Goodman / Amana GMVC96 / GCVC96 BB ComfortBridge Furnace Codes

Applies to: Goodman / Amana GMVC96 / GCVC96 BB ComfortBridge (96%, BB revision: GMVC96, GCVC96, Amana AMVC96, ACVC96). Seven-segment display on the ComfortBridge integrated control.

This chart is for the BB revision with the ComfortBridge control, which adds supply and return air sensor codes and R-32 leak mitigation codes. The BA revision has its own chart; check the revision letters in the model number.

CodeMeaningWhat to check
IdLIdle, normal operation.None.
nonENo display: no 115 V or 24 V to the control, blown fuse or tripped breaker, or a non-functional control.Check 115 V to the furnace and control (disconnect, door switch, a supply shared with other devices), look for shorts in the 115 V circuit, replace a dead control. How to fix →
EEEInternal control fault.Alarm table only (no symptoms row).
Eb0Circulator blower motor not running when it should be.Loose motor power or control leads, open circuit or loose connection at the inductor (3/4 and 1 HP models), or a failed motor.
Eb1Control lost communication with the circulator blower motor.Loose motor control leads, failed motor, or failed control.
Eb2Blower motor horsepower in the shared data doesn't match the motor.Make sure the motor horsepower is right for the model and the shared data is correct; re-populate with the CoolCloudHVAC app if needed.
Eb3Blower motor in a power, temperature or speed limit (reduced airflow).Blocked filters, restrictive or undersized ductwork, high ambient temperature; all registers open. How to fix →
Eb4Blower motor lost rotor control or senses high current.Abnormal motor loading or sudden blockage of the furnace air inlet or outlet: check filters, grilles, registers and ducts. How to fix →
Eb5Blower motor failed to start 10 times in a row.Obstruction in the blower housing, seized bearings or a failed motor.
Eb6Blower motor shut down for over or under voltage, or over temperature on its power module.Line voltage within the rating plate range; high ambient temperature.
Eb7Blower motor lacks the information to run, or failed to start 40 times in a row.Make sure the control has the correct shared data; check for a locked rotor.
Eb9Airflow lower than demanded.Blocked filters, restrictive or undersized ductwork, high ambient temperature; all registers open. How to fix →
Ed0Data not yet on network.Populate the shared data set using the CoolCloudHVAC app.
Ed1Invalid shared data.Make sure the shared data is right for the model; re-populate it with the app.
EE0Lockout after too many ignition retries (3 total).Gas interruption, front cover pressure switch, igniter, flame signal (clean the sensor with steel wool), flue piping, inducer performance. How to fix →
EE1Low stage pressure switch closed at the start of the heating cycle.Switch contacts sticking or a short in the switch wiring. How to fix →
EE2Low stage pressure switch open; inducer runs continuously.Switch hose, flue and inlet piping, drain system, weak inducer, setpoint or contacts, wiring. How to fix →
EE3Primary limit open; circulator runs continuously.Filters and ductwork, blower speed and performance, wiring in the high limit circuit. How to fix →
EE4Flame sensed with no call for heat.Short to ground at the flame sensor or wiring, a lingering flame, or a slow-closing gas valve.
EE5Open fuse.Find the short in the low voltage wiring; replace the fuse with a 3 A automotive type. How to fix →
EE6Low flame sense signal (furnace still runs).Clean the sensor (steel wool), check alignment, inlet air piping and gas pressure against the rating plate. How to fix →
EE7Igniter circuit problem.Igniter wiring, shorted igniter, furnace ground, igniter relay on the control. How to fix →
EE8High stage pressure switch closed at the start of the heating cycle; runs on low stage only.Switch contacts sticking or a short in the wiring. How to fix →
EE9High stage pressure switch open; runs on low stage only.Switch hose, flue and inlet piping, drain system, inducer performance, setpoint or contacts, wiring. How to fix →
EEA115 V polarity reversed, or poor furnace ground.Correct the polarity per the wiring diagram; verify the ground.
EEbGas valve not energized when it should be (external gas valve error).Miswired or open gas valve circuit, or the control's gas valve relay stuck open.
EECGas valve energized when it should not be (internal gas valve error).Miswired or shorted gas valve wiring, or the control's gas valve relay.
EEdAux limit switch (blower compartment) open.115 V shut off during a heat cycle, or not enough air (filters, ductwork, blower speed or failed blower), or wiring. How to fix →
EEFAux switch (condensate switch) open.High water in the evaporator coil drain pan or auxiliary pan: check the drain pan, trap, piping and auxiliary pan.
E10Grounding fault.Poor neutral: verify the neutral connection to the furnace and continuity to ground.
E11Open rollout switch.Gas pressure too high, misaligned burners, restricted heat exchanger or venting. How to fix →
E12Redundant relay open.Alarm table only.
E13Redundant relay stuck closed.Alarm table only.
E15External return air temperature sensor circuit open.Make sure the probe is plugged in all the way and its connector is crimped properly; the probe should read 10k ohms at 77°F (lower when warmer, higher when cooler). Replace the PCB if the rest checks out.
E16External return air temperature sensor circuit shorted.Check the probe terminals and conductors for a short; if the error shows with the probe unplugged, check the PCB connector; replace the PCB.
E17External supply air temperature sensor circuit open.Make sure the probe is plugged in all the way and crimped properly; it should read 10k ohms at 77°F. Replace the PCB if the rest checks out.
E18External supply air temperature sensor circuit shorted.Check the probe terminals and conductors for a short; if the error shows with the probe unplugged, check the PCB connector; replace the PCB.
E19Onboard return air temperature sensor unplugged.Power cycle (allow up to 90 seconds), check the PCB for visible damage at the onboard sensor (R311), replace the PCB.
E1AOnboard return air temperature sensor shorted.Power cycle (allow up to 90 seconds), make sure nothing on the PCB is shorting the onboard sensor (R311), replace the PCB.
EAFLost communication with the R-32 sensor; furnace in mitigation mode (fan only).The furnace may not be paired with an R-32 cooling unit (see the R-32 section of the manual). Check the R-32 sensor wire connection and wire; replace the sensor if needed.
EA0R-32 sensor detected a refrigerant leak; furnace in mitigation mode (fan only).Look for a refrigerant leak at the indoor coil. Normal operation resumes once no leak is detected and the 5-minute delay is over.
EA1R-32 sensor fault; furnace in mitigation mode.Check the R-32 sensor; replace it if needed.
EA2The control board's A2L relay detected a fault; furnace in mitigation mode.Check the A2L relay, cycle power, replace the control if needed.
EC1Network communication alarm.Alarm table only.
EC2E-Module network communication alarm.Alarm table only.
EC3Bluetooth module network communication alarm.Alarm table only.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Goodman/Amana 34.5" Chassis ACVC96*BB/AMVC96*BB/GCVC96*BB/GMVC96*BB Gas Furnaces Service and Troubleshooting manual RS6612023 Rev. 2 (2026), Alarm Code Definition Table p. 36, Troubleshooting pp. 40-44. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.