Home / Charts / Goodman / Amana furnace codes

Goodman / Amana GMVS80 U Ultra-Low NOx Furnace Codes

Applies to: Goodman / Amana GMVS80 U Ultra-Low NOx (80% single-stage, variable-speed communicating: GMVS80, Amana AMVS80). Seven-segment display on the integrated control.

CodeMeaningWhat to check
IdLNormal operation.None.
NoneNo display: no 115 V or 24 V to the control, blown fuse or tripped breaker, or a dead control.Restore power, or replace the control. How to fix →
d0Equipment lacks shared data.Populate the shared data set using the CoolCloudHVAC app.
Eb0Circulator blower motor not running when it should be.Wiring connections, continuity through the inductor (replace if open or shorted), the blower motor.
Eb1Control lost communication with the circulator blower motor.Wiring connections, the blower motor, the control.
Eb2Blower motor horsepower in the shared data doesn't match the motor.Make sure the motor horsepower matches the nameplate; make sure the shared data is right for the model and repopulate it with the correct memory card if needed.
Eb3Blower motor running in a power, temperature or speed limiting condition (reduced performance, low airflow).Filters, ductwork (blockage, registers fully open), duct sizing. How to fix →
Eb4Blower motor senses a loss of rotor control (high current).Filters, filter grille, registers, duct system and equipment inlet/outlet for blockage; correct and retest. How to fix →
Eb5Blower motor failed to start 10 times in a row.Obstructions at the blower; repair or replace the motor or wheel; check shaft rotation.
Eb6Blower motor shut down for over or under voltage, or for over temperature on its power module.Supply voltage to the furnace within the nameplate range.
Eb7Blower motor lacks information to operate, or failed to start 40 times in a row.Locked rotor; make sure the control's shared data is populated correctly.
Eb9Airflow lower than demanded (reduced performance, or low stage when high stage is expected).Filters, ductwork blockage and registers, duct sizing. How to fix →
E1bAPS reference error: sensor reference out of range (5.0 ±0.2 V) for 5 seconds.Electrical connections to the pressure sensor. How to fix →
E1CAPS null error: inconsistent pressure reading with the inducer off.Electrical connections to the pressure sensor. How to fix →
E1dAPS span error: inconsistent pressure reading with the inducer on.Electrical connections to the pressure sensor. How to fix →
E1EAnalog pressure error (blocked vent).For 5 seconds the pressure couldn't reach target at the inducer's maximum RPM, or stayed beyond target at its minimum RPM: a blocked vent, or an APS fault holding the reading. Check the vent, then the APS sensor and its connection. How to fix →
E1FAPS input error: sensor voltage out of range for 5 seconds.Check the APS sensor and its connection. Valid ranges: 0.25 to 4 V with 2" selected, 0.5 to 4.5 V with 4" selected (each ±0.06 V). How to fix →
E10Grounding fault or poor neutral connection.Neutral connection to the furnace and continuity to ground.
E11Open rollout switch.Gas pressure, burner alignment, burner restriction. How to fix →
Ed0Data not yet on network.Populate the shared data set using the CoolCloudHVAC app.
Ed1Invalid shared data.Make sure the shared data is right for the model; repopulate it with the CoolCloudHVAC app.
EE0Lockout after too many ignition retries (3 total).Gas interruption, front cover pressure switch and drainage, igniter, flame signal (sand a coated sensor), flue piping, inducer performance. How to fix →
EE1Low stage pressure switch closed at the start of the heating cycle.Switch contacts sticking or a short in the wiring. How to fix →
EE2Low stage pressure switch not closed; inducer runs continuously.Switch hose, flue and inlet piping, drain system, inducer performance, switch operation, wiring. How to fix →
EE3Primary limit open; circulator runs continuously.Filters and ductwork, blower speed and performance, wiring. How to fix →
EE4Flame sensed with no call for heat.Short at the flame sensor or its wiring; lingering or lazy flame; gas valve operation.
EE5Open fuse.Find the short in the low voltage wiring, then replace the fuse. How to fix →
EE6Low flame sense signal (furnace still runs).Clean the sensor, check alignment, inlet air piping and gas pressure against the rating plate. How to fix →
EE7Igniter circuit problem.Igniter wiring, shorted igniter, unit ground, igniter output from the control. How to fix →
EE8High stage pressure switch closed at the start of the heating cycle.Diagnose and replace the high stage switch if needed; repair any short. How to fix →
EE9High stage pressure switch not closed; runs on low stage only.Switch hose, flue and inlet piping, drain system, inducer performance, wiring. How to fix →
EEA115 V polarity reversed, or poor unit ground.Correct the polarity and verify the ground.
EEbGas valve not energized when it should be (external gas valve error).Gas valve circuit wiring; replace the control if the wiring is good.
EECGas valve energized when it should not be (internal gas valve error).Gas valve circuit wiring; replace the control if the wiring is good.
EEdAux limit switch (blower compartment) open.Filters and ductwork, blower speed and performance, wiring. How to fix →
EEFAux switch (condensate switch) open.Evaporator drain pan, trap and piping.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Goodman/Amana *MVS80*U Single Stage Variable Speed Ultra-Low NOx Gas Furnaces Service and Troubleshooting manual RS6612019 Rev. 4 (2026), Menu options p. 27, Status codes p. 28, Troubleshooting pp. 29-31. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.