HVAC Cheat Sheethvaccheatsheet.com/charts/furnace-codes/carrier-59tn7a
Carrier 59TN7A two-stage condensing Furnace Codes
| Code | Meaning | What to check |
|---|---|---|
| 10.1 | L1 polarity fault (LED flashes rapidly). | Check line voltage polarity and ground; the furnace won't run with reversed polarity. |
| 10.2 | Refrigerant leak detected; blower runs. | The control runs the blower in response to a refrigerant leak signal. |
| otA | Firmware install in process. | Wait for the install to finish. |
| btL | Failed to load; retry the firmware install. | Retry the firmware install. |
| 12.1 | W on at power-up. | Normal: the blower runs 90 seconds if the unit is powered up during a heat call (R-W closed) or when R-W opens during the blower on-delay. |
| 13.1 | Limit lockout: the limit, draft safeguard, flame rollout or blocked vent switch (if used) open longer than 3 minutes. | Auto-resets after 3 hours. See 33.1: dirty filter or restricted ducts, loose blower wheel, defective switch or connections, defective blower motor, wrong gas input. How to fix → |
| 14.1 | Ignition lockout after 4 consecutive ignition tries. | Auto-resets after 3 hours. See 34.1. How to fix → |
| 14.2 | Flame lost 3 times after 70 seconds of heating. | See 34.x for flame checks. How to fix → |
| 14.3 | Lockout: 7 loss-of-flame events during a heat call. | See 34.x for flame checks. How to fix → |
| 14.4 | Lockout: 7 pressure switch open events during a heat call. | See 31.6/31.7 for pressure switch checks. How to fix → |
| 15.1 | Blower lockout: no blower RPM detected. | Check for loose blower wire connections and a failed blower motor. How to fix → |
| 15.2 | Lockout: blower failed to reach 500 RPM at start-up. | Check for loose blower wire connections and a failed blower motor. How to fix → |
| 17.1 | Lost Bluetooth module (BTM) communication. | Carrier gives no further steps. |
| 21.1 | 24 VAC sensed on the gas valve when it shouldn't be; power reset only. | Turn off power and wait 5 minutes to retry. Check for a stuck-closed gas valve relay on the control and a miswire or short at the gas valve wire. |
| 22.1 | False flame: flame proved while the gas valve is off. | The inducer runs until the fault clears. Check for a stuck-open or leaky gas valve. How to fix → |
| 23.4 | Low pressure switch (LPS) stuck closed. | Check for an obstructed pressure tube and a pressure switch stuck closed. How to fix → |
| 23.5 | High pressure switch (HPS) stuck closed. | Check for an obstructed pressure tube and a pressure switch stuck closed. How to fix → |
| 24.1 | Fuse fault. | Look for a short in the 24 V wiring, including thermostat leads. Disconnect the thermostat leads to isolate it. How to fix → |
| 25.1 | No program in the control; no heating. | If the program in the control is missing, not recognized or corrupted, reprogram the control with the program number on the rating plate (service app or super plug). Replace the control if the problem remains. |
| 25.2 | Corrupted program file; no heating. | Reprogram the control with the service app or a super plug. If the program in the control is missing, not recognized or corrupted, reprogram the control with the program number on the rating plate (service app or super plug). Replace the control if the problem remains. |
| 25.4 | Main program invalid; running on the backup program. | The control still runs normally. Reprogram it to correct the problem. |
| 25.5 | Installer settings corrupted. | Reselect the installer settings or reprogram the control. It runs on default installer settings meanwhile. |
| 25.6 | Wrong program for this control; no heating. | Reprogram the control so the program matches the control used. |
| 27.1 | Program in the super plug missing, not recognized or corrupted. | Remove the super plug and retry. If you still get a 27 code, try a different super plug. If that fails, replace the control. |
| 27.2 | Program in the super plug missing, not recognized or corrupted. | Remove the super plug and retry. If you still get a 27 code, try a different super plug. If that fails, replace the control. |
| 27.3 | Program in the super plug missing, not recognized or corrupted. | Remove the super plug and retry. If you still get a 27 code, try a different super plug. If that fails, replace the control. |
| 31.6 | Open high pressure switch (HPS). | Check for a secondary pressure switch that failed to close after three trials, excessive wind, a restricted vent, a defective inducer motor, low inlet gas pressure (if a low gas pressure switch is used), inadequate combustion air, proper vent sizing, disconnected or obstructed pressure tubing, and restricted or blocked condensate drainage. If it opens during the blower on-delay, the blower comes on for the selected off-delay. Carrier's troubleshooting guide: the secondary (HPS) switch didn't close for one minute after the gas valve opened, or reopened. How to fix → |
