the integrated control; don't replace other parts based on this code.
EELProblem with the igniter circuit.Wiring from the control to the igniter; a shorted igniter; the furnace ground; the igniter output from the control (igniter relay fault). How to fix →
EEnIgniter open.Loose or incorrect wiring from the control to the igniter, or a damaged igniter. How to fix →
EAFLost communication with the R-32 sensor; the furnace is in mitigation mode (fan only).The furnace may not be paired with an R-32 cooling unit: see the manual's R-32 information section. Otherwise check the sensor wire and connection, and replace the sensor if needed.
EALThe R-32 sensor has detected a refrigerant leak; mitigation mode (fan only).Look for a leak at the indoor coil. Heating resumes once no leak is detected and the 5-minute delay is over.
EASThe R-32 sensor has detected a fault; mitigation mode (fan only).Check the R-32 sensor and replace it if necessary.
EArThe control has detected a problem with its internal A2L relay and is running mitigation mode.Disconnect any wire on the control's ALARM terminal and cycle power. If the code clears, repair the ALARM wiring; if not, replace the control.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Goodman Service and Troubleshooting, GR9T96/GD9T96 and Amana AR9T96/AD9T96 Two Stage Furnace with Nine Speed ECM Motor, RS6612304 Rev. 1, 2 Stage Troubleshooting Codes pp. 26-28 (read from page images). The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.