Carrier 58SU0A Furnace Codes

Applies to: Carrier 58SU0A (80% single-stage, ECM blower, Ultra Low NOx, 4-way multipoise; also 830SA). LED on the furnace control, two-digit status codes.

The newer 58SU0B uses three-digit codes and has its own chart. Bryant's manuals print the identical service label: Bryant 830SA (II830SA-06, p. 27).

CodeMeaningWhat to check
11No previous code.Stored codes are erased automatically after 72 hours. After the component test, 11 means the blower motor tested OK; check the inducer motor and hot surface igniter visually.
12Blower on after power up (115 VAC or 24 VAC).The blower runs 90 seconds if the unit is powered up during a call for heat (R-W closed) or R-W opens during the blower on-delay.
13Limit circuit lockout: a limit, draft safeguard, burner thermal switch or blocked vent switch (if used) is open.Auto-resets after three hours. Check for a loose blower wheel, a restricted vent, vent sizing, excess wind, a dirty filter or restricted ducts, the switch or its connections, and inadequate combustion air (burner thermal switch open). How to fix →
14Ignition lockout.Auto-resets after three hours. See 34. How to fix →
21Gas heating lockout (does NOT auto-reset): 24 VAC sensed at the gas valve when it shouldn't be.Mis-wired gas valve, or a defective control (valve relay).
22Abnormal flame-proving signal: flame is proved while the gas valve is de-energized.The inducer runs until the fault clears. Check for a leaky or stuck-open gas valve.
23Pressure above 0.15 in. w.c. at start-up.Check for an obstruction in the pressure tubing or the transducer vent holes, a defective transducer, and the transducer wiring. How to fix →
24Secondary voltage fuse is open.Short circuit in the 24 VAC wiring. How to fix →
25Invalid model selection or setup error: model plug missing or wrong.If the code flashes 4 times at power-up, the control is using the model selection stored in memory.
31Pressure transducer doesn't sense target pressure, or pressure is out of range.Check for excessive wind, vent sizing, a restricted vent, a defective inducer motor or low inducer voltage (115 VAC), inadequate combustion air, a defective pressure transducer, low inlet gas pressure (if an LGPS is used), and disconnected or obstructed pressure tubing. How to fix →
34Ignition proving failure: the control tries ignition four times before lockout 14.If the flame signal is lost during the blower on-delay, the blower runs for the selected off-delay. Check for oxide on the flame sensor (clean with fine steel wool), flame current (0.5 microamps DC minimum, 4.0-6.0 nominal), the manual shut-off valve, low inlet gas pressure, control ground continuity, a defective or turned-off gas valve, a flame sensor that is grounded or touching the casing, and poor flame carryover or rough ignition. The green/yellow wire must be connected to the furnace sheet metal. How to fix →
42Inducer motor fault: no RPM pulses within 20 seconds of a heat request, inducer outside its valid range, or RPM signal lost for 5 seconds.Check vent sizing, a restricted combustion air supply, a failed inducer motor, and loose or bad motor wiring. After the component test, also check the inducer, wiring, furnace control and tubing for poor connections.
45Control circuitry lockout: gas valve relay stuck open, flame sense circuit failure or software check error.Auto-resets after one hour. Reset power to clear the lockout; replace the control if the code repeats.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Carrier 58SU0A Installation, Start-up, Operating and Service and Maintenance Instructions 58SU0A-06SI, Fig. 35 Service Label (345641-201 Rev. C) p. 27 (read at 450 dpi). The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.