| 31.7 | High heat only for the next cycle: HPS failed to close in 75 seconds going from low to high heat. | Check for a secondary pressure switch that failed to close after three trials, excessive wind, a restricted vent, a defective inducer motor, low inlet gas pressure (if a low gas pressure switch is used), inadequate combustion air, proper vent sizing, disconnected or obstructed pressure tubing, and restricted or blocked condensate drainage. If it opens during the blower on-delay, the blower comes on for the selected off-delay. How to fix → |
| 32.2 | Open low pressure switch (main pressure switch). | If the LPS is open longer than 5 minutes or has reopened, the inducer shuts off for 15 minutes before retrying. If the low-heat switch opens within 5 minutes after the gas valve turns on, the next cycle is forced to high heat (32.2 stays shown during it). Troubleshoot as 31.6 and 31.7. How to fix → |
| 33.1 | Main limit circuit open (limit or flame rollout). | The blower runs 4 minutes or until the switch recloses, whichever is longer. Open longer than 3 minutes changes to lockout 13. The flame rollout switch and BVSS need a manual reset. Check for a dirty filter or restricted ducts, loose blower wheel, defective switch or connections, defective blower motor, wrong gas input. How to fix → |
| 34.1 | Ignition fault: four consecutive ignition trials failed. | First check the gas valve and manual shutoff are on, the green/yellow wire is connected to the furnace sheet metal, and the flame sensor isn't grounded. Then remove R and run the component test: the igniter should glow orange/white by the end of the 15-second warm-up. If not, unplug the igniter harness and rerun: no 115 V between pin 1 and NEUTRAL-L2 means replace the control; 115 V present means check the harness and igniter. How to fix → |
| 34.5 | After successful ignition: low heat flame lost before the blower on-delay. | Check flame current during trial for ignition: nominal 4.0-6.0 µA. Below 0.5, clean the sensor with fine steel wool and recheck; if still low, replace the electrode. If current is near normal and the burners still won't stay on, replace the control. How to fix → |
| 34.6 | Low heat flame lost after the blower on-delay. | Same flame checks as 34.5. How to fix → |
| 34.7 | High heat flame lost before the blower on-delay. | Same flame checks as 34.5. How to fix → |
| 34.8 | High heat flame lost after the blower on-delay. | Same flame checks as 34.5. (Carrier's troubleshooting guide words 34.5-34.8 differently from the service label; this chart follows the label.) How to fix → |
| 41.1 | No blower RPM at start-up. | Check for loose blower wire connections and a failed blower motor. How to fix → |
| 41.2 | No RPM while the blower motor is running. | Check for loose blower wire connections and a failed blower motor. How to fix → |
| 41.3 | Blower failed to reach 500 RPM at start-up. | Check for loose blower wire connections and a failed blower motor. How to fix → |
| 43.1 | HPS closed before LPS. | Check the pressure switches and tubing. How to fix → |
| 45.1 | Control failure: flame circuit fault, memory mismatch or sequence error (1 hour). | Cycle power. If code 45 repeats, replace the control. |
| 45.2 | Control failure: gas valve relay won't close. | Cycle power. If code 45 repeats, replace the control. |
| 45.3 | Control failure: EEPROM memory error (1 hour). | Cycle power. If code 45 repeats, replace the control. |
| 45.4 | Control failure: micro loss of communication. | Cycle power. If code 45 repeats, replace the control. |
| 51.1 | Outdoor air temperature sensor open. | Check for a loose connection at the control board screw terminals, cut or shorted sensor wires, and a damaged sensor. |
| 51.2 | Outdoor air temperature sensor shorted. | Check for a loose connection at the control board screw terminals, cut or shorted sensor wires, and a damaged sensor. |
| 52.1 | Supply air temperature sensor open. | Check for a loose connection at the control board screw terminals, cut or shorted sensor wires, and a damaged sensor. |
| 52.2 | Supply air temperature sensor shorted. | Check for a loose connection at the control board screw terminals, cut or shorted sensor wires, and a damaged sensor. |
| 53.1 | Return air temperature sensor open. | Make sure the RAT sensor is firmly plugged into the control board; check for a damaged sensor. |
| 53.2 | Return air temperature sensor shorted. | Make sure the RAT sensor is firmly plugged into the control board; check for a damaged sensor. |
How to read the codes
- The display shows major.minor: the first two digits are the major code, the third the minor. The door LED flashes only the major code: short flashes for the first digit, long flashes for the second.
- Normal displays: iDL idle, Ht2/Ht1 high/low heat, CL2/CL1 high/low cooling, HPd heat pump defrost, CFn/CF2/CF3 continuous fan, ##.# active status code.
- Stored faults: with 115 V on, no thermostat signal and all blower-off delays done, hold the blower door switch in and press MENU until FLt shows, then NEXT to step through the last 7. Clear them with CLr. Faults stay in memory for 72 hours of powered operation.
- Flame current: nominal 4.0 to 6.0 µA DC; below 0.5 during trial for ignition means clean the sensor with fine steel wool and recheck. Carry-over gap is .045 in. nominal.
- Gas supply pressure must be at least 4.5 in. w.c. (0.16 psig) and no more than 14 in. w.c. (0.5 psig).
Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.
Source: Carrier 59TN7A Installation, Start-up, Operating, Service and Maintenance Instructions 59TN7A-01SI (01/25), service label Fig. 61 p. 55 (read at 400 dpi), troubleshooting guide pp. 74-75. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.
Related
- How to read furnace LED flash codes
- Furnace pressure switch troubleshooting
- Flame sensor microamps and cleaning
Other brands
- Lennox Merit ML180UH (80% single-stage)
- Carrier 58CVA / 58CVX (80% variable-speed two-stage)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) R96MSN / N96MSN (single-stage 35-in. condensing, 4-way multipoise)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) R95MSU (single-stage Ultra Low NOx condensing, upflow/horizontal, 35 in. tall)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N95ESN / R92ESN (single-stage 35-in. condensing, 4-way multipoise; also PG95ESA)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N92ESN (single-stage 35-in. condensing, 4-way multipoise)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N9MSE (90% single-stage condensing, PSC blower)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N8MSN / N8MSL (80% single-stage, PSC blower)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N80ESU / R80ESU (80% single-stage, ECM blower, Ultra Low NOx, minor series 2 and 3)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N80MSU (80% single-stage, ECM blower, Ultra Low NOx, 3-digit display, minor series 3)
- Rheem / Ruud R96P / 96MDP (96% two-stage condensing, PSC blower; model numbers (-)96P and (-)(-)96MDP, e.g. R96PA0702317MSA)
- Rheem / Ruud R96V / 96MDV (96% two-stage communicating)
- Rheem / Ruud R97V (97% modulating communicating, downflow/horizontal)
- Rheem / Ruud R98V (98% modulating communicating, upflow)
- Goodman / Amana GR9S80 / GD9S80 (80% single-stage)
- Trane / American Standard S9X1 / S9X2 / S9B1 (96% condensing)
- Lennox EL296UHV / SL280UHV control 107045 (Elite EL296UHV(X), EL296DFV(X) and SL280UHV/SL280UHNV/SL280DFV, two-stage, variable-speed, communicating; EL296UH045V36B, EL296UH045XV36B, EL296UH070V36B, EL296UH070XV36B, EL296UH090V36C, EL296UH090XV36C, EL296UH090XV48C, EL296UH090V60C, EL296UH090XV60C, EL296UH110V48C, EL296UH110XV48C, EL296UH110V60C, EL296UH110XV60C, EL296UH135V60D, EL296UH135XV60D, EL296DF045XV36B, EL296DF070V48B, EL296DF070XV48B, EL296DF090V60C, EL296DF090XV60C, EL296DF110V60C, EL296DF110XV60C, SL280UH070V36A, SL280UH070XV36A, SL280UH090V36B, SL280UH090V48B, SL280UH090XV48B, SL280UH090V60C, SL280UH090XV60C, SL280UH110V60C, SL280UH110XV60C, SL280UH135V60D, SL280DF070V36A, SL280DF090V48B, SL280DF090V60C, SL280DF110V60C)
- Lennox EL296UHV / SL280UHV control 103130 (Elite EL296UHV(X), EL296DFV(X) and SL280UHV/SL280UHNV/SL280DFV, earlier units: EL296UH045V36B, EL296UH045XV36B, EL296UH070V36B, EL296UH070XV36B, EL296UH090V36C, EL296UH090XV36C, EL296UH090XV48C, EL296UH090V60C, EL296UH090XV60C, EL296UH110V48C, EL296UH110XV48C, EL296UH110V60C, EL296UH110XV60C, EL296UH135V60D, EL296UH135XV60D, EL296DF045XV36B, EL296DF070V48B, EL296DF070XV48B, EL296DF090V60C, EL296DF090XV60C, EL296DF110V60C, EL296DF110XV60C, SL280UH070V36A, SL280UH070XV36A, SL280UH090V36B, SL280UH090V48B, SL280UH090XV48B, SL280UH090V60C, SL280UH090XV60C, SL280UH110V60C, SL280UH110XV60C, SL280UH135V60D, SL280DF070V36A, SL280DF090V48B, SL280DF090V60C, SL280DF110V60C, SL280UH060NV36A, SL280UH080NV48B, SL280UH080NV60C, SL280UH100NV60C)
- Lennox Elite EL297UHVK(X) / EL297DFVK (two-stage, variable-speed, communicating; upflow/horizontal EL297UH045XV36BK, EL297UH070XV36BK, EL297UH090XV36CK, EL297UH090XV48CK, EL297UH090XV60CK, EL297UH110XV48CK, EL297UH110XV60CK, EL297UH135XV60DK; downflow EL297DF045XV36BK, EL297DF070XV48BK, EL297DF090XV60CK, EL297DF110XV60CK; also Merit SL280UHVK and SL280UHNVK: SL280UH070XV36AK, SL280UH090XV48BK, SL280UH090XV60CK, SL280UH110XV60CK, SL280UH070V36AK, SL280UH090V36BK, SL280UH090V48BK, SL280UH090V60CK, SL280UH110V60CK, SL280UH135V60DK, SL280UH060NV36AK, SL280UH080NV48BK, SL280UH080NV60CK, SL280UH100NV60CK)
- Lennox Signature SLP99UHVK (Dave Lennox Signature, variable capacity, variable speed, communicating: SLP99UH070V36BK, SLP99UH070XV36BK, SLP99UH090V36CK, SLP99UH090XV36CK, SLP99UH090V48CK, SLP99UH090XV48CK, SLP99UH090V60CK, SLP99UH090XV60CK, SLP99UH110V60CK, SLP99UH110XV60CK, SLP99UH135V60DK, SLP99UH135XV60DK)
- Lennox Signature SLP99DFV (Dave Lennox Signature downflow, variable capacity, variable speed, communicating: SLP99DF070XV36B, SLP99DF090XV36C, SLP99DF090XV48C, SLP99DF090XV60C, SLP99DF110XV60C)
- Lennox Elite EL296UHE (96% two-stage, constant torque: EL296UH045XE36B, EL296UH070XE36B, EL296UH090XE48C, EL296UH110XE60C, EL296UH135XE60D; also Elite EL280DFE downflow: EL280DF070E36A, EL280DF090E48B)
- Lennox Elite EL297UHEK (two-stage, constant torque, non-communicating: EL297UH045XE36BK, EL297UH070XE36BK, EL297UH090XE48CK, EL297UH110XE60CK, EL297UH135XE60DK; same control and codes: Elite EL280UHEK and EL280DFEK (80%): EL280UH045E36AK, EL280UH070E36AK, EL280UH070XE36AK, EL280UH090E36BK, EL280UH090E48BK, EL280UH090XE48BK, EL280UH110E48CK, EL280UH110E60CK, EL280UH110XE60CK, EL280DF070E36AK, EL280DF090E48BK)
- Lennox Merit ML196UHEK / Elite EL196UHEK (80% single-stage, constant torque: ML196UH030XE36BK, ML196UH045XE36BK, ML196UH070XE36BK, ML196UH070XE48BK, ML196UH090XE36CK, ML196UH090XE48CK, ML196UH090XE60CK, ML196UH110XE60CK, ML196UH135XE60DK, EL196UH030XE36BK, EL196UH045XE36BK, EL196UH070XE36BK, EL196UH090XE48CK, EL196UH110XE60CK; same control and codes: Elite EL180UHNEK, Merit ML180UHEK, ML193DFEK, Elite EL195UHNEK: EL180UH040NE36AK, EL180UH060NE36AK, EL180UH080NE48BK, EL180UH100NE60CK, ML180UH045E36AK, ML180UH045XE36AK, ML180UH070E36AK, ML180UH070E36BK, ML180UH070XE36BK, ML180UH090E48BK, ML180UH090XE48BK, ML180UH090E60CK, ML180UH110E60CK, ML180UH110XE60CK, ML180UH135E60DK, ML193DF045XE36BK, ML193DF070XE36BK, ML193DF090XE48CK, EL195UH040NE36BK, EL195UH060NE36BK, EL195UH080NE48CK, EL195UH100NE60CK; variable-speed Merit ML180UHVK: ML180UH030V36AK, ML180UH045V36AK, ML180UH070V36AK, ML180UH070V36BK, ML180UH070V48BK, ML180UH090V48BK, ML180UH110V60CK, ML180UH135V60DK)
- Lennox Merit ML196UHE / ML196DFE / ML193UHE (single-stage, red LED controls 103217-03 and 107163-01: ML196UH030XE36B, ML196UH045XE36B, ML196UH070XE36B, ML196UH070XE48B, ML196UH090XE36C, ML196UH090XE48C, ML196UH090XE60C, ML196UH110XE60C, ML196UH135XE60D, ML196DF045XE36B, ML196DF070XE48B, ML196DF090XE48C, ML196DF110XE60C, ML193UH030XE36B, ML193UH045XE36B, ML193UH070XE36B, ML193UH090XE36C, ML193UH090XE48C, ML193UH110XE48C, ML193UH110XE60C; also ML180UHE and ML180DFE: ML180UH045E36A, ML180UH045XE36A, ML180UH070E36A, ML180UH070XE36A, ML180UH070E36B, ML180UH070XE36B, ML180UH090E48B, ML180UH090XE48B, ML180UH090E60C, ML180UH110E60C, ML180UH110XE60C, ML180UH135E60D, ML180DF045E36A, ML180DF070E36A, ML180DF070E36B, ML180DF090E48B, ML180DF110E60C; ML180UHV: ML180UH030V36A, ML180UH045V36A, ML180UH070V36A, ML180UH070V36B, ML180UH070V48B, ML180UH090V48B, ML180UH110V60C; Elite EL195UH (2011): EL195UH045P24B, EL195UH045P36B, EL195UH070P36B, EL195UH070P48B, EL195UH090P36C, EL195UH090P48C, EL195UH090P60C, EL195UH110P48C, EL195UH110P60C, EL195UH135P60D)
- Lennox Merit ML296UHVK / ML296DFVK / ML297UHVK (two-stage, variable-speed; upflow/horizontal ML296UH045XV36BK, ML296UH070XV36BK, ML296UH090XV48CK, ML296UH110XV60CK; downflow ML296DF045XV36BK, ML296DF070XV48BK, ML296DF090XV60CK; ML297UH045XV36BK, ML297UH070XV36BK, ML297UH090XV36CK, ML297UH090XV60CK, ML297UH110XV60CK, ML297UH135XV60DK)
- Lennox SL280UHV (80% two-stage variable speed)
- Goodman / Amana / Daikin GM9S96 / GC9S96 / GM9S92 (96% and 92% condensing, single-stage; also Daikin DM96SN, DM92SN, DC96SN: DM96SN0403AN, DM96SN0603BN, DM96SN0803BN, DM96SN0804CN, DM96SN0805CN, DM96SN1005CN, DM96SN1205DN, DM92SN0403AN, DM92SN0603BN, DM92SN0803BN, DM92SN0804CN, DM92SN0805CN, DM92SN1004CN, DM92SN1005CN, DM92SN1205DN, DC96SN0403BN, DC96SN0603BN, DC96SN0804CN, DC96SN1005CN, DC96SN1205DN)
- Payne PG96VTAB (two-stage condensing, variable-speed, non-communicating, 4-way multipoise)
- Payne PG9YAA / PG9YAB (95% single-stage condensing, direct or non-direct vent)
- Carrier 59TP6C (two-stage condensing with InteliSense, Performance series; also 926TC)
- Lennox G60DF / G60DFV (older two-stage SureLight boards 18M3401, 46M9901, 18M9901, 49M5901)
- Lennox G60UH / G60UHV (SureLight boards 100869 and 100870)
- Rheem / Ruud R801T Ultra Low NOx (14 ng/J) single-stage upflow/horizontal, constant-torque blower
- Rheem / Ruud 802V / 80MDV (80% two-stage communicating, ECM blower; model numbers (-)802V and (-)(-)80MDV)
- Trane / American Standard S8B1 / S8X1 / S8X2 (80% single-stage and two-stage)
- Trane / American Standard A801X060AM3S (80% single-stage, 2024 installation manual)
- Trane / American Standard A801X (80% single-stage: A801X040AM3SD, A801X040BM2SD, A801X060BM4SD, A801X080BM4SD, A801X080CM5SD, A801X100CM5SD, A801X120DM5SD)
- Goodman / Amana GMEC96 / GCEC96 (two-stage, multi-speed ECM: GMEC96, GCEC96, Amana AMEC96, ACEC96)
- Goodman / Amana / Daikin GMSS92 / GMSS96 / GCSS9 (single-stage, 92% and 96%: GMSS92, GMSS96, GCSS92, GCSS96, Amana AMSS92, AMSS96, ACSS92, ACSS96, Daikin VMSS9, VCSS9)
- Goodman / Amana / Daikin GMES92 / GMES96 / GCES96 (single-stage, 92% and 96%: GMES92, GMES96, GCES96, Amana AMES92, AMES96, ACES96, Daikin VMES96, VCES96)
- Goodman / Amana GM9C96 / GC9C96 (two-stage, nine-speed ECM: GM9C96, GC9C96, Amana AM9C96, AC9C96)
- Goodman / Amana GMH8 / GDH8 / GME95 (modified two-stage: 80% GMH8, GDH8, Amana AMH8, ADSH8; 95% GME95, Amana AMEH96)
- Goodman / Amana / Daikin GMS8 / GDS8 (80% single-stage: GMS8, GDS8, Amana AMS8, ADSS8, Daikin VMS8, VDS8)
- Goodman / Amana GMES96 U Ultra-Low NOx (single-stage 96%, U models: GMES96, Amana AMES96)
- Goodman / Amana GM9S96 U Ultra-Low NOx (single-stage 96%, U models: GM9S96, Amana AM9S96; Daikin DM96SN U: DM96SN0403BU, DM96SN0603BU, DM96SN0805CU)
- Goodman / Amana GMVS80 U Ultra-Low NOx (80% single-stage, variable-speed communicating: GMVS80, Amana AMVS80)
- Goodman / Amana GKS9 / AKSS92 (92% single-stage upflow: GKS9, Amana AKSS92)
- Goodman / Amana GMVM97 / GCVM97 ComfortBridge (97% modulating, BA revision and later: GMVM97, GCVM97, Amana AMVM97, ACVM97)
- Goodman / Amana GMVC96 / GCVC96 (96% two-stage variable-speed, *MVC96*BA and *CVC96*BA)
- Goodman / Amana GMVC96 / GCVC96 BB ComfortBridge (96%, BB revision: GMVC96, GCVC96, Amana AMVC96, ACVC96)
- Goodman / Amana / Daikin AMVC96 / DM96VC / DM80VC ComfortNet (two-character codes: AMVC96, ACVC96, GMVC96, GCVC96 before the BA revision; DM96VC0403BN, DM96VC0603BN, DM96VC0803BN, DM96VC0804CN, DM96VC1005CN, DM96VC1005DN, DM96VC1205DN, DC96VC0403BN, DC96VC0603BN, DC96VC0803BN, DC96VC0804CN, DC96VC1005CN, DC96VC1205DN, DM80VC0603B, DM80VC0604B, DM80VC0805C, DM80VC1005C, DD80VC0603B, DD80VC0805C, DD80VC1005C)
- Goodman / Amana GMVS96 / AMVS96 U-revision (96% variable-speed with analog pressure sensor, model numbers GMVS96*U and AMVS96*U; also Daikin DM96SC U: DM96SC0603BU, DM96SC0805CU)
- Goodman / Amana GMVM96 / GCVM96 / AMVM96 / ACVM96 (96% modulating, model numbers *MVM96 and *CVM96; also Daikin DM97MC/DC97MC: DM97MC0603BNA, DM97MC0803BNA, DM97MC0804CNA, DM97MC1005CNA, DM97MC1205DNA, DC97MC0603BNA, DC97MC0803BNA, DC97MC0804CNA, DC97MC1005CNA)
- Rheem / Ruud R801T / 80MSX (80% single-stage, constant-torque blower; model numbers (-)801T and (-)(-)80MSX)
- Rheem / Ruud 802P / 80MDP (80% two-stage, model numbers (-)802P and (-)(-)80MDP)
- Rheem / Ruud 802T / 80MDT (80% two-stage with constant-torque blower, model numbers (-)802T and (-)(-)80MDT)
- Rheem / Ruud 801S / 801P / 80MSS / 80MSP (80% single-stage, model numbers (-)801S, (-)801P, (-)(-)80MSS and (-)(-)80MSP)
- Rheem / Ruud W801T (Rheem Select 80% downflow single-stage)
- Rheem / Ruud R951T / R95T / R92T (90%+ single-stage condensing, constant-torque blower; model numbers (-)951T, (-)95T, (-)(-)95MSX, (-)92T, (-)(-)92MSX, e.g. R95TC0701317MSA, R92TC0701317MSA)
- Rheem / Ruud 801V Ultra Low NOx (80% communicating, constant CFM blower, upflow/horizontal)
- Carrier 58STA / 58STX (80% single-stage, 4-way multipoise; also 313AAV, 313JAV)
- Carrier 58CTA / 58CTX (80% two-stage, 4-way multipoise, Series 140/E)
- York TG9S (95.5% AFUE single-stage PSC, multi-position)
- York TM9T (96% AFUE two-stage PSC, multi-position)
- York TM9X (95.5% AFUE single-stage ECM, multi-position: TM9X040A10MP11, TM9X060B12MP11, TM9X080B12MP11, TM9X080C16MP11, TM9X100C16MP11, TM9X100C20MP11, TM9X120D20MP11)
- York TM9M (97% AFUE modulating PSC, multi-position)
- York YP9C / TP9C / CP9C / LP9C (up to 98% AFUE modulating ECM, multi-position)
- York TM9V (96% AFUE two-stage variable-speed ECM, multi-position)
- York UTEC Board (single- and two-stage furnaces from August 2009; SAP 539617, 542760, 542767, 542766; Source 1 S1-33102956000, S1-03102951001, S1-33102954000, S1-33102955000)
- York White-Rodgers Board (the generation before the 2009 UTEC boards; 265901, S1-33109167000 / 265902, S1-33109168000 / 265903, S1-33109169000 / 265904)
- York TI Board (older furnaces; 031-01972-000 TI 6DT-1, 031-01973-000 TI 6DT-2, 031-09117-000 TI 6MD-1, 031-09118-000 TI 6MI-1)
- Carrier 58TN0A / 58TN1A (80% two-stage, variable-speed, 4-way multipoise; also 880TA, 881TA)
- Carrier 58TN0B / 58TN1B (80% two-stage, variable-speed, 4-way multipoise)
- Carrier 58TP0A / 58TP1A (80% two-stage, variable-speed ECM, 4-way multipoise; also PG80VTLA)
- Carrier 58TP0B / 58TP1B InteliSense (80% two-stage, variable 25-speed ECM, 4-way multipoise)
- Carrier 59SC5A (single-stage condensing, 4-way multipoise; also 912SB, 912SC, 922SA, 925SA, PG92SAS, PG92SCS, PG95SAS)
- Bryant 925TA (two-stage condensing, 4-way multipoise; also PG95XAT)
- Bryant 926SA (single-stage condensing, multi-speed ECM, multipoise)
- Bryant 926SB (single-stage condensing, 25-speed ECM, InteliSense)
- Carrier 59SC5B / 59SC2D (single-stage 35-in. condensing, 4-way multipoise; also 912SD, 915SB)
- Carrier 59MN7A / 59MN7B (modulating condensing, 4-way multipoise; also 987MA, 987MB)
- Carrier 59MN7C modulating condensing (59MN7C060C17, 59MN7C060C21, 59MN7C080C17, 59MN7C080C21, 59MN7C100C21, 59MN7C120C24; also 987MC)
- Carrier 59TP6B / 59TP6A / 59TN6A two-stage (condensing, two-digit codes; also 926TA, 926TB, 986TB, PG96VAT, PG96VTAA)
- Carrier 59TN6B two-stage condensing (variable-speed: 59TN6B060C17, 59TN6B080C17, 59TN6B080C21, 59TN6B100C21, 59TN6B120C24; also 986TC)
- Carrier 59TN6C two-stage condensing (variable-speed, 35 in. tall: 59TN6C040C14, 59TN6C060C17, 59TN6C080C17, 59TN6C080C21, 59TN6C100C21, 59TN6C120C24)
- Carrier 59SU5A (single-stage Ultra Low NOx condensing, upflow/horizontal, 35 in. tall)
- Carrier 59SU5B single-stage Ultra Low NOx (condensing, 35 in. tall: 59SU5B040M17, 59SU5B060M17, 59SU5B080M21, 59SU5B100M21; also PG95MSUA)
- Carrier 59TP7A two-stage InteliSense (condensing, variable-speed, non-communicating: 59TP7A060V17, 59TP7A080V17, 59TP7A080V21, 59TP7A100V21, 59TP7A120V24)
- Carrier 59SC2E / 59SC6A (single-stage 35-in. condensing, 4-way multipoise; also 912SE, PG96MSAA)
- Carrier 58CU0A (80% communicating, Ultra Low NOx, 4-way multipoise)
- Carrier 58SU0A (80% single-stage, ECM blower, Ultra Low NOx, 4-way multipoise; also 830SA)
- Carrier 58SU0B (80% single-stage, ECM blower, Ultra Low NOx, 3-digit display)
- Carrier 58SB0B / 58SB1B / 58SC0B / 58SC1B (80% single-stage, multi-speed ECM, 4-way multipoise; also PG80MSA, PG80MSLA)
- Bryant 820SA / 821SA (80% single-stage, 4-way multipoise)
- Carrier 58SB0A / 58SB1A / 58SC0A / 58SC1A (single-stage, non-condensing; 58SC is the multi-speed ECM version; also 800SA, 801SA, PG80ESAA, PG80ESLA)
Did you find your code?
One field tip a week
A short, practical HVAC tip in your inbox every week: diagnostics, charging, airflow and code changes. Free, unsubscribe anytime.
We'll only use your email for the newsletter. Privacy policy.
HVAC Cheat Sheet · Free PT charts, code lookups and calculators for techs at hvaccheatsheet.com